You are on page 1of 33

LALITPUR POWER GENERATION COMPANY LIMITED

LALITPUR SUPER THERMAL POWER PROJECT - 3 X 660 MW

Title of Document: BusBar Protection of 220kV


Package
LPGCL DOC. Number : BE-LAL-EEV-109-J-0036 109 Switchyard
Name
Vendor DOC.
O12166-E-SY-VD-RP-2006
Number:

BAJAJ INFRASTRUCTURE DEVELOPMENT COMPANY LIMITED

L&T Construction
Power Transmission & Distribution

SUB VENDOR M/s Schneider Electric


03 25.07.13 A THY THY APS APS VSA VSA
02 09.05.13 A THY THY APS APS RNM RNM
01 03.04.13 A THY THY APS APS RNM RNM
00 26.02.13 A THY THY APS APS RNM RNM
REV
DATE STATUS INTLS SGN INTLS SGN INTLS SGN INTLS SGN
NO.
PREPARED BY CHKD. BY REVIEWED. BY ISSUE
Schneider Electric Schneider Electric L&T AUTHORISATION
1 2 3 4 5 6 7 8

A
220kV BUSBAR PROTECTION PANEL A

LIST OF DOCUMENTS
B DRG. NO BIDCO DRG. NO L&T DRG. NO DESCRIPTION. REVISION DATE ISSUE B
3269PP552-CI-11
3269PP552-GL-11 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043 L&T DRG. NO: O12166-E-SY-VD-RP-2006 GENERAL ARRANGEMENT & LEGEND C 16/07/2013 FOR APPROVAL
3269PP552-S-11 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043 L&T DRG. NO: O12166-E-SY-VD-RP-2006 SCHEMATIC DRAWING C 16/07/2013 FOR APPROVAL
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

C C

D D

PANEL TYPES : +2BB


LIST REFERENCE DOCUMENTS:
E
CUSTOMER: BAJAJ INFRASTRUCTURE DEVELOPMENT E
Sl.NO CIRCUIT CIRCUIT
COMPANY LTD.
1 CT BE-LAL-EEV-109-B-0015 CLIENT: LALITPUR POWER GENERATION COMPANY
2 CVT BE-LAL-EEV-109-B-0017 LIMITED.
3 SLD BE-LAL-EEV-109-G-0004 REV-02 CONTRACTOR: L&T CONSTRUCTION
4 CB BE-LAL-EEV-109-J-0013 POWER TRANSMISSION & DISTRIBUTION
5 ISOLATOR BE-LAL-EEV-109-B-009 PROJECT: 3x660MW SUPER CRITICAL TPP - LALITPUR, UP
F F
Schneider Electric Infrastructure Ltd
PO. No & Date: L&T/PT&D/SS/BIDCO /LOA/02
CHENNAI , INDIA DATED :26.12.2012
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

SHEET DESCRIPTION
000 INDEX SHEET
001 GENERAL ARRANGEMENT
002 BILL OF MATERIALS FOR +2BB PANEL
003 BILL OF MATERIALS FOR +2BB PANEL
004 BILL OF MATERIALS FOR +2BB PANEL
005 BILL OF MATERIALS FOR +2BB PANEL

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

C C

D D

E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 000 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION INDEX SHEET REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 001
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 DRG. NO.: 3269PP552-GL-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

800

+2BB
A cl A

80DC1

80DC2
87CUA
B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

87CUB

C C
2200

BSS1 DCS BSS2

PB01
BSS3 BSS4

D D

E BLKA BLKB E

ANTIVIBRATION PAD
100

15

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 001 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION GENERAL ARRANGEMENT REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION RELAY PANEL: +BB2 APPROVED : APS CONT: 002
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006 DRG. NO.: 3269PP552-GL-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FRONT VIEW EQUIPMENTS

A DESIGNATION MANUFACTURER MATERIAL DESCRIPTION


` COMMENT A
BUSBAR PROTN. CENTRAL UNIT, AUX VOTL: 110-250V DC/100-240V AC, OPTO I/P: 8, O/P CONTACT: 8, RELAY COMMUNICATION UNITS: 5 FOR 20
87CUA SCHNEIDER ELECTRIC P741356A6M0518K B/B PROTN. CENTRAL UNIT MAIN-1
PERIPHERAL UNITS, PROTOCOL: IEC61850, CASE: 80TE, MOUNTING: PANEL

BUSBAR PROTN. CENTRAL UNIT, AUX VOTL: 110-250V DC/100-240V AC, OPTO I/P: 8, O/P CONTACT: 8, RELAY COMMUNICATION UNITS: 5 FOR
87CUB SCHNEIDER ELECTRIC P741356A6M0518K B/B PROTN. CENTRAL UNIT MAIN-2
20 PERIPHERAL UNITS, PROTOCOL: IEC61850, CASE: 80TE, MOUNTING: PANEL

80DC1 ALSTOM MVAAM11B1CJ5516A DC SUPERVISION RELAY, 2M 2C FLAG-REV : 110-125 / 220-250V AC/DC SLUG: 100ms TDDO WD:Z1MVAAM11014 DC-1 SUPVN RELAY

80DC2 ALSTOM MVAAM11B1CJ5516A DC SUPERVISION RELAY, 2M 2C FLAG-REV : 110-125 / 220-250V AC/DC SLUG: 100ms TDDO WD:Z1MVAAM11014 DC-2 SUPVN RELAY

B B
DCS SWITRON SS3NLSPAPAW00 SELECTOR SWITCH 10 WAYS,3 POSITION,STAYPUT,NON LOCKABLE WITH PISTOL GRIP HANDLE DC SELECTOR SWITCH
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

BSS1 SWITRON SS2LBSPBP8W00 SELECTOR SWITCH 8 WAYS,2 POSITION,STAYPUT,LOCKABLE WITH PISTOL GRIP HANDLE B/B IN /OUT SWITCH FOR MAIN1 ZONE1

BSS2 SWITRON SS2LBSPBP8W00 SELECTOR SWITCH 8 WAYS,2 POSITION,STAYPUT,LOCKABLE WITH PISTOL GRIP HANDLE B/B IN /OUT SWITCH FOR MAIN1 ZONE-2

BSS3 SWITRON SS2LBSPBP8W00 SELECTOR SWITCH 8 WAYS,2 POSITION,STAYPUT,LOCKABLE WITH PISTOL GRIP HANDLE B/B IN /OUT SWITCH FOR MAIN2 ZONE1

C C
BSS4 SWITRON SS2LBSPBP8W00 SELECTOR SWITCH 8 WAYS,2 POSITION,STAYPUT,LOCKABLE WITH PISTOL GRIP HANDLE B/B IN /OUT SWITCH FOR MAIN2 ZONE-2

