You are on page 1of 8

1 2 3 4 5 6 7 8 9 10

REV 0
F F
PV7482SC

E E
FILE NAME:

DRG. NO.

D D
IF IN DOUBT, ASK

C C
CG Power and Industrial Solutions Limited

B B
All information contained in this document
is confidential and should not be used
without prior consent of

1 2 3 4 5

A 4 NAME DATE
COVERSHEET DRN. ADS 04.05.23 W.O.NO. PV7482
3
TITLE

FOR APPD. VAC 04.05.23 CG Power and Industrial


2 SHEET 1 OF 1 Solutions Limited
36kV O/D PCVCB THIRD ANGLE PROJECTION MV Switchgear Division
1 ALL DIMENSIONS ARE IN mm Ambad, Nashik, India
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. PV7482SC REV 0
1 2 3 4 5 6 7 8 9 10

0
REV
NOTES:-

PV7482GB F F

E E
FILE NAME:

DRG. NO.

D D

*
RATING:-
IF IN DOUBT, ASK

SIDE VIEW.
FRONT VIEW.

C FOUNDATION PLAN DETAILS DETAIL AT 'Y' C


DETAILS OF FOUNDATION BOLT
FRONT
80

A=SUITABLE FOR
40 & 44.5
900
450
CG Power and Industrial Solutions Limited

B B
All information contained in this document
is confidential and should not be used

DETAILS OF PALM OF LOWER AND


UPPER TERMINAL PLATES
without prior consent of

A 5 NAME DATE
GENERAL ARRANGEMENT DRG DRN. ADS 04.05.23 W.O.NO. PV7482
4
TITLE

3 FOR APPD. VAC 04.05.23 CG Power and Industrial


SHEET 1 OF 2 Solutions Limited
2 36kV OUTDOOR PCVCB MV Switchgear Division
THIRD ANGLE PROJECTION Ambad, Nashik, India
1 ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. PV7482GB REV 0
1 2 3 4 5 6 7 8 9 10

0
REV

F F

RATING PLATE DETAILS


PV7482GB

PORCELAIN CLAD VACUUM CIRCUIT BREAKER


E
CG Power and Industrial RATING TO : IEC62271-100
E

Solutions Limited.
FILE NAME:

CIRCUIT BREAKER TYPE 36PV25A


DRG. NO.

Medium Voltage Switchgear Divn.


Ambad, Nashik-422010. SR.NO ##
MADE IN INDIA.

VOLTAGE 33 kV BREAKING CAPACITY 25 kA

D CURRENT 1250 AMP MAKING CAPACITY 62.5 kAp ### YEAR D

FREQUENCY 50 Hz SHORT TIME CURRENT 25 kA FOR 3 SEC


IF IN DOUBT, ASK

NO OF POLES 3 DC. COMPONENT < 50% BIL 70/170 kVp

OPERATING SEQUENCE/DUTY : O - 0.3Sec - CO - 3Min - CO

C SHUNT TRIP 110 VDC CLOSING COIL 110 VDC C

## Sr.Nos.

### MONTH& YEAR TO BE INCORPORATED IN WHICH JOB IS DESPATCHED


CG Power and Industrial Solutions Limited

B B
All information contained in this document
is confidential and should not be used
without prior consent of

A 5 NAME DATE
RATING PLATE DRN. ADS 04.05.23 W.O.NO. PV7482
4
TITLE

3 DETAILS FOR APPD. VAC 04.05.23 CG Power and Industrial


SHEET 2 OF 2 Solutions Limited
2 36kV OUTDOOR PCVCB MV Switchgear Division
THIRD ANGLE PROJECTION Ambad, Nashik, India
1 ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. PV7482GB REV 0
1 2 3 4 5 6 7 8 9 10

0
500
REV

F
480* F

310 450*
GP2078Q1

E E
FILE NAME:

500 310
DRG. NO.

