a) From the data given above, determine the Voltage Regulation AND Efficiency of the transformer
when it is supplying at full load, 0.8 power factor lagging, and a terminal voltage of 230V. (17 marks)
b) Transformer Y from a different manufacturer has the same rating (15kVA, 2300/230V) with
Transformer X, but Transformer Y has a different series impedance of 0.02 + j0.05 ohm (referred
to the LV side) and zero core losses. Transformer Y is supplying the same load conditions as in
part(a).
Which transformer would you choose and justify why (calculations required)? (8 marks)
60MVA
11kV 50MVA 50MVA
11/132kV 132/33kV
X = 6% 1 X = 10%
2 3 X = 8%
4
132kV
G
X = + j52.272W
T1 T2
5 MW + j2 Mvar 30 MW + j10 Mvar
It is required to hold the voltage at Bus_4 at 320 kV. Use 100 MVA base and 11kV as the voltage base
at the generator. Working in per-unit, determine:
a) The actual voltage of Bus_2 (V2). (Show all workings to receive full credit) [10 marks]
b) The actual internal emf (EG)of the generator. [5 marks]
c) Proof that current drawn from generator is equal to the sum of currents consumed by
Load 1(5MW+j2Mvar) and Load 2(30MW+j10Mvar) . (Hint: Use Bus_2 as reference.) [10 marks]
Standard List of Formulae for EEPB353.
1. TRANSFORMER
𝑉𝑝 3𝑉𝑝2 𝑉2 𝑍𝑝 𝑉 2 𝑆𝐵
𝐼𝑝 = 𝑍 , 𝑍𝑝 = 𝑆 ∗ = 𝑆 ∗ 𝐿𝐿 , 𝑍𝑝𝑢 = 𝑍 = ( 𝑉𝐿𝐿 ) ∗
𝑝 𝐿−3∅ 𝐿−3∅ 𝐵 𝐵 𝑆𝐿−3∅
𝑛𝑒𝑤 𝑛𝑒𝑤 2
𝑛𝑒𝑤 Ω 𝑍 𝑆𝐵 𝑛𝑒𝑤 𝑜𝑙𝑑 𝑆𝐵 𝑉 𝑜𝑙𝑑
𝑍𝑝𝑢 = 𝑍 𝑛𝑒𝑤 = 𝑍Ω 2 , 𝑍𝑝𝑢 = 𝑍𝑝𝑢 𝑜𝑙𝑑 (𝑉𝐵𝑛𝑒𝑤 )
𝐵 (𝑉𝐵𝑛𝑒𝑤 ) 𝑆𝐵 𝐵