BLKA NELSTER GBRLYTESTBLKNEL STANDARD TEST BLOCK TEST BLOCK FOR 87CUA

BLKB NELSTER GBRLYTESTBLKNEL STANDARD TEST BLOCK TEST BLOCK FOR 87CUA

PB01 TEKNIC TK-PB-BLK-4NO PUSH BUTTON BLACK, 4NO GRP-A/B TRIP RELAY RESET

D D

E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 002 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION BILL OF MATERIALS FOR +2BB PANEL REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 003
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-GL-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INTERNAL MOUNTING DEVICES

DESIGNATION MANUFACTURER MATERIAL DESCRIPTION


` COMMENT
A A
CIL PHILIPS CIL-11W-230VAC COMPACT FLOURESCENT LAMP - 11W 230V AC

DS KAYCEE DS-230VAC DOOR SWITCH

HS SWITRON HS-230VAC HEATER SWITCH

ALCO/HOT SET/
HT SAUTER RACE HT-60W-230AC HEATER 230V AC 50HZ, 60W

B B
PS ANCHOR PS-5-15A-230VAC POWER SOCKET 5/15A WITH SWITCH + 3PIN PLUG, 230V AC
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

TS ANCO TS-30-90DEG-230VAC THERMOSTAT 230V AC, 30-90 DEG

MCB1 SCHNEIDER ELECTRIC MCB-2P-4A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 4A, BREAKING CURRENT 20kA @220V

MCB2 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

C MCB3 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V C

MCB4 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB5 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB6 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

D MCB7 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V D

MCB8 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB9 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB10 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB11 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V
E E

MCB12 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB13 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB14 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 003 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION BILL OF MATERIALS FOR +2BB PANEL REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 004
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-GL-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INTERNAL MOUNTING DEVICES

DESIGNATION MANUFACTURER MATERIAL DESCRIPTION


` COMMENT
A A
MCB15 SCHNEIDER ELECTRIC MCB-1P-4A-110/250VDC SINGLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 4A,BREAKING CURRENT 20kA @220V

MCB16 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB17 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB18 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

B B
MCB19 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

MCB20 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB21 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB22 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

C MCB23 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V C

MCB24 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB25 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB26 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

D MCB27 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V D

MCB28 SCHNEIDER ELECTRIC MCB-2P-6A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 6A,BREAKING CURRENT 20kA @220V

MCB29 SCHNEIDER ELECTRIC MCB-2P-25A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 25A,BREAKING CURRENT 20kA @220V

MCB30 SCHNEIDER ELECTRIC MCB-2P-25A-110/250VDC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/250V DC, 25A,BREAKING CURRENT 20kA @220V

MCB91 SCHNEIDER ELECTRIC MCB-2P-16A-110/240VAC DOUBLE POLE MCB WITH AUX CONTACT: 1 C/O, 110/240V AC, 16A,BREAKING CURRENT 10kA @415V
E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 004 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION BILL OF MATERIALS FOR +2BB PANEL REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 005
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-GL-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INTERNAL MOUNTING DEVICES

DESIGNATION MANUFACTURER MATERIAL DESCRIPTION


` COMMENT
A A
X1 CONNECTWELL STH4 NON-DISCONNECT TERMINAL

X4 CONNECTWELL STH4 NON-DISCONNECT TERMINAL

X7 CONNECTWELL STH4 NON-DISCONNECT TERMINAL

X201 CONNECTWELL STH4 NON-DISCONNECT TERMINAL

B B
X202 CONNECTWELL STH4 NON-DISCONNECT TERMINAL
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X203 CONNECTWELL STH4 NON-DISCONNECT TERMINAL

C C

D D

E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 005 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION BILL OF MATERIALS FOR +2BB PANEL REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: NIL
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-GL-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SHEET DESCRIPTION
A 000 INDEX SHEET A

001 LIST OF SYMBOLS


002 SINGLE LINE DIAGRAM
003 SINGLE LINE DIAGRAM
004 SINGLE LINE DIAGRAM
005 TYPICAL IO LIST FOR CUA
006 TYPICAL IO LIST FOR CUB
007 AC DISTRIBUTION
008 DC CHANGEOVER SCHEME
B 009 DC SOURCE-1 DISTRIBUTION CKT. B

010 DC SOURCE-1 DISTRIBUTION CKT.


011 DC SOURCE-2 DISTRIBUTION CKT.
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

012 DC SOURCE-2 DISTRIBUTION CKT.


013 DC MCB FAIL CKT.
014 BUSBAR PROTN CENTRAL UNIT CKT.
015 BUSBAR PROTN CENTRAL UNIT CKT.
016 FIBRE OPTIC INTERFACE CIRCUIT
017 FIBRE OPTIC INTERFACE CIRCUIT
C 018 FIBRE OPTIC INTERFACE CIRCUIT C

019 FIBRE OPTIC INTERFACE CIRCUIT


020 SPARE CONTACT DISTRIBUTION
021 DEVICE REFERENCE
022 DEVICE REFERENCE
023 DEVICE REFERENCE
024 TERMINAL BLOCK ALLOCATION

D D

E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 000 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION INDEX SHEET REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 001
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LIST OF STANDARD SYMBOLS

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION


A A

NORMALLY OPEN NON-DISCONNETING TB TERMINAL GROUP STANDARDS


COMPACT
RESISTOR CONTACT SELF FOR INTER PANEL BUS
FLOURESCENT LAMP
RESET WIRING TB REF FUNCTION
X1 AC/DC CIRCUITS
NON-DISCONNETING TB X2 CT CIRCUITS
NORMALLY CLOSE
DOOR/HEATER CONTROL / CONTACT SELF
FOR SCADA/BCU X3 PT CIRCUITS
SWITCH SELECTOR SWITCH X4 CONTROL INPUTS (TO OPTO/CONT MUL. RELAY)
RESET
NON-DISCONNETING TB X5 CONTROL OUTPUTS (TO CB CONTROL)
CHANGEOVER
X6 CONTROL OUTPUTS (TO ISOL./ESW. CONTROL)
B HEATER TEST BLOCK CONTACT SELF TB PRIMARY X7 SPARE OUTPUTS B
RESET EQUIPMENTS X8 TEMP SCANNER/SCADA/RTU/DCS CKTS
X9 INDICATION/ANNUNCIATON CKTS
DIODE X-BCU-DIU-SLOT BCU DI INPUTS
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

