You are on page 1of 12

SIL-A

O/C& E/F Line Protection

Overcurrent & Earth Fault Protection

Primary & Secondary Distribution Protection Relay

5
Five year
guarantee
fanox.com
SIL-A
Overcurrent & Earth Fault Protection Relay
for Primary & Secondary Distribution
Line Protection Relay

ANSI CODE PROTECTIONS

50 Instantaneous phase overcurrent

51 Inverse time phase overcurrent

Instantaneous calculated neutral


50N
overcurrent
Instantaneous measured neutral
50G
overcurrent
Inverse time calculated neutral
51N
overcurrent
Overcurrent & Earth Fault Protection Relay
Inverse time measured neutral
51G
overcurrent Line Protection for Primary and Secondary Distribution
46 Phase balance current protection

46BC Broken Conductor Detection • The SIL-A is an overcurrent and earth fault protection relay for primary
and secondary distribution with auxiliary power supply 24-230 Vac/dc. The
Instantaneous phase current measurement is obtained either by standard current transformers /1
37
undercurrent or /5, or by special Low Power Current Transformers (LPCT).
74CT Phase CT supervision • Many protection functions: 50_1, 50/51, 50N/G_1, 50/51N/G, 52, 46, 79,
74TCS, CLP, 86, 49T and optionally 50_2, 50N/G_2, 49, 74CT, 37, 46BC,
49 Thermal overload 50BF, TB and SHB.

SHB Second Harmonic Blocking • Metallic box with high electromagnetic compatibility level (EMC) and wide
range of operating temperature.
52 Breaker Wear Monitoring
• Direct signalling/control of the circuit breaker (52 function) and the recloser
(79 function).
50BF Circuit breaker failure
• Zone selection interlocking (68 function) is available through configurable
74TCS Trip Circuit Supervision inputs and outputs thanks to the programmable logic (PGC).

79 AC Reclosing device • To allow the communication, relays are provided with a local RS232
front port and with remote communication with different options (ports and
CLP Cold Load Pickup protocols) on the rear side:

49T External Trip  1 RS485 Port: IEC60870-5-103, Modbus RTU or DNP3.0


Serial (selectable by general settings).
86 Trip lockout
 1 RJ45 Port: IEC61850, Modbus TCP/IP, DNP3.0 TCP/IP
or IEC60870-5-104 (selectable by general settings).
68 Zone selection interlocking

Trip block for switch • The SIL-A has configurable and dedicated inputs and outputs, depending
TB on adaptation:
disconnector

PGC Programmable logic control  Adaptation “B”: 6 configurable Digital Inputs and 4
configurable Digital Outputs.

 Adaptation “C”: 4 configurable Digital Inputs, 2 dedicated


Digital Inputs and 4 configurable Digital Outputs.

2
• SIL-A is fitted with the demand of current (Load Data Profiling) with the following characteristics:

 Number of records: 168.

 Recording mode circular.

 Sampling rate (interval): configurable through communications (1-60 min).

• SIL-A is provided with non-volatile RAM memory in order to store up to 200 events and disturbance fault recording
(DFR - 20 fault reports and 5 oscillographic records in COMTRADE format), maintaining date & time thanks to its internal
RTC (real Time Clock).

•The oscillography is downloaded by communications port. The SICom communications program allows the oscillography
record to be downloaded and saved in COMTRADE format (IEEE C37.111-1991).

3
Function Diagram SIL-A

BUS

3
50 51 49* SHB* 49T* 37* 46BC* 46 74CT*

ANSI CODE PROTECTIONS


50N* 51N* TB* 50BF* CLP

50 Instantaneous phase overcurrent

1 51 Inverse time phase overcurrent


50G* 51G*

Instantaneous calculated neutral


50N
overcurrent
Instantaneous measured neutral
50G
overcurrent
52 Inverse time calculated neutral
51N
* optional
overcurrent
79 52 74TCS 68 86
Inverse time measured neutral
51G
1
overcurrent
RS232
46 Phase balance current protection
CNT RTC ALRM PGC HMI SER 1
RS485

