Professional Documents
Culture Documents
Firmware
v2.61 (changes from v2.60).
1. Fix - BACnet MSTP - UART stops listening (receiving) if frequent who-has broadcasts are received
ViewPoint HD Viewer
v2.16
1. No Changes
Localization File
9/9/2022
1. No Changes
Register List
9/9/2022
1. No Changes
User Manual
9/9/2022
1. No Changes
Hardware
1. No Changes
ViewPoint HD Viewer
v2.16 (Changes since 2.15).
2. Changed data tables to suppress “disabled or off” channels
3. Changed Power Page aPF to dPF (more effective at correcting CT phasing issues)
4. Improved Charting behavior (Harmonics and Phasor Plots)
5. Relocated Meter Clock Setting to Meter Setup Page
Localization File
10/10/2020
1. Updated images to include Part # in CT Picker photo (customer request)
Register List
10/10/2020
2. Changed Definition of object 2377 (System Phase Check). This register and BACnet object are now Boolean
system variables.
User Manual
10/10/2020
2. No Changes
Hardware
2. MD24/48 Power Supply Revision (I) for Improved Surge Immunity
Distribution Release 6/30/2020
Firmware
v2.50 (changes from v2.07).
ViewPoint HD Viewer
v2.15 (Changes since 2.14).
1. Reworked Alarm configuration page (removed all alarm types except under-voltage)
2. Remove unsupported data formats in RS485 setup
3. Introduced range restrictions on voltage scaling factors (eliminate safety concerns for entering a 0)
4. Minor Bug fixes & performance enhancements
Localization File
06/30/2020
1. Re-Order CT Picker to move most common CT types to the top of the list
Register List
06/30/2020
1. Added documentation for missing (unused) registers within each organizational block
2. Added User Configuration Register 2296 for Control of Web Page Access
3. Moved RTC Register from 2501/2502 2489/2490
4. Removed Alarm and Trigger Registers for Current: 2245,2246, 2452, 2455,2456
5. Removed Pulse Output Registers 2279-2290
User Manual
06/30/2020
1. No Changes
ViewPoint HD Viewer
v2.14 (Changes since 2.13).
Localization File
09/01/2019
1. No changes
Register List
09/01/2019
1. No changes
User Manual
09/01/2019
1. No changes
Distribution Release 6/15/2019
Firmware
v2.06 (changes from v2.04). v2.05 – a provisional release to a specific customer
ViewPoint HD Viewer
v2.13 (Changes since 2.11). v2.12 - a provisional release to a specific customer
Localization File
06/15/2018
1. No changes
Register List
06/15/2019 (Changes since 12/31/2018)
1. Change name of Modbus and BACnet object 1141 from “Current Sum Element” to “Current Avg Element”
2. Remove BACnet objects for WEC (used by ViewPoint HD)
3. Added User Configuration Register 2296 (Reserved for Future Use)
4. Added Factory Configuration Register for Meter Feature Control (not public)
5. Added Data format notes to Alarm Enable Mask Register 2452
User Manual
06/15/2019 (Changes since 12/31/2018)
1. No changes
Distribution Release 12/31/2018
Firmware
v2.04 (changes from v2.03)
1. Correct bug in web page configuration, CT type for CH2 now correctly indicated.
2. Allow changes to Modbus Address from LCD to take effect without power cycle.
3. DHCP renewal (meter response to power cycle of DHCP server).
4. Clear Alarm bits when alarm is disabled.
5. Improve compatibility with SunSpec Discovery Tools.
6. Correct LCD display of model number in “About Meter”.
7. Improve numeric auto-scaling for LCD display.
8. Improve meter response to “Clear Demand” user entry.
9. Add 20msec delay to meter response to modus function 17 “Report Slave ID”.
10. Add BACnet object [2248] for “Power Factor Sign Convention”.
11. Corrected swapped channel behavior for CT Flipper 2 & 3.
12. Corrected avg voltage calculation for Veris Emulation [Register #6].
13. Removed menu item for changing modbus port in LCD (fixed at 502).
14. Corrected RoCoil Snap To Zero behavior (was using mV snap setting).
15. Corrected RoCoil amperage reporting where CT range register was not updated (non ViewPoint entry).
16. Removed Modbus entry field from Web Page.
17. Corrected errant character in modbus function 17 “Report Slave ID” in Veris emulation mode.
ViewPoint HD Viewer
v2.11 (Changes since 2.10)
1. Remove modbus port conflict causing USB connectivity issues with meter.
2. Allow Viewer application to be minimized.
3. Remove IP address range restrictions when connecting to meters.
4. Correct refresh behavior on Waveform Capture Page.
Localization File
06/01/2018
1. No changes
Register List
12/31/2018 (Changes since 6/01/2018)
User Manual
12/31/2018 (Changes since 6/01/2018)
1. Introduction
a. Updated meter anatomy drawings (change pulse outputs to pulse inputs).
b. Updated UL logo to include E File number.
2. Meter Installation
a. Updated Video Table to include more descriptive language of video content.
b. Remove specific video hyperlinks in favor of top menu link (better maintainability).
3. Communication & Verification
a. Updated Section on Pulse Outputs (discontinued).
b. Update section on Pulse Inputs.
4. RTU Programming & Scripting
a. Corrected Error in Register Template Table.
b. Updated Supported Modbus Command Table.
c. Updated Modbus String Entry Section (including examples).
d. Added Section on Floating Point Register Entry (including examples).