3
D 2 D

4
1
IF IN DOUBT, ASK

1310

C C

480* 450*
CG Power and Industrial Solutions Limited

B B

5 02 SIDE BRACING ANGLE


All information contained in this document
is confidential and should not be used

4 01 SUPPORT ANGLE
3 VERTICAL ANGLE (R.H.) W.A.
without prior consent of

02
2 02 VERTICAL ANGLE (L.H.) W.A.
1 02 FRONT BRACING ANGLE
ITEM QTY DESCRIPTION
PARTS LIST
A 5 NAME DATE
GENERAL ARRANGEMENT DR DRN. ADS 04.05.23 W.O.NO. PV7482
4
TITLE

3 FOR BREAKER SUPPORT APPD. VAC 04.05.23 CG Power and Industrial


SHEET 1 OF 1 Solutions Limited
2 STRUCTURE MV Switchgear Division
THIRD ANGLE PROJECTION Ambad, Nashik, India
1 ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. GP2078Q1 REV 0
1 2 3 4 5 6 7 8 9 10

0
REV

F F
101 110V DC SUPPLY FROM CUSTOMER 102

REMOTE
LR CLOSE 94
4 D K13 103 104 FOR FUTURE K19 A1 A2

J3

J4
INTERLOCK
94 16
LR TNC ZZ2 VCB52
FC1 VCB52 203
FC2
1 2 K11 1 A K15 2 B K17 105 106 15 18 a b 10 9 XF1 XF2 204 2 1
CLOSE CIRCUIT
PV7482SC

6A K19 K21 K23 K25 K25A K12A K12


6A

E E
REMOTE
TRIP-2 PRE-CLOSE CONTACT 111 K101 2
VCB52 1
FILE NAME:

LR OF TRIPPING COIL-1
DRG. NO.

5 E 108 109
K3

LR TNC VCB52 VCB52


FT1 205 206 112 FT2
1 2 K1 2 B K5 1 A K7 4 3 K9 MX1 MX2 K2 K2 2 1
K9A K2A
TRIP CIRCUIT-1
6A 6A

107 110 POST-CLOSE CONTACT


TRIPPING FROM
PROTECTIVE RELAY OF TRIPPING COIL-1
D D

REMOTE PRE-CLOSE CONTACT VCB52


LR 117 K151 6 5
TRIP-2 OF TRIPPING COIL-2
IF IN DOUBT, ASK

6 F 114 115
K53

LR TNC VCB52 VCB52


FT3 207 208 118 FT4
1 2 K51 3 C K55 3 C K57 8 7 K59 MX3 MX4 K52 K52 2 1
K59A K52A
TRIP CIRCUIT-2
6A 6A

113 116
TRIPPING FROM POST-CLOSE CONTACT
PROTECTIVE RELAY OF TRIPPING COIL-2
C C

SPARE AUX. CONTACT OF BREAKER FOR REMOTE IND. OF BREAKER

VCB52 VCB52
123 U01 16 15 U02 124 129 U07 18 VCB52 17 U08 130 119 L1 12 11 L3 120
BREAKER 'ON' IND.
VCB52 VCB52 VCB52
125 U03 20 19 U04 126 131 U09 22 21 U10 132 14 13 L5 121
BREAKER 'OFF' IND.
CG Power and Industrial Solutions Limited

B B
VCB52
127 U05 24 23 U06 128 ZZ3
All information contained in this document
is confidential and should not be used

a b L7 122
SPRING CHARGE IND.
without prior consent of

2 3 4 5

A 5 NAME DATE
SCHEMATIC DRG FOR DRN. ADS 04.05.23 W.O.NO. PV7482
4
TITLE

3 36kV O/D PCVCB APPD. VAC 04.05.23 CG Power and Industrial


SHEET 1 OF 2 Solutions Limited
2 CONTROL CIRCUIT MV Switchgear Division
THIRD ANGLE PROJECTION Ambad, Nashik, India
1 ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. PV7482SC REV 0
1 2 3 4 5 6 7 8 9 10

0
REV

F F

133 230V AC SUPPLY 134


PV7482SC

SPRING CHARGING MOTOR

H3

H4
E E
FM ZZ1
1 2 M1 a b M3 201 M3 P1 M N1 M2 202 M2 2 LKM 1 MOTOTR CIRCUIT
FILE NAME:

6A 1
DRG. NO.