46BC Broken Conductor Detection


LDP MET STTG CMMD DFR 1
ETHERNET *
LINE Instantaneous phase
37
undercurrent

74CT Phase CT supervision

ADDITIONAL FUNCTIONS 49 Thermal overload

CNT Counters SHB Second Harmonic Blocking

RTC Real Time Clock 52 Breaker Wear Monitoring

ALRM Alarm panel 50BF Circuit breaker failure


Programmable Logic
PGC 74TCS Trip Circuit Supervision
Control

HMI Human Machine Interface 79 AC Reclosing device

SER Sequential Event Recording CLP Cold Load Pickup


Disturbance Fault
DFR 49T External Trip
Recording

LDP Load Data Profiling 86 Trip lockout

MET Metering 68 Zone selection interlocking

Trip block for switch


STTG Settings Groups TB
disconnector
CMMD Commands PGC Programmable logic control

4
Technical parameters SIL-A

Function enable: Function enable:


- Adaptation “B”: Yes/No - Adaptation “B”: Yes/No
- Adaptation “C”: Yes/No/SHB - Adaptation “C”: Yes/No/SHB
Current tap: 0.10 to 30 xIn (step 0.01 Curve Type: IEC 60255-151 and IEEE
xIn) curves.
Time delay: Curve type: IEC Inverse curve, IEC
- Adaptation “B”: 0.02 to 300 s (step very inverse curve, IEC extremely
0.01 s) inverse curve, IEC long time inverse,
Function 50_1 - Adaptation “C”: 0.00 to 300 s (step IEEE Inverse curve, IEEE very inverse
0.01 s) curve, IEEE extremely inverse curve,
Function 50_2 (*) Defined Time:
Activation level: 100% Time delay:
Deactivation level: 95% - Adaptation “B”: 0.02 to 300 s (step
0.01 s)
Instantaneous deactivation - Adaptation “C”: 0.00 to 300 s (step
0.01 s)
Timing accuracy:
- If Time delay 0.00 to 0.02 s: ± 50 ms Time dial (TMS): 0.02 to 2.20 (step
or ± 0.5% Function 50/51_1 0.01)
- If Time delay 0.02 to 300 s: ± 30 ms
or ± 0.5% Current Tap: 0.10 to 7 xIn (step 0.01
Function 50/51_2 (*) xIn)
Function enable:
Curve, activation level: 110%
- Adaptation “B”: Yes/No
- Adaptation “C”: Yes/No/SHB Curve, deactivation level: 100%
Current tap: Defined time, activation level: 100%
- Adaptation “B”: 0.10 to 30 xIn (step
0.01 xIn) Defined time, deactivation level: 95%
- Adaptation “C”: 0.05 to 30 xIn (step Instantaneous deactivation
0.01 xIn)
Timing accuracy for IEC and IEEE
Time delay: curves selection:
- Adaptation “B”: 0.02 to 300 s (step ± 30 ms or ± 5% (greater of both).
Function 50N/G_1 (*)
0.01 s)
- Adaptation “C”: 0.00 to 300 s (step
Function 50N/G_2 (*) Timing accuracy for defined time
0.01 s)
curve selection:
Activation level: 100% - If Time delay 0.00 to 0.02 s: ± 50 ms
or ± 5%
Deactivation level: 95% - If Time delay 0.02 to 300 s: ± 30 ms
or ± 5%
Instantaneous deactivation
Function enable:
Timing accuracy:
- Adaptation “B”: Yes/No
- If Time delay 0.00 to 0.02 s: ± 50 ms
or ± 0.5% - Adaptation “C”: Yes/No/SHB
- If Time delay 0.02 to 300 s: ± 30 ms Curve Type: IEC 60255-151 and IEEE
or ± 0.5% curves.
Function enable: Yes/No Curve type: IEC Inverse curve, IEC
very inverse curve, IEC extremely
Tap: 0.10 to 2.40 xIn (step 0.01xIn)
inverse curve, IEC long time inverse,
ζ heating: 3 to 600 min (step 1 min) IEEE Inverse curve, IEEE very inverse
curve, IEEE extremely inverse curve,
ζ cooling: 1 to 6 x ζ heating (step 1) Defined Time:
Time delay:
Alarm: 20 to 99% (step 1%)
- Adaptation “B”: 0.02 to 300 s (step
Trip level: 100% 0.01 s)
Function 49 (*) - Adaptation “C”: 0.00 to 300 s (step
Trip reset: 95% of alarm level 0.01 s)
Timing accuracy: ± 5% respect of Time dial (TMS): 0.02 to 2.20 (step
theorical value. 0.01)
Trip time curves are valid under 20 Function 46 (*) Current tap: 0.10 to 7 xIn (step 0.01
times the adjusted tap. With currents xIn)
higher than 20 times the adjusted tap,
trip time and thermal image value are Curve, activation level: 110%
truncated to 20 times the adjusted
tap. Curve, deactivation level: 100%

