Professional Documents
Culture Documents
1 Scope............................................................. 2
2 Conflicts and Deviations................................. 2
3 References..................................................... 2
4 Information Required with Quotation.............. 3
5 Definitions....................................................... 4
6 General........................................................... 5
7 Rating............................................................. 5
8 Enclosure....................................................... 5
9 Conductors..................................................... 6
10 Retrofit/Replacement
Vacuum Circuit Breakers........................ 7
11 Interlocks........................................................ 8
12 Accessories.................................................... 9
13 Nameplates and Marking............................... 9
14 Testing............................................................ 9
1 Scope
2.1 If there are any conflicts between this Specification and associated purchasing,
project or engineering documents, this specification shall take precedence.
2.2 Direct all requests to deviate from this Specification in writing to the Company
or Buyer Representative, who shall follow internal company waiver procedure.
3 References
The following is a summary of all the documents which have been mentioned within
this Specification. The specific part(s) of these documents which are applicable have
been identified throughout this Specification.
Page 2 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
4.1 The following is a list of the information that shall be supplied with the
Quotation for each Retrofit/Replacement Vacuum Circuit Breaker design.
This information shall be reviewed by CSD, and approval obtained prior to
placing an order for Retrofit/Replacement Vacuum Circuit Breakers to be used
in any Saudi Aramco facility.
a) “Certified Test Reports/Certificates” as specified in testing Section 14
b) User's List of the same or similar equipment, which has been in service for
a minimum of two (2) years. List should indicate:
i) User company name, address, contact information (telephone, Fax,
email)
ii) Installation site
Page 3 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
4.2 The items listed in paragraph 4.1 are necessary to complete the technical
evaluation of the Quotation. The Quotations shall be considered technically
unacceptable if any of the items listed in paragraph 4.1 are not submitted with
the Quotation. The items listed in paragraph 4.1 are in addition to the
information specified within the Quotation Request or the Purchase Order
documents (e.g., information required within Saudi Aramco Form NMR-(to be
assigned).
4.3 The “Certified Test Reports/Certificates” mentioned within paragraph 4.1 shall
be from, or endorsed by, an independent testing laboratory or Saudi Aramco
approved third party and shall provide with clear, traceable evidence that the
subject tests were performed.
5 Definitions
Conductor: All material, devices and parts which are expected to carry current as part
of their normal function (e.g., cable, bus, relay contacts, terminal block studs, etc.).
Main Circuit: All the conductive parts of an assembly included in a circuit, which is
intended to transmit electrical energy to the connected load.
Retro-fill: Terminology used to identify Vacuum circuit breakers and the associated
hardware used as a replacement for Air Magnetic circuit breakers or perhaps other
original manufactures Vacuum circuit breakers. The switchgear cell is usually modified
to accommodate the replacement vacuum circuit breaker thus preventing the use of the
original circuit breaker in the cell. Retro-fill Circuit Breakers are not acceptable.
Page 4 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
6 General
6.1 Whenever this specification requires compliance to a third party document, this
document shall be the edition referenced in this specification not the edition in
effect on the date of the Quotation Request.
6.2 This specification shall take precedence over any referenced third party
document.
6.4 Saudi Aramco inspection requirements are presented within Saudi Aramco Form
175-Special. This form is included with the Quotation Request or the Purchase
Order documents.
6.5 Saudi Aramco's nonmaterial requirements are presented within Saudi Aramco
Form NMR-Special. This form is included with the Quotation Request or the
Purchase Order documents.
7 Rating
7.1 The continuous, rms short circuit interrupting and close and latch current ratings
of the Retrofit/Replacement Vacuum Circuit Breaker shall be equal to or exceed
those of the Original Equipment Circuit Breaker to be replaced. The continuous
current ratings shall not be dependent on forced-air systems.
7.3 Saudi Aramco shall provide the nameplate ratings of the Original Equipment
Circuit Breaker as listed in Data Schedule 1.
