Professional Documents
Culture Documents
Instrumentation
Packagers must provide safety shutdowns, controls, and instrumentation to ensure the compressor sys-
tem operates within published Ariel limits. The use of “alarm” instead of “shutdown” for any minimum
instrumentation requirement may result in equipment damage. Additional information for control and
instrumentation may be found in the appropriate Ariel Maintenance and Repair Manual.
NOTE: Ariel recommends the use of shipboard or armored cabling as opposed to wiring in
conduit to minimize nuisance shutdowns due to wire chafing and shorts. Cable in cable
trays also facilitates maintenance access.
CAUTION: DO NOT drill holes in cylinders or other pressure containing components for
any purpose. Epoxy-mounted clamps (to bare metal) for wiring and tubing are a suitable
alternative. See Ariel ER-89.10.
Notes
1. Install the compressor frame low lube oil pressure shutdown set to stop the unit if oil pressure down-
stream of the filter falls below 45 psig (3.1 barg). Compressor operation for only a few seconds
without oil pressure causes major damage. Normal oil pressure is about 60 psig (4.1 barg) at full
rated speed and normal operating temperature. The low oil pressure shutdown must activate after
oil pressure exceeds 45 psig (3.1 barg) at start-up. Ariel provides a 1/4 inch tubing fitting to connect
the low lube oil pressure shutdown and ties a tag to this connection before each compressor ships.
Do not operate the compressor for prolonged periods at less than 50 psig (3.4 barg) oil pressure.
2. Automated pre-lube systems require a start permissive to sense minimum required pressure/time at
oil gallery inlet. See ER-56.06. Unit must shut down if the system fails to achieve 45 psig (3.1 barg)
oil pressure within 10 seconds after crankshaft starts to turn.
3. Mount overhead lube oil supply tanks high enough to provide oil flow to the level control at all ambi-
ent temperatures.
4. On multi-nozzle cylinders, Ariel strongly recommends a temperature device in both discharge
nozzles.
5. Install the high lube oil inlet temperature shutdown at the filter inlet connection.
6. At a minimum, install one vibration shutdown for two and four throw frames and two for six throw
frames. Mount vibration devices near the top of the frame with the sensitive axis parallel to the piston
rod axis.
7. Install all safety shutdowns, controls, instrumentation, ignition systems, electrical devices, and high
temperature piping (gas discharge and engine exhaust) in accordance with good engineering prac-
tice and applicable codes for the area classification at the end user location. Ensure compatibility of
all systems for area classification.
8. If packing vent temperature is monitored, alarm and shutdown set points should be confirmed
through vent flow rates.
Ariel offers several lube system shutdown devices. See TABLE 2 for specifications on available types.
For detailed information about each device, visit the vendor literature section of www.arielcorp.com.
Shutdown Switch
The shutdown switch monitors divider block pin position and supplies a shutdown contact. If the divider
block stops cycling for a given time, the switch sends a shutdown signal to the control system.
For no flow shutdown devices, Normally Open (NO) refers to the switch state while the divider block
cycles or the unit runs. An NO switch means when the unit runs, the shutdown switch is open or non-
failsafe; the control system cannot detect damaged devices or loose or cut wires at startup and will
never stop the unit. A Normally Closed (NC) switch means when the unit runs, the shutdown switch is
closed or failsafe; the control system will detect a loose or cut wire and shutdown the unit.
Ariel recommends NC (failsafe) switches. However, when a NO (non-failsafe) switch is used, Ariel
recommends testing shutdown circuits at least once a month.
Proximity Switch
The proximity switch senses divider block piston position and changes switch state or pulses with every
position change. This device must work with a PLC or some other counter/timer device to produce a
shutdown. Some devices open the switch when the pin is in and close when the pin is out. Others pro-
duce a 0.5 second pulse when the pin moves in and out. With pulses, the control system must sense
switch cycling and stop the unit if a block stops cycling.