Function enable: Yes/No Defined time, activation level: 100%

Current tap: 5% to 50% (step 1%) Defined time, deactivation level: 95%

Reset time: 0.00 to 300 s (step 0.01 s) Instantaneous deactivation

Block threshold: 0.10 to 30.00 xIn Timing accuracy for IEC and IEEE
Function SHB (*) curves selection:
(step 0.01 xIn)
± 30 ms or ± 5% (greater of both).
Activation level: 100%
Timing accuracy for defined time
Deactivation level: 95% curve selection:
Temporized deactivation - If Time delay 0.00 to 0.02 s: ± 50 ms
or ± 5%
- If Time delay 0.02 to 300 s: ± 30 ms
or ± 5%

5
Technical parameters SIL-A
Function enable: Function enable: Yes/No
- Adaptation “B”: Yes/No
- Adaptation “C”: Yes/No/SHB Number of recloses: 1 to 5 (step 1)

Curve Type: IEC 60255-151 and IEEE Reclosing time: 0.02 to 300 s (step
curves. 0.01 s)

Curve type: IEC Inverse curve, IEC Hold enable: Yes/No/No time
Function 79
very inverse curve, IEC extremely Hold time: 0.02 to 300 s (step 0.01 s)
inverse curve, IEC long time inverse,
IEEE Inverse curve, IEEE very inverse Reset time: 0.02 to 300 s (step 0.01 s)
curve, IEEE extremely inverse curve,
Defined Time: Safe time: 0.02 to 300 s (step 0.01 s)
Time delay: Locking possibilities: pulse inputs,
- Adaptation “B”: 0.02 to 300 s (step level inputs, commands.
0.01 s)
- Adaptation “C”: 0.00 to 300 s (step Maximum number of openings: 1 to
0.01 s) 10000 (step 1)

Time dial (TMS): 0.02 to 2.20 (step Max. accumulated amps: 0 to 100000
0.01) (M(A²)) (step 1)

Current tap: Maximum number of repetitive


Function 50/51N/G (*) - Adaptation “B”: 0.10 to 7 xIn (step openings: 1 to 10000 (step 1)
0.01 xIn)
Time of repetitive openings: 1 to 300
- Adaptation “C”: 0.05 to 7 xIn (step min (step 1 min)
0.01 xIn) Function 52
Maximum opening time 0.02 to 30 s
Curve, activation level: 110% (step 0.01 s)
Curve, deactivation level: 100% Maximum closing time 0.02 to 30 s
Defined time, activation level: 100% (step 0.01 s)

Defined time, deactivation level: 95% Open circuit breaker activation


threshold: 8% In
Instantaneous deactivation
Open circuit breaker reset threshold:
Timing accuracy for IEC and IEEE 10% In
curves selection:
± 30 ms or ± 5% (greater of both). Function enable: Yes/No
Time delay: 0.02 to 300 s (step 0.01 s)
Timing accuracy for defined time
curve selection: Continuity in circuits A and B
- If Time delay 0.00 to 0.02 s: ± 50 ms Function 74TCS
or ± 5% Inputs:
- If Time delay 0.02 to 300 s: ± 30 ms - Adaptation “B”: Configurable digital
or ± 5% inputs
- Adaptation “C”: Dedicated digital
Function enable: Yes/No inputs
Settings group: 1 to 4 (step 1) Function enable: Yes/No

