26 27 26
WIRING DEVICES
Contents
1.0 GENERAL
1.1 Reference
Design, Supply, Installation all low voltage and ELV wiring devices.
1.3.1 Design, manufacture, testing and method of installation of all apparatus and
materials furnished under requirements of these specifications shall conform to
latest publications or standard rules of the following:
c) British Standards.
The following Codes and Standards to the extent specified herein, form a part
of this specification. When an edition date is not indicated for a Code or
Standard the latest edition enforce at the time of proposal submitted shall apply.
1.4 Submittals
2.0 PRODUCTS
2.1 Switches
2.1.1 Light switches and sockets finish shall be metal plate in silver colour from the
manufacturers standard range of products rating and type as per
CONSULTANT selection.
2.1.3 All switches shall be installed in boxes with adjustable lugs to ensure front
plate is true, and square. Flush boxes shall finish flush with the wall surface
and overlapping front plates shall be used. Boxes shall be suitable for the
wiring system used.
2.1.4 All switches shall be 10/15 Ampere grid type as shown on the floor plans.
2.1.6 Switches shall be suitable for back and side wiring with 4.0 MM2 or 2 x 2.5
MM2 standard conductors.
2.2.1 13A and 15A Socket outlets shall comply to BS 1363 and BS 546 as
appropriate switched and shuttered and mounted in ring or multiple assemblies
and shall be of the type and rating as specified / indicated on the drawing.
All socket outlets shall be of double pole switched and with tamper proof
shutters on the live, neutral and earth connection.
2.2.2 All 13A standard switched socket outlets shall be with two earth terminals to
provide high integrity earthing to comply with section 607 of BS 7671.
2.2.3 All 13A standard switched socket outlets to be fed from emergency power
supply system (by standby diesel generator set) in case of failure of normal
power supply shall be of ‘white’ in colour but with ‘red’ rockers for easy
identification.
2.2.4 All the switched socket outlets and other connection points, shall be provided
with neon indicator where it is desirable to have a visual indication of the
presence or absence of power to the equipment. (eg: fridge, fire alarm panel,
etc) as per end user requirements.
2.2.5 All outdoor socket outlets shall be of weather protected type to IP 55 minimum
and incorporated with a 30 mA RCD in accoradnce with ADDC requirements.
The outdoor socket outlets shall be of high impact resistant polycarbonate.
2.2.6 Socket outlets shall be complete with boxes not less than 35mm deep and the
box shall have a suitably mounted brass protective conductor terminal.
Socket outlets installed in flush installations shall have overlapping front plates.
In surface installations front plates shall be flush with the sides of the box and
shall be metal clad unless otherwise specified.
2.2.7 Where socket outlets are installed on perimeter paneling, metal frames for
panel mounting shall be provided.
2.2.8 The earth pin of the socket shall be connected to the box earth terminal with a
green and yellow PVC-insulated protective conductor. Cover screws are not
acceptable for earth continuity.
2.2.10 Socket outlets for voltages other than 240V for single phase and 400 for three
phase supply shall be color coded in accordance to be BSEN60309-2 and shall
allow plugging of only similar rated voltages plugs.
2.2.11 Socket outlet shall be suitable for back and side wiring with 1 x 6.0 mm 2 or 2 x
4.0 mm2 standard conductors.
Ceiling rose shall be made of white plastic and manufactured in accordance with
BS 67: 1987. The ceiling rose shall incorporate tunnel type terminals with
backed out terminal screws with capacity of 3x2.5mm2. The ceiling rose shall
be suitable for mounting over a circular conduit box to BS 45 68.PT2.
Flexible outlet shall be rated 20A or 45A. The flexible outlet shall be complete
with 3 pair of terminals each suitable for 4mm2 conductor and 10mm diameter
cord outlet for the 20 A flex outlet and with 3 pair of terminals each suitable for
10mm2 conductor for the 45A. The flexible outlet shall be provided with
moulded cover and cable clamp.
The 20A double pole switch shall be manufactured to BS 3676 Part 1 1989 and
shall be fitted with neon indicator. The double pole switch supplied for the water
heaters shall be engraved ‘Water Heater’.
3.0 EXECUTION
3.1 Installation
3.1.1 Install single throw switches with lever in "UP" position when switch is closed.
3.1.2 All accessories shall be properly aligned with vertical edges plumb and
horizontal edges level.
3.1.2 Install switches in gang type outlet boxes with ganged coverplate when more
than one device is shown in one location.
3.1.3 Cover plates shall be screwless stainless steel type and to be installed after all
painting has been completed.
3.1.4 Provide phase barriers where more than one phase enters a lighting switch,
panel.
3.1.5 All electrical accessories (switching, sockets, etc) shall be provided with tag to
THE CONSULTANT approval indicating, feeding circuit reference and the
related distribution board number.