HSW TH HE1
FH LKH
1 2 H21 1 2 H23 1 2 H25 1 2 H22 H22 2 1 HEATER CIRCUIT
6A
80W,230V AC

D PSW LMP D
1 2 H27 1 2 PANEL ILLUMINATION LAMP
IF IN DOUBT, ASK

SKT

SSW
1 2 H29 P N H22 3 PIN SOCKET

90 E
ET

C C
CG Power and Industrial Solutions Limited

B B
All information contained in this document
is confidential and should not be used
without prior consent of

A 5 NAME DATE
SCHEMATIC DRG FOR DRN. ADS 04.05.23 W.O.NO. PV7482
4
TITLE

3 36kV O/D PCVCB APPD. VAC 04.05.23 CG Power and Industrial


SHEET 2 OF 2 Solutions Limited
2 A.C CIRCUIT MV Switchgear Division
THIRD ANGLE PROJECTION Ambad, Nashik, India
1 ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. PV7482SC REV 0
1 2 3 4 5 6 7 8 9 10

0
REV
ANSI CODE, TAG, SYMBOL DESCRIPTIONS
F F
ANSI
PROTECTIVE FUNCTIONS SYMBOL DESCRIPTION TAG TAG DESCRIPTION TAG TAG DESCRIPTION TAG TAG DESCRIPTION
CODE
21 DISTANCE PROTECTION RELAY TERMINAL ON BREAKER III INDICATIONS VI METERS X FUSES & MCB
25 CHECK SYNCHRONIZING RELAY TERMINAL ON C.R. PANEL R BREAKER ON INDICATION(RED) AM ANALOG/DIGITAL AMMETER FR,FY,FB PT SECONDARY(Y SIDE) FUSES

27 UNDER VOLTAGE RELAY HRC FUSE G BREAKER OFF INDICATION(GREEN) VM ANALOG/DIGITAL VOLTMETER F1,F2 PT SECONDARY(V SIDE) FUSES

32 DIRECTIONAL POWER RELAY LINK A AUTO TRIP INDICATION(AMBER) HZ FREQUENCY METER FC1,FC2 CLOSING CIRCUIT FUSES

37 UNDER CURRENT/POWER RELAY PLUG AND SOCKET W TRIP CKT HEALTHY INDICATION(WHITE) KW WATT METER FT1,FT2 TRIPPING CIRCUIT FUSES

46 NEGATIVE SEQUENCE VOLTAGE RELAY NORMALLY OPEN CONTACT B SPRING CHARGED INDICATION (BLUE) KVAR REACTIVE VOLT AMP METER FI1,FI2 INDICATION CIRCUIT FUSES
PV6512Q

47 NEGATIVE SEQUENCE CURRENT RELAY NORMALLY CLOSED CONTACT DF DC FAIL INDICATION(CLEAR) KVA VOLT AMP METER FAN1,FAN2 ANNUNCIATION CIRCUIT FUSES
E 49 THERMAL RELAY HAND RESET CONTACT AF AC FAIL INDICATION(CLEAR) PF POWER FACTOR METER FCA1,FCA2 COMMON ALARM CIRCUIT FUSES E

50 HIGHSET OPERATED OC/EF RELAY AUDIBLE ALARM DH DC HEALTHY INDICATION(GREEN) KWH WATTHOUR METER FAX1,FAX2 AUXILLARY RELAY CKT FUSES
FILE NAME:

50N SENSITIVE EF RELAY NORMALLY OPEN PUSH BUTTON AH AC HEALTHY INDICATION(GREEN) TVM TRIVECTOR METER FM/LKM FUSE/LINK FOR MOTOR CIRCUIT
DRG. NO.