S NORMALLY OPEN
W POWER SOCKET
POTENTIO METER CONTACT HAND X-BCU-DOU-SLOT BCU DO INPUTS
WITH SWITCH
RESET X-BCU-AIU-SLOT BCU AI INPUTS
SEMAPHORE
X10 FOR INTER PANEL CABLES
X100 BUS WIRING CT/PT CKTS (INTRA-BAY)
X101-X109 BUS WIRING CONTROL CKTS (INTRA-BAY)
NORMALLY CLOSE
THERMOSTAT POTENTIAL CONTACT HAND X200 BUS WIRING CT/PT CKTS (INTER-BAY)
TRANSFORMER RESET CLIO INPUT X201-X209 BUS WIRING CONTROL CKTS (INTER-BAY)
C C

CHANGEOVER
CURRENT
FUSE CONTACT HAND CLIO OUTPUT
TRANSFORMER
RESET

BUS WIRE FERRULE NUMBERING STANDARDS


LINK REPRESENTATION
+

SOURCE / TARGET FERRULE CIRCUIT


"A" CT CIRCUIT-MAIN PROTECTION
POWER SUPPLY DIGITAL OPTO INPUT
D "B" CT CIRCUIT-BUSBAR PROTECTION D
NORMAL WIRE "C" CT CIRCUIT-BACKUP PROTECTION
MCB REPRESENTATION
- SOURCE / TARGET "D" CT CIRCUIT-METERING
"E" VT CIRCUIT-PROTECTION/METERING
"G" VT CIRCUIT-SYNCHRONISING
"H" AUXILARY AC CIRCUIT
INDICATING
LAMPS SELT-RESET SLOW
"J" AUXILARY DC CIRCUIT
SELF-RESET COIL "K" CONTROL CIRCUIT
OPERAING COIL WITH
WITH/WITHOUT
FLAG
REVERSE/FORWARD "L" INDICATION & ALARM CIRCUITS
FLAG
PUSH BUTTON "P" DC CIRCUIT- BUSBAR PROTECTION CIRCUIT
NC CONTACT "S" SCADA/EVENT LOGGER/DAS CIRCUITS
E SPARE CONTACTS E
"U"
PUSH BUTTON
NO CONTACT ANNUNCIATOR
WINDOW INPUT
HAND-RESET COIL
WITH/WITHOUT
FLAG
METROSIL
DISCONNETING TB

NOTE: RELAY CONTACTS SHOWN WITH CONTACT DE ENERGIZED CONDITION.

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 001 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION LIST OF SYMBOLS REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 002
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

220KV,2000A,50Hz,40KA FOR 1SEC., MAIN BUS-I 4xACSR MOOSE CONDUCTOR

A 220KV,2000A,50Hz,40KA FOR 1SEC., MAIN BUS-II 4xACSR MOOSE CONDUCTOR A


220KV,1600A,50Hz,40KA FOR 1SEC., TRANSFER BUS 2xACSR MOOSE CONDUCTOR

M 201-89TA M 201-89TB M 201-89TC M 202-89LA M 202-89LB M 202-89LC M 203-89LA M 203-89LB M 203-89LC

2B1-89AE1 2B2-89AE1
201-89TBE 202-89LBE 203-89LBE

M 2B1-89A M 2B2-89A

201-52T 202-52L 203-52L


B 2B1-89AE2 2B2-89AE2 B
201-89TDE1 202-89LDE1 203-89LDE1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

M 201-89TD M 202-89LD M 203-89LD

2B1-CVT 2B2-CVT 201-89TDE2 202-89LDE2 203-89LDE2

C 201-CT1T 202-CT1L 203-CT1L PUA (87)


C
PUA (87) PUA (87)
P1 P1 P1
CORE-5 CORE-5 CORE-5
P2 P2 P2

MiCOM P743
MiCOM P743 MiCOM P743
PUB (87)
PUB (87) PUB (87)
P1 P1 P1
CORE-6 CORE-6 CORE-6
P2 P2 P2

MiCOM P743
MiCOM P743 MiCOM P743
D D

201-EMVT 202-EMVT 203-EMVT

E E

202-CVTL 203-CVTL

201-LAT
202-LAL 203-LAL

TO ICT - 1 LINE-1 TO UPPCL JHANSI SUBSTATION LINE-2 TO UPPCL JHANSI SUBSTATION


220kV (EXSTING) 220kV (EXSTING)

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 002 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION SINGLE LINE DIAGRAM REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 003
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

220KV,2000A,50Hz,40KA FOR 1SEC., MAIN BUS-I 4xACSR MOOSE CONDUCTOR

A 220KV,2000A,50Hz,40KA FOR 1SEC., MAIN BUS-II 4xACSR MOOSE CONDUCTOR A


220KV,1600A,50Hz,40KA FOR 1SEC., TRANSFER BUS 2xACSR MOOSE CONDUCTOR

205-89BTCE1

M 204-89TA M 204-89TB M 204-89TC M 205-89BTA M 205-89BTB M 205-89BTC M 206-89BCA M 206-89BCB M 207-89LA M 207-89LB M 207-89LC

204-89TBE 205-89BTBE 205-89BTCE2 206-89BCAE 206-89BCBE 207-89LBE

B 204-52T 207-52L
B

206-CT1BC PUA (87)


204-89TDE1 207-89LDE1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

P2
CORE-5
M 204-89TD P1 M 207-89LD
205-52BT
MiCOM P743
204-89TDE2 207-89LDE2

C C
206-52BC

204-CT1T 205-CTBT PUB (87) 207-CT1L


PUB (87) PUB (87)
P1 P1 P1
CORE-5 CORE-5 CORE-5
P2 P2 206-CT2BC P2
PUB (87)
MiCOM P743
MiCOM P743 P1 MiCOM P743
CORE-5
PUA (87) P2
PUA (87) PUA (87)
P1 P1 MiCOM P743 P1
D CORE-6 CORE-6 CORE-6 D
P2 P2 P2

MiCOM P743
MiCOM P743 MiCOM P743

204-EMVT 207-EMVT

E E

207-CVTL

204-LAT
207-LAL

TO ICT - 2 LINE-3 TO UPPCL LALITPUR SUBSTATION


220kV (PLANNED)

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 003 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION SINGLE LINE DIAGRAM REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 004
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

220KV,2000A,50Hz,40KA FOR 1SEC., MAIN BUS-I 4xACSR MOOSE CONDUCTOR

A 220KV,2000A,50Hz,40KA FOR 1SEC., MAIN BUS-II 4xACSR MOOSE CONDUCTOR A

220KV,1600A,50Hz,40KA FOR 1SEC., TRANSFER BUS 2xACSR MOOSE CONDUCTOR

M 208-89LA M 208-89LB M 208-89LC M 209-89TA M 209-89TB M 209-89TC M 210-89TA M 210-89TB M 210-89TC

208-89LBE 209-89TBE 210-89TBE

208-52L
B 209-52T 210-52T
B

208-89LDE1
209-89TDE1 210-89TDE1
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