Function CLP No load time: 0.020 to 300.000 s (step Time delay: 0.02 to 300 s (step 0.01 s)
Function 74CT (*)
0.001 s)
Timing accuracy: ± 30 ms or ± 0.5%
Cold load time: 0.020 to 300.000 s (greater of both).
(step 0.001 s)
Function enable: Yes/No
Function enable: Yes/No
Time delay: 0.02 to 1.00 s (step 0.01
Current tap: 15 to 300 xIn (step 0.01 s)
xIn)
Open circuit breaker activation
Function 50BF (*)
Time delay: 0.00 to 300 s (step 0.01 s) threshold: 8% In
Activation level: 100% Open circuit breaker reset threshold:
Function 46BC (*) 10% In
Deactivation level: 95%
Configurable function pickup
Timing accuracy:
- If Time delay 0.00 to 0.02 s: ± 50 ms Function enable: Yes/No
or ± 0.5% Function TRIP BLOCK (*)
- If Time delay 0.02 to 300 s: ± 30 ms Current tap: 1.5 to 20 xIn (step 0.01)
or ± 0.5% Available through configurable
Function enable: Yes/No Function 86 inputs and outputs thanks to the
programmable logic (PGC).
Current tap: 0.10 to 30 xIn (step 0.01
xIn) Available through configurable
Function 68 inputs and outputs thanks to the
Time delay: 0.02 to 300 s (step 0.01 s) programmable logic (PGC).
Activation level: 100% OR4, OR4_LATCH, OR4_PULSES,
OR4_TIMERUP, OR4_PULSE, NOR4,
Function 37 (*) Deactivation level: 105% NOR4_LATCH, NOR4_TIMERUP,
Programmable logic control (PGC) NOR4_PULSE, AND4, AND4_
Instantaneous deactivation
PULSES, AND4_TIMERUP, AND4_
Timing accuracy: PULSE, NAND4, NAND4_TIMERUP,
- If Time delay 0.00 to 0.02 s: ± 50 ms NAND4_PULSE.
or ± 0.5% 4 settings groups
- If Time delay 0.02 to 300 s: ± 30 ms Settings Groups
or ± 0.5% Selectable by input or general setting

6
Technical parameters SIL-A

Sequential Events Recording Local port (RS232 DB9): Modbus RTU


200 events
(SER)
1 remote port with the following
16 samples/cycle options
- 1 Remote port RS485: ModBus RTU,
Fault start configurable IEC 60870-5-103 or DNP3.0 Serial, by
Communications model/settings.
20 fault reports with 24 events each
one - 1 Remote port RJ45: IEC 61850,
DNP3.0 TCP/IP, Modbus TCP/IP or
Disturbance fault recording (DFR) 5 COMTRADE records (100 cycles): 3 IEC 60870-5-104, by model/settings.
pre-fault cycles + 97 postfault cycles. (IEC 60870-5-104 only for adaptation
“B”)
COMTRADE IEEE C37.111-1991:
- Adaptation “B”: 4 analog channels Power supply 24-230 Vdc / Vac -20%/+10%
and 48 digital channels
- Adaptation “C”: 4 analog channels Operating temperature: -10 to 70ºC
and 36 digital channels Environmental conditions Storage temperature: -20 to 80 ºC
Demand of current with the following Relative humidity: 95%
characteristics:
- Number of records: 168 Measurement 3 or 4 CT /5 or /1
- Recording mode circular (depending on model)
- Sampling rate (interval): configurable Transformers Measurement 3 LPCT (current
through communications (1-60 min)
transformers with voltage output.
Load Data Profiling (LDP) - Record format: (only for adaptation “B”)
Date/Time
IMAX (in interval) Metallic box
Imax (at the moment of
the record) Panel mounted
IA Height x Width: 177 x 107 (mm)
IB Mechanical characteristics
IC Depth: 122.1 mm
IN
IP-54
Same voltage as the auxiliary power
Weight: 1,5 kg
supply:
Inputs - Adaptation “B”: 6 configurable DI (*) Optional depending on model
- Adaptation “C”: 4 configurable DI +
2 dedicated DI
4 Configurable outputs
250 V AC – 8 A
Outputs 30 V DC – 5 A
Output 1 and Output 2: NC - NO
Output 3 and Output 4: NO
Frequency 50/60Hz
Adaptation “B”:
- Phase current (IA, IB, IC), neutral
(IN), positive sequence (I1), negative
sequence(I2), maximum current (Imax)
and thermal image (TI)
Adaptation “C”:
- Phase current (IA, IB, IC), neutral
(IN), positive sequence (I1), negative
sequence(I2), phase second harmonic
current (IA-2H, IB-2H and IC-2H),
maximum current (Imax) and thermal
image (TI)