51 IDMTL OPERATED OC/EF RELAY NORMALLY CLOSED PUSH BUTTON RP,YP, R/Y/B PHASE ON INDICATION MDC MAXIMUM DEMAND CONTROLLER FH/LKH
BP FUSE/LINK FOR HEATER CIRCUIT

51N DEFINITE TIME EF RELAY M MOTOR BF BREAKER FAIL INDICATION(RED) LM LOAD MANAGER FS/LKS FUSE/LINK FOR SOCKET CIRCUIT

51G IDMTL EF RELAY CURRENT TRANSFORMER SMI SEMAPHORE INDICATOR MFM MULTIFUNCTION METER FV1-4 FUSES FOR VOLT SEL SCHEME

55 POWER FACTOR RELAY VOLTAGE TRANSFORMER IV PUSH BUTTONS RH RUN HOUR METER MCB MINIATURE CIRCUIT BREAKER

59 OVER VOLTAGE RELAY THERMOSTAT PB TRIP CKT HEALTHY TEST PUSH BUTTON VII TEST TERMINAL BLOCKS XI AUXILLARY CONTACTOR
59N VOLTAGE BALANCE RELAY (NDR) BUZZER/HOOTER DA DC FAIL ACCEPT PUSH BUTTON MTTB METERING TEST TERMINAL BLOCK 52X AUX CONTACTOR FOR VCBCONTACT MULT.
D LAMP RELAY TEST TERMINAL BLOCK C1,C2... AUX CONTACTOR D
61 CURRENT BALANCE RELAY (NDR) AA AC FAIL ACCEPT PUSH BUTTON RTTB

63R TRANSFORMER FAULT RELAY SWITCH(TNC,LR,AUTO MANUAL) EPB EMERGENCY PUSH BUTTON VIII DEVICES & ADDITIONAL RELAYS XII TRANSDUCERS
64R REF RELAY TOGGLE SWITCH PA/PR ACCEPT/RESET PUSH BUTTON ADF AC DC FAIL RELAY (WITH ALARM LOGIC) CTX CURRENT TRANSDUCER
IF IN DOUBT, ASK

64N GROUND FAULT RELAY COIL PM/PT MUTE/TEST PUSH BUTTON DCF DC FAIL RELAY (WITH ALARM LOGIC) VTX VOLTAGE TRANSDUCER

67 AC DIRECTIONAL CURRENT RELAY CC CURRENT COIL OF METER V CONTROL SWITCHES CAR COMMON ALARM SCHEME KWX KW TRANSDUCER

79 AUTO RECLOSING RELAY PC PRESSURE COIL OF METER ZZ1 OPENS WHEN SPRINGS ARE CHARGED VSS VOLTAGE SELECTION SCHEME KVARX KVAR TRANSDUCER

80 DC SUPPLY SUPERVISION RELAY (52a)VCB OPERATED NO CONTACT ZZ2,ZZ3 CLOSES WHEN SPRINGS ARE CHARGED IX ACCESSORIES TEMX TEMPERATURE TRANSDUCER

81U UNDER FREQUENCY RELAY (52b)VCB OPERATED NC CONTACT LS CLOSES WHEN VCB IS MECH.FREE TO CLOSE ANN ANNUNCIATOR
81O OVER FREQUENCY RELAY 3PIN SOCKET TNC BREAKER CONTROL SWITCH HCA HOOTER FOR COMMON ALARM
C 85 PILOT WIRE RECEIVER RELAY C
TAG NAME DESCRIPTION LR LOCAL REMOTE SWITCH HAN HOOTER FOR ANNUNCIATOR
86 MASTER TRIP(LOCK OUT) RELAY I CIRCUIT BREAKER SYNCHRONIZING SELECT SWITCH HAF HOOTER FOR AC FAIL ALARM
SS
87B BUS BAR DIFFERENTIAL RELAY 52 CIRCUIT BREAKER AS/VS AMMETER/VOLTMETER SELECTOR SWITCH HDF HOOTER FOR DC FAIL ALARM