M 208-89LD
M 209-89TD M 210-89TD
208-89LDE2
209-89TDE2 210-89TDE2

C C
208-CT1L 209-CT1T 210-CT1T
PUB (87) PUB (87)
PUB (87)
P1
CORE-5
P2 P1 P1
CORE-5 CORE-5
P2 P2
MiCOM P743 MiCOM P743
MiCOM P743
PUA (87) PUA (87) PUA (87)
P1
CORE-6
P2 P1 P1
CORE-6 CORE-6
P2 P2

D MiCOM P743 MiCOM P743 MiCOM P743 D

208-EMVT

210-EMVT
209-EMVT

E E

208-CVTL

210-LAL
209-LA1T
208-LAL

LINE-4 TO UPPCL LALITPUR STATION TRANSFORMER - 2 STATION TRANSFORMER - 1


SUBSTATION 220kV (PLANNED)

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 004 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION SINGLE LINE DIAGRAM REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 005
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INPUT/OUTPUT LIST FOR CUA

A A
OUTPUT RELAYS
SL.NO PROTECTION FUNCTIONS (P741 RELAY) 87CUA
RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8 WD1 WD2

TO MAIN-II CU (87CUB)
B B

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

01 RELAY FAULTY a

02 SPARES a a a a a a a a a

OPTO INPUTS
SL.NO STATUS (P741 RELAY) 87CUA
I/P-1 I/P-2 I/P-3 I/P-4 I/P-5 I/P-6 I/P-7 I/P-8
C C

TO RESET ALL
BAYS BB TRIP
PROTECTION

PROTECTION

PROTECTION

PROTECTION

FOR STATUS

FOR STATUS

FOR STATUS
TO BUSBAR

TO BUSBAR

TO BUSBAR

TO BUSBAR

RELAY
01 B/B PROTN. ZONE-1 IN SERVICE a

02 B/B PROTN. ZONE-1 OUT OF SERVICE a


D D
03 B/B PROTN. ZONE-2 IN SERVICE a

04 B/B PROTN. ZONE-2 OUT OF SERVICE a

05 ACMCB TRIPPED a

06 RELAY RESET a

07 DC SOURCE-2 FAIL/MCB TRIPPED a

E 08 CUB RELAY FAULTY a E

Sl.NO NOTATION DISCRIPTION

1 RL RELAY OUTPUT CONTACT

2 WD WATCHDOG CONTACT

3 I/P DIGITAL OPTO INPUT

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 005 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION TYPICAL IO LIST FOR CUA REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 006
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INPUT/OUTPUT LIST FOR CUB

A A
OUTPUT RELAYS
SL.NO PROTECTION FUNCTIONS (P741 RELAY) 87CUB
RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8 WD1 WD2

TO MAIN-I CU (87CUA)
B B

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

01 RELAY FAULTY a

02 SPARES a a a a a a a a a

OPTO INPUTS
SL.NO STATUS (P741 RELAY) 87CUB
I/P-1 I/P-2 I/P-3 I/P-4 I/P-5 I/P-6 I/P-7 I/P-8
C C

BAYS BB TRIP
TO RESET ALL
PROTECTION

PROTECTION

PROTECTION

PROTECTION

FOR STATUS

FOR STATUS
TO BUSBAR

TO BUSBAR

TO BUSBAR

TO BUSBAR

SPARE

RELAY
01 B/B PROTN. ZONE-1 IN SERVICE a

02 B/B PROTN. ZONE-1 OUT OF SERVICE a


D D
03 B/B PROTN. ZONE-2 IN SERVICE a

04 B/B PROTN. ZONE-2 OUT OF SERVICE a

05 SPARE a

06 RESET RELAY a

07 DC SOURCE-1 FAIL/MCB TRIPPED a

E 08 CUA RELAY FAULTY a E

Sl.NO NOTATION DISCRIPTION

1 RL RELAY OUTPUT CONTACT

2 WD WATCHDOG CONTACT

3 I/P DIGITAL OPTO INPUT

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 006 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION TYPICAL IO LIST FOR CUB REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 007
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+ADJ. PANEL

3269PP552-S-05/093.1A

3269PP552-S-05/093.1A
A A

+2BB
X201 X201
B X1 B
1 2 1 2
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

H1

H2
MCB91

3
MCB91 1 2
.5C .4C
C C

4
16A
3 4
12
11 14 /014.5C

H3

H4
1 1

D DS HS D

2 2
H5

H7
3 1 1

SW
CIL
PS
TS
4
2 2
E E
H4

H9
1

HT
2

H4

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 007 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION AC DISTRIBUTION REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 008
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PN552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+DCDB-1
220V DC SOURCE-1 +DCDB-2
SUPPLY 220V DC SOURCE-2
SUPPLY
A A

+Ve -Ve
+Ve -Ve

+2BB

X1 X1 X1 X1
3 4 5 6
80DC1
J101

J102

J201

J202
B 11 B
COIL 14 .2C
13
TO 87CUB (DC-1 FAIL) 5 /015.7C
1

3
1 3
MCB29 MCB30
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

6
.7D .7E 2 4
2

4
25A 25A
7 9

SPARE 8 10 /020.3C

11 13 11 13

80DC2
MVAAM11 MVAAM11 11
COIL 14 .5C
J103

J104

J203

J204
80DC1 COIL 80DC2 COIL 13
C .7B .7C C
TO 87CUA (DC-2 FAIL) 5 /014.7C
1 3
6
2 4
14 14 7 9

SPARE 8 10 /020.4C

MCB29
D DCS D
1 2
7 9 1 3 15 17 11 13 .1B
SOURCE-1
IND
3 4
SOURCE-2 12
8 10 2 4 16 18 12 14 11 14

MCB30
1 2
.4B
3 4
12
E 11 14 E
J11

J12

J21

J22
/009.2B

/009.2B

/011.2B

/011.2B

NOTE: ** - TERMINALS TO BE IDENTIFIED AT SITE

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 008 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DC CHANGEOVER SCHEME REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 009
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DC SUPPLY TO 87CUA RELAY DC SUPPLY TO ICT-1 BAY DC SUPPLY TO LINE-1 BAY DC SUPPLY TO LINE-2 BAY DC SUPPLY TO ICT-2 BAY DC SUPPLY TO TBC BAY

A +2BB A

MCB1 MCB2 MCB3 MCB4 MCB5 MCB6


1 2 1 2 1 2 1 2 1 2 1 2
.2C .3C .4C .5C .6C .7C
3 4 3 4 3 4 3 4 3 4 3 4
12 12 12 12 12 12
11 14 /013.2B 11 14 /013.2B 11 14 /013.3B 11 14 /013.3B 11 14 /013.4B 11 14 /013.4B

B B

TO DC SOURCE-1
SELECTOR CKT.