7.4 The Vendor shall provide the ratings of the Retrofit/Replacement Vacuum
Page 5 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
8 Enclosure
The Vendor must inspect the switchgear cubicle(s) at the Saudi Aramco location that is
to be provided with a Retrofit/Replacement Vacuum Circuit Breaker and verify that the
data provided is correct and up to date. In addition, the Vendor will ensure that the
Retrofit/Replacement Vacuum Circuit Breaker will properly fit in the switchgear
cubicle(s), the existing control wiring is correctly shown in Saudi Aramco's drawings,
and the existing parts in the switchgear cubicle(s) are in good serviceable condition.
8.3 The Vendor shall ensure that the metal enclosed, metal clad, dead front design
of the switchgear cubicle and circuit breaker is maintained. No modifications
shall be made to the cubicle that interferes with or prevents use of the Original
Equipment Circuit Breaker at any time.
8.4 The door of the cubicle containing the Retrofit/Replacement Vacuum Circuit
Breaker shall be able to be closed and secured with the circuit breaker in the
connected, test and withdrawn positions.
9 Conductors
9.1 Material
9.1.2 Mating surfaces of all current carrying conductors shall be silver or tin
Page 6 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
plated.
9.2 Low voltage wiring for circuit breakers manufactured to North American
Standards shall be ANSI/NFPA 70; Type SIS, XHHW or THHN/THWN.
9.3 Low Voltage wiring for circuit breakers manufactured to IEC Standards shall be
85°C rated meeting the requirements of IEC 60227.
10.1 Be electrically and mechanically trip free, and shall be designed for remote and
local electrical closing and tripping.
Page 7 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
10.3 Connection to main circuit primary stationary stabs shall be via self-aligning
contacts, which exactly duplicate the primary disconnects of the Original
Equipment Circuit Breaker.
10.4 Breakers of the same type and rating shall be mechanically and electrically
interchangeable within the switchgear assembly.
11 Interlocks
11.1.1 Prevent the closing of the circuit breaker poles if it is between the
connected and test positions.
11.1.2 Prevent circuit breakers with different ratings from being inserted in
the same cubicle.
11.1.3 Prevent circuit breakers from being withdrawn from, or connected to,
the main circuit if the breaker poles are closed.
Page 8 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
11.1.5 Prevent circuit breakers from being inserted into the connected position
until the control/auxiliary circuits are connected.
12 Accessories
12.2 A complete detailed list of spare parts available from the Vendor shall be
supplied for each type Retrofit/Replacement Vacuum Circuit Breaker and shall
be included with the documents to be supplied with the quotation.
13.2 The Manufacturer's shop order number, date, and catalog designation should be
indicated on the Retrofit/Replacement Vacuum Circuit Breaker nameplate in
addition to the nameplate information required by the Standards indicated within
the data sheets.
13.3 The manufacturer's standard embossed metallic nameplate, complete with rating
information specified in ANSI/IEEE or IEC standards for metal clad switchgear
is acceptable. The nameplates shall be in the English language.
Page 9 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
14 Testing
Page 10 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
14.3 Equipment (including vacuum interrupters) shall be tested based upon their rated
voltage, not the operating voltage. For example, 15 kV interrupters used within
in 4.76 kV rated circuit breakers shall be field tested at 27 kV AC.
Revision Summary
14 October 2008 Editorial revision to replace Electrical Substations Equipment Standards Committee
Chairman and Vice Chairman.
Revised the "Next Planned Update".
10 April 2011 Minor revision to ensure the replacement is complying with the Arc Flash safety requirement.
Page 11 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
Data Schedule 1
Retrofit/Replacement Vacuum Circuit Breakers
Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
(Information Supplied by Saudi Aramco)
for each Original Equipment Circuit Breaker type and rating)
Page 12 of 13
Document Responsibility: Electrical Substations Equipment Standards Committee 16-SAMSS-522
Issue Date: 10 April 2011 Retrofit/Replacement Vacuum Circuit Breakers
Next Planned Update: 14 October 2013 Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
Data Schedule 2
Retrofit/Replacement Vacuum Circuit Breakers
Applied in Indoor Metal-Clad Switchgear: 1 to 38 kV
(Information Supplied by the Vendor with
Quotation for each Retrofit/Replacement Vacuum Circuit Breaker type and rating)
7 Rated Short Circuit Current, kA: _________ 15 Close and Latch Current, rms _________
Crest, kA:
Line No. Certified Design Test Data Check Mark Line No. Certified Conformance Test Data Check Mark
Page 13 of 13