87M MOTOR DIFFERENTIAL RELAY 52C CLOSE COIL TSS TRIP SEL SWITCH(USED IN SYNCHRO.CKT) HNTA HOOTER FOR NON TRIP ALARM

87T TRANSFORMER DIFFERENTIAL RELAY 52T SHUNT TRIP COIL BSS CB SEL SWITCH(USED IN SYNCHRO. CKT) PP POWERPACK

94 ANTI PUMPING RELAY 52S SERIES TRIP COIL ACS AC SOURCE SEL SWITCH HE SPACE HEATER

95 TRIP CKT. SUPERVISION RELAY DSS DC SOURCE SEL SWITCH TH THERMOSTAT


HSW /
96 FUSE FAILURE RELAY II INSTRUMENT TRANSFORMERS PSW TOGGLE SWITCH FOR HEATER/ PANEL LAMP T1,T2... TIMER
98 CONTACTOR CT CURRENT TRANSFORMER SSW TOGGLE SWITCH FOR SOCKET R1,R2... RESISTOR
CG Power and Industrial Solutions Limited

B B
99 MOTOR PROTECTION RELAY VT VOLTAGE TRANSFORMER DS DOOR SWITCH

ICT INTERPOSING CURRENT TRANSFORMER AMS AUTO MANUAL SELECTOR SWITCH


All information contained in this document
is confidential and should not be used
without prior consent of

NOTES
1. THESE ARE THE FREQUENTLY USED ABBREVIATIONS AS PER CGL STANDARD DRAWINGS
2. REFERENCES: IEV-440 , IS-5578, IEC-60050

A 5 NAME DATE
LEGENDS DRN. ADS 04.05.23 W.O.NO. PV7482
4
TITLE

3 SYMBOLS APPD. VAC 04.05.23 CG Power and Industrial


SHEET 1 OF 1 Solutions Limited
2 DEVICE NUMBER MV Switchgear Division
THIRD ANGLE PROJECTION Ambad, Nashik, India
1 ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. PV6512Q REV 0
B'SHEET FOR W. O. : PV7482 REV '0'
B'SHEET NO. PB7482
BOARD : 33kV PCVCB
TOTAL QTY.: 2 No.
PREPARED BY : ADS
APPROVED BY : VAC
DATE : 04.05.23

IT DESCRIPTION PCVCB TOTAL


MAKE:AS PER CGL STANDARD
A1 BASIC UNIT 1 2
33kV/1250A/25kA
SP.CH.MOTOR:230V AC,AUX.SUPPLY: 110V DC

A2 ANTI PUMPING DEVICE 1 2


MAKE : SELECTRON/EQ.
AUX.SUPPLY: 110VDC.

A3 TNC SWITCH 1 2
TYPE - NON-LOCKABLE
CONTACTS: 2NO IN EACH POSITION

A4 LOCAL/REMOTE SELECTOR SWITCH 1 2


TYPE - NON-LOCKABLE
CONTACTS : 3N/O IN EACH POSITION

A5 PANEL ILLUMINATION LAMP(LED) 1 2


RATING: 5 WATT, 230V AC

A6 PANEL LAMP HOLDER 1 2

A7 3 PIN PLUG SOCKET 1 2


RATING:230V,5A

A8 TOGGLE SWITCH 2 4
FOR HEATER AND SOCKET
RATING:-6A,230V AC

A9 DOOR OPERATED SWITCH 1 2


RATING : 2A,230V AC

A10 SPACE HEATER 1 2


RATING : 80W,230VAC

A11 THERMOSTAT-RIGID PROBE TYPE 1 2


RATING : 230V AC

You might also like