/008.1E J11 J11


/010.1B

DISTN.CKT.
FROM DC
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

/008.1E J12 J12


/010.1B
1

3
C MCB1 MCB2 MCB3 MCB4 MCB5 MCB6 C
.2A .3A .4A .5A .6A .7A
2

4
4A 6A 6A 6A 6A 6A
P111

P112

P121

P122

P131

P132

P141

P142

P151

P152
P101

P102
/014.1B

/014.1F

D D

TO 87 CUA RELAY
X202 X202 X202 X202 X202 X202 X202 X202 X202 X202
5 6 7 8 9 10 11 12 13 14

+ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +ADJ. PANEL

3269PP552-S-05/105.1C

3269PP552-S-05/105.1C

3269PP552-S-05/105.1C

3269PP552-S-05/105.1C

3269PP552-S-05/105.1C

3269PP552-S-05/105.1D
3269PP552-S-05/105.1B

3269PP552-S-05/105.1B

3269PP552-S-05/105.1B

3269PP552-S-05/105.1B

E E

TO ICT-1 TO LINE-1 TO LINE-2 TO ICT-2 TO TBC


BAY-201 BAY-202 BAY-203 BAY-204 BAY-205

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 009 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DC SOURCE-1 DISTRIBUTION CKT. REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 010
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DC SUPPLY TO BC BAY DC SUPPLY TO LINE-3 BAY DC SUPPLY TO LINE-4 BAY DC SUPPLY TO ST-2 BAY DC SUPPLY TO ST-1 BAY DC SUPPLY TO FUTURE BAY DC SUPPLY TO FUTURE BAY DC SUPPLY TO FUTURE BAY

A +2BB A

MCB7 MCB8 MCB9 MCB10 MCB11 MCB12 MCB13 MCB14


1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
.1C .2C .3C .4C .5C .6C .7C .8C
3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4
12 12 12 12 12 12 12 12
11 14 /013.4B 11 14 /013.5B 11 14 /013.5B 11 14 /013.6B 11 14 /013.6B 11 14 /013.7B 11 14 /013.7B 11 14 /013.8B

/009.7B J11

B B

/009.7B J12
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

3
C MCB7 MCB8 MCB9 MCB10 MCB11 MCB12 MCB13 MCB14 C
.1A .2A .3A .4A .5A .6A .6A .7A
2

4
6A 6A 6A 6A 6A 6A 6A 6A
P161

P162

P171

P172

P181

P182

P191

P192

P201

P202

P221

P222

P231

P232

P241

P242
D D

X202 X202 X202 X202 X202 X202 X202 X202 X202 X202 X1 X1 X1 X1 X1 X1
7 8 9 10 11 12
15 16 17 18 19 20 1 2 3 4

+ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +FUTURE BAY +FUTURE BAY +FUTURE BAY
3269PP552-S-05/105.1D

3269PP552-S-05/105.1D

3269PP552-S-05/105.1D

3269PP552-S-05/105.1D

3269PP552-S-05/105.1E

3269PP552-S-05/105.1E

3269PP552-S-05/105.1A

3269PP552-S-05/105.1A

3269PP552-S-05/105.1A

3269PP552-S-05/105.1B
E E

TO BUS COUPLER TO LINE-3 TO LINE-4 TO ST-2 TO ST-1 TO FUTURE TO FUTURE TO FUTURE


BAY-206 BAY-207 BAY-208 BAY-209 BAY-210 BAY-211 BAY-212 BAY-213

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 010 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DC SOURCE-1 DISTRIBUTION CKT. REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 011
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DC SUPPLY TO 87CUB RELAY DC SUPPLY TO ICT-1 BAY DC SUPPLY TO LINE-1 BAY DC SUPPLY TO LINE-2 BAY DC SUPPLY TO ICT-2 BAY DC SUPPLY TO TBC BAY

A +2BB A

MCB15 MCB16 MCB17 MCB18 MCB19 MCB20


1 2 1 2 1 2 1 2 1 2 1 2
.2C .3C .4C .5C .6C .7C
3 4 3 4 3 4 3 4 3 4 3 4
12 12 12 12 12 12
11 14 /013.2E 11 14 /013.2E 11 14 /013.3E 11 14 /013.3E 11 14 /013.4E 11 14 /013.4E

TO DC SOURCE-2
SELECTOR CKT.

/008.4E J21 J21


B /012.1B B

DISTN.CKT.
FROM DC
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

/008.4E J22 J22


/012.1B
1

3
MCB15 MCB16 MCB17 MCB18 MCB19 MCB20
.2A .3A .4A .5A .6A .6A
2

4
4A 6A 6A 6A 6A 6A
C C

P411

P412

P421

P422

P431

P432

P441

P442

P451

P452
P401

P402
/015.1F
/015.1B

D D
TO 87 CUB RELAY

X203 X203 X203 X203 X203 X203 X203 X203 X203 X203
5 6 7 8 9 10 11 12 13 14

+ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +ADJ. PANEL

3269PP552-S-05/109.1C

3269PP552-S-05/109.1C

3269PP552-S-05/109.1C

3269PP552-S-05/109.1C

3269PP552-S-05/109.1C

3269PP552-S-05/109.1D
3269PP552-S-05/109.1B

3269PP552-S-05/109.1B

3269PP552-S-05/109.1B

3269PP552-S-05/109.1B

E E

TO ICT-1 TO LINE-1 TO LINE-2 TO ICT-2 TO TBC


BAY-201 BAY-202 BAY-203 BAY-204 BAY-205

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 011 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DC SOURCE-2 DISTRIBUTION CKT. REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 012
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DC SUPPLY TO BC BAY DC SUPPLY TO LINE-3 BAY DC SUPPLY TO LINE-4 BAY DC SUPPLY TO ST-2 BAY DC SUPPLY TO ST-1 BAY DC SUPPLY TO FUTURE BAY DC SUPPLY TO FUTURE BAY DC SUPPLY TO FUTURE BAY

A +2BB A

MCB21 MCB22 MCB23 MCB24 MCB25 MCB26 MCB27 MCB28


1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
.1C .2C .3C .4C .5C .6C .7C .8C
3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4
12 12 12 12 12 12 12 12
11 14 /013.4E 11 14 /013.5E 11 14 /013.5E 11 14 /013.6E 11 14 /013.6E 11 14 /013.7E 11 14 /013.7E 11 14 /013.8E

