cooling load
R. TONS BTU/H Kcal/h
(kW)
Building fabric and reasonable solar gains (sensible) 3.3 0.94 11243.61 2810.90
Fresh air and infiltration gains (sensible) 0.25 0.07 851.79 212.95
Lighting gains (sensible) 0.54 0.15 1833.90 458.48
Personnel gains (sensible) 0.375 0.11 1277.68 319.42
Fresh air and infiltration gains (latent) 0.15 0.04 511.07 127.77
Personnel gains (latent) 0.125 0.04 425.89 106.47
IT Equipment (sensible) 0 0.00 0.00 0.00
x x x x x
Sensible Cooling Capacity Required 4.46 1.27 15206.98 3801.75
Latent Cooling Capacity Required 0.275 0.08 936.97 234.24
Sensible + Latent Cooling Capacity 4.74 1.35 16143.95 4035.99
Mixed air temperature=[(Air volume required for ventilation/Supply air volume required) x Outside temperature
Mixed air temperature (C) 22.52
volume required) x Room temperature)] or Tm=((Vo/Vs) x To) + ((Vr/Vs) x Tr)
Room temperature (C) 22.00 x x x
COIL ∆T (F) 17.02 x x x
COIL ∆T (C) 9.46 x x x
Supply air temperature (F) 55.52 x x x
Mixed air temperature (F) 72.54 x x x
Cooling load
Equation
volumex30W
volumex5W
Area (sq. m) x 21.53
No. of Persons x gain 75W
volumex3W
No. of Persons x gain 25W
Same total IT load power (W)
x
sum of sensible loads
sum of latent loads
sensible + latent
Sensible Cooling Capacity+ Sensible heat from
fan motor
sum of latent loads
Total Sensible Cooling Capacity Required + Total
Latent Cooling Capacity Required
x
Cooling load
x
x
x
Supply air temp. = Room temp. - [(sensible heat gain without ventilation(kcal/h) / supply air volume(m3/h) x 0.3)] or V=Hs'/0.3x(tr-ts) or ts=tr-Hs'/V
x 0.3
x
x
x
x
x
x
x
x
Mixed air temperature=[(Air volume required for ventilation/Supply air volume required) x Outside temperature)]+[(Room air volume/Supply air
volume required) x Room temperature)] or Tm=((Vo/Vs) x To) + ((Vr/Vs) x Tr)
x
x
x
x
x
Air Cycles
extract air to outside Supply air Airconditioning unit Fresh air from outside
Mixing
22 C 13.0658053664096 C 22.5227879534719 C 36 C
coil
Room
29.4117647058824
788.09122755 CFM 788.09122755 CFM 29.4117647058824 CFM
CFM
← ← ← ←
↓ ↑
22 C
Return air
→ 758.679462844118 CFM →