Universiti Tenaga Nasional

Electrical Power System I (EEPB353) Name : ________________________________________________


Test 2 – August 2015. ( Sem1 – 15/16 ) SID : __________________________________________
Answer ALL two (2) questions.
Time allocated is 75 minutes. [ 25 +25 = 50 marks. ] Section : ______________________________________
Lecturer : ____________________________________

Question 1 : [25 marks] [10+5+5+5 = 25 marks]


A 15kVA, 2300/230V single-phase Transformer X was subjected to the following test conditions:
Open Circuit Test : Rated voltage is applied to the high voltage winding and the low voltage winding is
open-circuited. Under this condition, the current into the high voltage winding is 0.21A and the power taken
from the high voltage source is 100W.
Short Circuit Test: A reduced voltage of 47V is applied to the high voltage winding and the low voltage
winding is short-circuited. Under this condition, the current flowing into the high voltage winding is 6.5A
and the power taken from the high voltage source is 160W.

a) From the data given above, determine the Voltage Regulation AND Efficiency of the transformer
when it is supplying at full load, 0.8 power factor lagging, and a terminal voltage of 230V. (17 marks)

b) Transformer Y from a different manufacturer has the same rating (15kVA, 2300/230V) with
Transformer X, but Transformer Y has a different series impedance of 0.02 + j0.05 ohm (referred
to the LV side) and zero core losses. Transformer Y is supplying the same load conditions as in
part(a).
Which transformer would you choose and justify why (calculations required)? (8 marks)

Question 3 : [25 marks] [10+5+10 = 25 marks]


A three-phase power system network with its ratings is as shown in figure below. The connected loads
are , Load 1 = 5MW + j2Mvar and Load 2 = 30MW + j10Mvar

60MVA
11kV 50MVA 50MVA
11/132kV 132/33kV
X = 6% 1 X = 10%
2 3 X = 8%
4
132kV
G
X = + j52.272W
T1 T2
5 MW + j2 Mvar 30 MW + j10 Mvar

It is required to hold the voltage at Bus_4 at 320 kV. Use 100 MVA base and 11kV as the voltage base
at the generator. Working in per-unit, determine:

a) The actual voltage of Bus_2 (V2). (Show all workings to receive full credit) [10 marks]
b) The actual internal emf (EG)of the generator. [5 marks]
c) Proof that current drawn from generator is equal to the sum of currents consumed by
Load 1(5MW+j2Mvar) and Load 2(30MW+j10Mvar) . (Hint: Use Bus_2 as reference.) [10 marks]
Standard List of Formulae for EEPB353.

1. TRANSFORMER

𝑉1 = 𝑉2′ + (𝑅𝑒1 + 𝑗𝑋𝑒1 )𝐼2′ , 𝑉1′ = 𝑉2 + (𝑅𝑒2 + 𝑗𝑋𝑒2 )𝐼2 , 2


𝑋𝑒1 = √𝑍𝑒1 2
− 𝑅𝑒1

𝑉12 𝑉 𝑉 𝑉𝑠𝑐 𝑃𝑠𝑐


𝑅𝐶 = , 𝐼𝐶 = 𝑅1 , 𝐼𝑚 = √𝐼02 − 𝐼𝐶2 , 𝑋𝑚 = 𝐼 1 , 𝑍𝑒1 = , 𝑅𝑒1 = 2
𝑃0 𝐶 𝑚 𝐼𝑠𝑐 𝐼𝑠𝑐

𝑛×𝑆×𝑝𝑓 𝑉2𝑛𝑙 −𝑉2


𝜂 = (𝑛×𝑆×𝑝𝑓)+(𝑛2 , % 𝑉𝑅 = × 100 , 𝑃𝑐𝑢 = 3𝑅𝑒2 𝐼22
×𝑃𝑐𝑢 )+𝑃𝑐 𝑉2

2. PER UNIT SYSTEM


2
SB (𝑉𝐵 )2 ∗ 𝑉𝑝𝑢 𝑉2
IB = , 𝑍𝐵 = , 𝑆𝑝𝑢 = 𝑉𝑝𝑢 × 𝐼𝑝𝑢 , 𝑍𝑝𝑢 = 𝑆∗ , 𝑍𝑃 = 𝑆 ∗ 𝐿𝐿 ,
√3VB 𝑆𝐵 𝐿𝑝𝑢 𝐿(3∅)

𝑉𝑝 3𝑉𝑝2 𝑉2 𝑍𝑝 𝑉 2 𝑆𝐵
𝐼𝑝 = 𝑍 , 𝑍𝑝 = 𝑆 ∗ = 𝑆 ∗ 𝐿𝐿 , 𝑍𝑝𝑢 = 𝑍 = ( 𝑉𝐿𝐿 ) ∗
𝑝 𝐿−3∅ 𝐿−3∅ 𝐵 𝐵 𝑆𝐿−3∅

𝑛𝑒𝑤 𝑛𝑒𝑤 2
𝑛𝑒𝑤 Ω 𝑍 𝑆𝐵 𝑛𝑒𝑤 𝑜𝑙𝑑 𝑆𝐵 𝑉 𝑜𝑙𝑑
𝑍𝑝𝑢 = 𝑍 𝑛𝑒𝑤 = 𝑍Ω 2 , 𝑍𝑝𝑢 = 𝑍𝑝𝑢 𝑜𝑙𝑑 (𝑉𝐵𝑛𝑒𝑤 )
𝐵 (𝑉𝐵𝑛𝑒𝑤 ) 𝑆𝐵 𝐵