/011.7B J21
B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

/011.7B J22

C C
1

3
MCB21 MCB22 MCB23 MCB24 MCB25 MCB26 MCB27 MCB28
.1A .2A .3A .4A .5A .6A .6A .7A
2

4
6A 6A 6A 6A 6A 6A 6A 6A
P461

P462

P471

P472

P481

P482

P491

P492

P501

P502

P511

P512

P521

P522

P531

P532
D D

X203 X203 X203 X203 X203 X203 X203 X203 X203 X203 X1 X1 X1 X1 X1 X1
13 14 15 16 17 18
15 16 17 18 19 20 1 2 3 4

+ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +ADJ. PANEL +FUTURE BAY +FUTURE BAY +FUTURE BAY
3269PP552-S-05/109.1D

3269PP552-S-05/109.1D

3269PP552-S-05/109.1D

3269PP552-S-05/109.1D

3269PP552-S-05/109.1E

3269PP552-S-05/109.1E

3269PP552-S-05/109.1A

3269PP552-S-05/109.1A

3269PP552-S-05/109.1A

3269PP552-S-05/109.1B
E E

TO BUS COUPLER TO LINE-3 TO LINE-4 TO ST-2 TO ST-1 TO FUTURE TO FUTURE TO FUTURE


BAY-206 BAY-207 BAY-208 BAY-209 BAY-210 BAY-211 BAY-212 BAY-213

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 012 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DC SOURCE-2 DISTRIBUTION CKT. REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 013
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A +2BB A

/015.7B P402
DC-1 MCB’s TRIP TO 87CUB

B 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 B
MCB1 MCB2 MCB3 MCB4 MCB5 MCB6 MCB7 MCB8 MCB9 MCB10 MCB11 MCB12 MCB13 MCB14
/009.2A /009.3A /009.4A /009.5A /009.6A /009.7A /010.1A /010.2A /010.3A /010.4A /010.5A /010.6A /010.6A /010.7A
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

14 14 14 14 14 14 14 14 14 14 14 14 14 14

P419
/015.7C
C C

/014.7B P103

D D
DC-2 MCB’s TO 87CUA

12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11 12 11

MCB15 MCB16 MCB17 MCB18 MCB19 MCB20 MCB21 MCB22 MCB23 MCB24 MCB25 MCB26 MCB27 MCB28
/011.2A /011.3A /011.4A /011.5A /011.6A /011.6A /012.1A /012.2A /012.3A /012.4A /012.5A /012.6A /012.6A /012.7A

14 14 14 14 14 14 14 14 14 14 14 14 14 14

E E

P119
/014.7C

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 013 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DC MCB FAIL CKT. REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 014
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
B/B PROTN. ZONE-1 IN B/B PROTN. ZONE-1 OUT B/B PROTN. ZONE-2 IN B/B PROTN. ZONE-2 OUT GRP-A BB TRIP RELAY DC SOURCE-2 FAIL/MCB
ACMCB TRIPPED CUB RELAY FAULTY
SERVICE OF SERVICE SERVICE OF SERVICE RESET TRIPPED

A +2BB A

/009.2D P101

S1
BLKA
/023.5B
R1

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

P103
/013.1D
BSS1 BSS2
12 11 5 1
13 L11
1 3 1 3 MCB91 PB01 80DC2 WD1
/007.5C /023.6B /008.7C
M-1B/B Z-1 IN M-1B/B Z-1 IN M-1B/B Z-2 IN M-1B/B Z-2 IN 87CUB

/013.1E
/023.2B M-1 B/B Z-1 OUT /023.2B M-1 B/B Z-1 OUT /023.4B M-1 B/B Z-2 OUT /023.4B M-1 B/B Z-2 OUT 14 /022.5D
2 4 2 4 14 3
C C
L12

P119
P103

P105

P107

P109

P113

P115

P117
P741
+

L2 K2 K4 K6 K8 K10 K12 K14 K16


87CUA
/021.2B

P741
D 87CUA D
/021.5E

- K1 K3 K5 K7 K9 K11 K13 K15


L1
P104

E E

R2
BLKA
/023.5B
S2

/009.2D P102

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 014 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION BUSBAR PROTN CENTRAL UNIT CKT. REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 015
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
B/B PROTN. ZONE-1 IN B/B PROTN. ZONE-1 OUT B/B PROTN. ZONE-2 IN B/B PROTN. ZONE-2 OUT GRP-B BB TRIP RELAY DC SOURCE-1 FAIL/MCB
SPARE CUA RELAY FAULTY
SERVICE OF SERVICE SERVICE OF SERVICE RESET TRIPPED

A +2BB A

/011.2D P401

S1
BLKB
/023.5D
R1

B B

P402
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

BSS3 BSS4

/013.1A
X4 5 1 L11
1
1 3 1 3 WD1
M-2 B/B Z-1 IN M-2 B/B Z-1 IN M-2 B/B Z-2 IN M-2 B/B Z-2 IN 23 80DC1 87CUA
/023.2D M-2 B/B Z-1 OUT /023.2D M-2 B/B Z-1 OUT /023.4D M-2 B/B Z-2 OUT /023.4D M-2 B/B Z-2 OUT /008.7B /021.5D
2 4 2 4 PB01
/023.6B

/013.1C
24 3 L12

C C
X4
2

P419

P419A
P402

P405

P407

P409

P413

P415

P417

P419
P741
+

L2 K2 K4 K6 K8 K10 K12 K14 K16


87CUB
/022.2B

D D
P741
87CUB
/022.5E

- K1 K3 K5 K7 K9 K11 K13 K15


L1

E E
P404

R2
BLKB
/023.5D
S2

/011.2D P402

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 015 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION BUSBAR PROTN CENTRAL UNIT CKT. REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 016
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+2BB

A P741 A
CENTRAL UNIT
87CUA
/021.3B
POSITION-A

TX1 RX1 TX2 RX2 TX3 RX3 TX4 RX4

B B

+201ATA +202LA +203LA +204ATA


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

RX TX RX TX RX TX RX TX

P743 P743 P743 P743


PUA PUA PUA PUA
3269PP552-S-01/078.3B 3269PP552-S-02/105.3B

C PERIPHERAL UNIT PERIPHERAL UNIT PERIPHERAL UNIT PERIPHERAL UNIT C

+2BB

P741
87CUA CENTRAL UNIT
/021.3C
POSITION-B

D D

TX1 RX1 TX2 RX2 TX3 RX3 TX4 RX4

+205TBCA +206BCA +207LA +208LA

E E
RX TX RX TX RX TX RX TX

P743 P743 P743 P743


PUA PUA PUA PUA
3269PP552-S-05/070.3B 3269PP552-S-06/070.3B

PERIPHERAL UNIT PERIPHERAL UNIT PERIPHERAL UNIT PERIPHERAL UNIT

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 016 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION FIBRE OPTIC INTERFACE CIRCUIT REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 017
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
+2BB