Current measurements Fundamental values (DFT)


Sampling: 16 samples/cycle
Measurement accuracy:
- Adaptation “B”: ±2% accuracy over
a band of ±20% over the nominal
current and 4% over the rest of the
range
- Adaptation “C”: ±2% Accuracy over
a band of ±20% over the nominal
current and 4% or ±5 mA (greater of
both) over the rest of the range
Saturation limit: 30 times rated current

7
Technical parameters SIL-A

3 LPCT transformers

C
SILA
Overcurrent & Earth Fault relay
ETH*

Power Supply
24-230 Vac/dc

3 LPCT Transformers

(*) Example of connections diagram

LPCT

8
Connection diagram SIL-A

3 Standard current transformers

C
C

C
C SILA
SILA
Overcurrent & Earth Fault relay
Overcurrent & Earth Fault relay
ETH*

ETH*
C

C
SILA
Overcurrent & Earth Fault relay Power Supply
Power Supply 24-230 Vac/dc
24-230 Vac/dc
ETH*

3 LPCT Transformers 3 Standard Current Transformers

Power Supply
24-230 Vac/dc

LPCT
3 Standard Current Transformers
4 Standard current transformers

SILA
Overcurrent & Earth Fault relay
ETH*

Power Supply
24-230 Vac/dc

4 Standard Current Transformers


9
C
Dimmensions and cutout SIL-A

107

18.5 70 18.5
18.5

8
161

177

161
8

8
18 5

100
122.1
120.3
106

105

17.5 70 17.5
Ø7 Ø7
4

CUTOUT
153
161
4

Ø7 Ø7

10
Selection & Ordering data SIL-A
Overcurrent & Earth Fault Protection
SIL-A
Relay for Primary & Secondary Distribution
PHASE CURRENT MEASUREMENT
X LPCT (Primary In = 50 – 800 A)
0 Standard: 1 A or 5 A
S Sensitive 0.5 A or 2.5 A
NEUTRAL CURRENT MEASUREMENT
X LPCT (Neutral internally calculated).
0 Standard: 1 A or 5 A
S Sensitive 0.5 A or 2.5 A
NET FREQUENCY
0 Defined by General Setting
POWER SUPPLY
C 24-230 Vac/dc
ADDITIONAL FUNCTIONS
0 -
2 + 49 + 74CT + 37 + 46BC + Trip Block
4 + 49 + 46BC + SHB (Available only for Adaptation ‘C’)
COMMUNICATIONS
A RS232 (Modbus RTU) + RS485 (Modbus RTU or IEC 60870-5-
103)
B RS232 (Modbus RTU) + RJ45 (IEC 61850)
C RS232 (Modbus RTU) + RJ45 (IEC 60870-5-104)
7 RS232 (Modbus RTU) + RS485 (Modbus RTU or DNP3.0 serial)
8 RS232 (Modbus RTU) + RJ45 (Modbus TCP/IP or DNP3.0 TCP/
IP)
INPUTS AND OUTPUTS
1 6 Inputs + 4 Outputs
MECHANICAL ASSEMBLY
2 Vertical Assembly
LANGUAGE
A English, Spanish and German
B English, Spanish and Turkish
C English, Spanish and French
E English, Turkish and Russian
ADAPTATION
B Default Functions: 50_1 + 50_2 + 50/51 + 50N/G_1 + 50N/G_2
+ 50/51N/G + 52 + 50BF + 46 + 79 + 74TCS + CLP + 86 + 49T
C Default Functions: 50 + 50/51 + 50N/G + 50/51N/G + 52 + 46
+ 79 + 74TCS (with dedicated inputs) + CLP + 86 + 49T

Example of ordering code:

SIL-A 0 0 0 C 2 A 1 2 A B SIL A 0 0 0 C 2 A 1 2 A B