P741
CENTRAL UNIT
87CUA
/021.3D
POSITION-C

B TX1 RX1 TX2 RX2 TX3 RX3 TX4 RX4 B


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

+209STA +210STA

RX TX RX TX

C C
P743 P743
PUA PUA
3269PP552-S-09/093.3B

PERIPHERAL UNIT PERIPHERAL UNIT

+2BB

P741
87CUA
D /021.2D D
POSITION-D

TX1 RX1 TX2 RX2 TX3 RX3 TX4 RX4

E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 017 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION FIBRE OPTIC INTERFACE CIRCUIT REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 018
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+2BB

A P741 A
CENTRAL UNIT
87CUB
/022.3B
POSITION-A

TX1 RX1 TX2 RX2 TX3 RX3 TX4 RX4

B B

+201ATA +202LA +203LA +204ATA


This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

RX TX RX TX RX TX RX TX

P743 P743 P743 P743


PUB PUB PUB PUB
3269PP552-S-01/079.3B 3269PP552-S-02/106.3B

C PERIPHERAL UNIT PERIPHERAL UNIT PERIPHERAL UNIT PERIPHERAL UNIT C

+2BB

P741
87CUB CENTRAL UNIT
/022.3C
POSITION-B

D D

TX1 RX1 TX2 RX2 TX3 RX3 TX4 RX4

+205TBCA +206BCA +207LA +208LA

E E
RX TX RX TX RX TX RX TX

P743 P743 P743 P743


PUB PUB PUB PUB
3269PP552-S-05/071.3B 3269PP552-S-06/071.3B

PERIPHERAL UNIT PERIPHERAL UNIT PERIPHERAL UNIT PERIPHERAL UNIT

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 018 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION FIBRE OPTIC INTERFACE CIRCUIT REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 019
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

+2BB

P741
CENTRAL UNIT
87CUB
/022.3D
POSITION-C

B B
TX1 RX1 TX2 RX2 TX3 RX3 TX4 RX4
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

+209STA +210STA

RX TX RX TX
C C
P743 P743
PUB PUB
3269PP552-S-09/094.3B

PERIPHERAL UNIT PERIPHERAL UNIT

+2BB
D D
P741
87CUB
/022.2D
POSITION-D

TX1 RX1 TX2 RX2 TX3 RX3 TX4 RX4

E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 019 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION FIBRE OPTIC INTERFACE CIRCUIT REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 020
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
+2BB

B B
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

8 8 J13 J14 J13 J14


RL7 RL7
C 80DC1 80DC2 87CUA 87CUB C
/008.7B /008.7C /021.5C /022.5C

10 10 J15 J15
U1

U2

U3

U4

U5

U6

U7

U8
X7 X7 X7 X7
1 2 3 4 5 6 7 8

D D

E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 020 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION SPARE CONTACT DISTRIBUTION REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 021
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02
DATED :26.12.2012 PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+2BB

A A

87CUA 87CUA

TX1 TX1
K1 J1
K2 J2 RL1
RX1 RX1

K3 J3
TX2 TX2
K4 J4 RL2

POSITION-A

POSITION-E
B RX2 RX2 B
K5 J5
/016.3B
K6 J6 RL3
TX3 TX3
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

K7 J7
RX3 RX3
K8 J8 RL4

/014.2D TX4 TX4


K9 J9
K10 J10 RL5
RX4 RX4

K11 J11
K12 J12 RL6 MiCOM P741 LED CONFIGARATION
TX1
(DEDICATED LED's)
C K13 J14 C
RX1
K14 /020.5C J13
SPARE RL7
J15 TRIP
TX2
K15
J17
POSITION-B

K16 ALARM
RX2
J16
/016.3D J18 RL8
TX3 OUT OF SERVICE

RX3 HEALTHY

TX1
TX4
RX1 MiCOMP741 LED CONFIGARATION
D RX4 D
L11
TX2
POSITION-D

/015.8C L12 WD1


TO 87CUB (CUA FAIL)

RX2 TX1 FIBRE COM ERROR


L13
/017.3E
L14 WD2 ZONE-1 OPTD.
TX3 RX1

RX3 TX2 ZONE-2 OPTD.


POSITION-C

TX4 RX2 CT CIRCUIT FAULTY

/017.3B
RX4 TX3 ZONE-1 OUT OF SERVICE

E L2 -
E
RX3 ZONE-2 OUT OF SERVICE

/014.1D
L1 + SPARE
TX4

RX4 SPARE

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 021 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DEVICE REFERENCE REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 022
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+2BB

A A

87CUB 87CUB

TX1 TX1
K1 J1
K2 J2 RL1
RX1 RX1

K3 J3
TX2 TX2
K4 J4 RL2

POSITION-A

POSITION-E
B RX2 RX2 B
K5 J5
/018.3B
K6 J6 RL3
TX3 TX3
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

K7 J7
RX3 RX3
K8 J8 RL4

/015.2D TX4 TX4


K9 J9
K10 J10 RL5
RX4 RX4

K11 J11
K12 J12 RL6 MiCOM P741 LED CONFIGARATION
TX1
(DEDICATED LED's)
C K13 J14 C
RX1
K14 /020.5C J13
SPARE RL7
J15 TRIP
TX2
K15
J17
POSITION-B

K16 ALARM
RX2
J16
/018.3D J18 RL8
TX3 OUT OF SERVICE

RX3 HEALTHY

TX1
TX4
RX1 MiCOMP741 LED CONFIGARATION
D RX4 D
L11
TX2
POSITION-D

/014.8C L12 WD1


TO 87CUA (CUB FAIL)

RX2 TX1 FIBRE COM ERROR


L13
/019.3E
L14 WD2 ZONE-1 OPTD.
TX3 RX1

RX3 TX2 ZONE-2 OPTD.


POSITION-C

TX4 RX2 CT CIRCUIT FAULTY

/019.3B
RX4 TX3 ZONE-1 OUT OF SERVICE

E L2 -
E
RX3 ZONE-2 OUT OF SERVICE

/015.1D
L1 + SPARE
TX4

RX4 SPARE

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 022 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DEVICE REFERENCE REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 023
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+2BB

A A

BSS1 BSS2

B/B Z-1 OUT

B/B Z-2 OUT


B/B Z-1 IN

B/B Z-2 IN
1 2 /014.2C 1 2 /014.4C
BLKA PB01
3 4 /014.3C 3 4 /014.5C 13 14 /014.6C
S1 R1 /014.1B

S2 R2 /014.1E 23 24 /015.6C
5 6 5 6
S3 R3 33 34
B B
7 8 7 8 S4 R4 43 44

S5 R5
9 10 9 10
S6 R6
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

11 12 11 12 S7 R7

S8 R8
13 14 13 14
S9 R9

S10 R10
15 16 15 16

C C

BLKB
S1 R1 /015.1B
BSS3 BSS4
B/B Z-1 OUT

B/B Z-2 OUT


S2 R2 /015.1F
B/B Z-1 IN

B/B Z-2 IN
S3 R3
D S4 R4 D
1 2 /015.2C 1 2 /015.4C S5 R5

S6 R6
3 4 /015.3C 3 4 /015.5C
S7 R7
5 6 5 6 S8 R8

S9 R9
7 8 7 8
S10 R10

9 10 9 10

11 12 11 12

E E
13 14 13 14

15 16 15 16

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 023 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION DEVICE REFERENCE REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: 024
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+2BB

TAG REF TAG REF TAG REF TAG REF TAG REF TAG REF
A X1 : 1 /007.5B X4 : 1 /015.5C X7 : 1 /020.3D X201 : 1 3269PP552-S-05/093.1A,/007.4B X202 : 1 3269PP552-S-05/105.1A,/010.4D X203 : 1 3269PP552-S-05/109.1A,/012.4D A
X1 : 2 /007.5B X4 : 2 /015.5C X7 : 2 /020.3D X201 : 2 3269PP552-S-05/093.1A,/007.4B X202 : 2 /010.4D,3269PP552-S-05/105.1A X203 : 2 3269PP552-S-05/109.1A,/012.4D
X1 : 3 /008.1B X4 : 3 SPARE X7 : 3 /020.4D X201 : 3 SPARE X202 : 3 /010.5D,3269PP552-S-05/105.1A X203 : 3 /012.5D,3269PP552-S-05/109.1A
X1 : 4 /008.1B X4 : 4 SPARE X7 : 4 /020.4D X201 : 4 SPARE X202 : 4 3269PP552-S-05/105.1B,/010.5D X203 : 4 3269PP552-S-05/109.1B,/012.5D
X1 : 5 /008.4B X7 : 5 /020.5D X201 : 5 SPARE X202 : 5 3269PP552-S-05/105.1B,/009.3D X203 : 5 /011.3D,3269PP552-S-05/109.1B
X1 : 6 /008.4B X7 : 6 /020.5D X201 : 6 SPARE X202 : 6 /009.3D,3269PP552-S-05/105.1B X203 : 6 3269PP552-S-05/109.1B,/011.3D
X1 : 7 /010.6D X7 : 7 /020.5D X202 : 7 /009.4D,3269PP552-S-05/105.1B X203 : 7 /011.4D,3269PP552-S-05/109.1B
X1 : 8 /010.6D X7 : 8 /020.6D X202 : 8 /009.4D,3269PP552-S-05/105.1B X203 : 8 3269PP552-S-05/109.1B,/011.4D
X1 : 9 /010.7D X7 : 9 SPARE X202 : 9 3269PP552-S-05/105.1C,/009.5D X203 : 9 3269PP552-S-05/109.1C,/011.5D
X1 : 10 /010.7D X7 : 10 SPARE X202 : 10 /009.5D,3269PP552-S-05/105.1C X203 : 10 3269PP552-S-05/109.1C,/011.5D
X1 : 11 /010.8D X7 : 11 SPARE X202 : 11 3269PP552-S-05/105.1C,/009.6D X203 : 11 3269PP552-S-05/109.1C,/011.6D
X1 : 12 /010.8D X7 : 12 SPARE X202 : 12 /009.6D,3269PP552-S-05/105.1C X203 : 12 3269PP552-S-05/109.1C,/011.6D
X1 : 13 /012.6D X7 : 13 SPARE X202 : 13 3269PP552-S-05/105.1C,/009.7D X203 : 13 3269PP552-S-05/109.1C,/011.7D
B B
X1 : 14 /012.6D X7 : 14 SPARE X202 : 14 3269PP552-S-05/105.1D,/009.7D X203 : 14 /011.7D,3269PP552-S-05/109.1D
X1 : 15 /012.7D X7 : 15 SPARE X202 : 15 3269PP552-S-05/105.1D,/010.1D X203 : 15 /012.1D,3269PP552-S-05/109.1D
X1 : 16 /012.7D X202 : 16 3269PP552-S-05/105.1D,/010.1D X203 : 16 3269PP552-S-05/109.1D,/012.1D
X1 : 17 /012.8D X202 : 17 3269PP552-S-05/105.1D,/010.2D X203 : 17 /012.2D,3269PP552-S-05/109.1D
This document is the exclusive property of Schneider Electric and shall not be used, copied or communicated to third parties without prior authorization.

X1 : 18 /012.8D X202 : 18 /010.2D,3269PP552-S-05/105.1D X203 : 18 /012.2D,3269PP552-S-05/109.1D


X1 : 19 SPARE X202 : 19 3269PP552-S-05/105.1E,/010.3D X203 : 19 3269PP552-S-05/109.1E,/012.3D
X1 : 20 SPARE X202 : 20 3269PP552-S-05/105.1E,/010.3D X203 : 20 3269PP552-S-05/109.1E,/012.3D
X1 : 21 SPARE
X1 : 22 SPARE

C C

D D

E E

F CUSTOMER : BAJAJ INFRASTRUCTURE DEVELOPMENT CLIENT: LALITPUR POWER GENERATION COMPANY TITLE : 220kV BUSBAR PROTECTION PANEL PREPARED : GD REVISION: C SHT : 024 F
COMPANY LTD. LIMITED.
PROJECT : 3x660MW SUPER CRITICAL TPP - LALITPUR, UP CONTRACTOR: L&T CONSTRUCTION TERMINAL BLOCK ALLOCATION REVIEWED : THY
DATE: 16/07/2013
POWER TRANSMISSION & DISTRIBUTION APPROVED : APS CONT: NIL
PO. No.& Date: L&T/PT&D/SS/BIDCO /LOA/02 BIDCO DRG. NO: BE-LAL-EEV-109-J-0043
DATED :26.12.2012 L&T DRG. NO: O12166-E-SY-VD-RP-2006
PANEL TYPE : +2BB DRG. NO.: 3269PP552-S-11