When using a proximity switch, a local cycle indicator is required for local monitoring of lube cycle times.
Ariel recommends a control system set to find the time between triggered cycles when the switch trans-
itions from off to on. See FIGURE 2.
1. Shutdown Time with No Lubrication - Distribution block cycle times vary slightly from cycle to
cycle; 12 seconds for one cycle, then 15, then 14 is normal. The recommended shutdown time is
double the design cycle time + 30 seconds, limited between 30 seconds and 3 minutes.
Shutdown Time = (2 x design cycle time + 30 seconds)
Find design cycle time on the compressor lube sheets or the compressor tag.
2. DE-BOUNCE and Latching Circuits - The device and control system scan time may necessitate
de-bounce hardware and/or software. Some devices include no built-in de-bounce circuits and can
cause a fast control system to double or triple count. Other times, it may be necessary to latch input
to allow the control system to detect only the first transition from low to high. This becomes sig-
nificant when displaying the cycle time for the operator to set pump flow rates and when calculating
total oil through the divider block.
3. Suggested Operator Displays
Divider Block Cycle Time - Set lube system pumps according to recommended divider block
cycle times. A display of divider block cycle time in seconds is helpful to adjust lube pumps as they
wear out, or to set divider block cycle times at pump replacement.
Time Since Last Pulse - It is helpful to display the timer so the operator sees it actively timing.
Average Cycle Time - Cycle time varies a few seconds from cycle to cycle. It is sometimes helpful
to display a cycle time averaged over 5 to 10 cycles.
Total Oil Consumed - Displays how much oil the lube system uses for accurate oil orders.
4. Sample Flow Diagram to Create Shutdown - FIGURE 2 shows one method to create a shut-
down within the PLC from a cycling digital input.
FIGURE 2 Suggested
Force Feed Lube System
Proximity Switch
Shutdown Logic Diagram
Infrared Port NO NO NO
Remote Mounting NO NO NO
Local Cycle Indicator Separate Indicator YES - LED YES - LCD & LED
Programmable
Shutdown Time PLC 180 seconds
20 to 255 seconds
1. Ariel does not provide vibration limits for skid piping, bottles, or scrubbers.
2. Table does not apply to JGI - vertical non-balanced compressors.
3. These figures apply to balanced opposed reciprocating compressors. They are measured in terms
of velocity, inches per second (mm/s), in zero to peak values, band filtered from 10 to 250 Hz. The
values are guidelines only. In general, if vibration levels fall below those in TABLE 3, stress levels
are well below equipment fatigue stress limit.
4. Analyze levels exceeding TABLE 3 values to determine the cause. A spectral vibration analysis
should be performed by a qualified vibration specialist.
The following devices are acceptable for use on Ariel equipment.
Vibration Switch
Ariel requires installation of an inertial or electronic vibration switch with the sensitive axis in the piston
rod direction. A minimum of 2 switches are recommended for six throw machines. Switches are not
required if transducers are utilized.
Velocity Transducers
For frames over 500 HP, Ariel recommends velocity transducers (or accelerometer transducers integ-
rated to a velocity measure) from a 10-250 Hz bandwidth, measured in peak or RMS converted to peak
levels.
Mount velocity transducers perpendicular to the crankshaft at the crankshaft centerline elevation. A
single transducer on the drive end is adequate on 2-throw and 4-throw machines. Six-throw frames
require one transducer on the drive end and one on the auxiliary end. Many Ariel frames now have
machined bosses for easy and solid connection. TABLE 3 guidelines can be applied to these readings.
The packager may set these levels as initial alarms in the shop, but must reduce them to more con-
servative protection levels after achieving normal operation.
Load changes from pneumatic clearance pockets or HE unloader actuation may cause intermittent high
vibration levels that can cause nuisance shutdowns. If this is problematic, a 1-second delay to ensure
the vibration is not a transient condition is acceptable. Other more complicated methods in control logic
can prevent these nuisance shutdowns as well.
Accelerometer Transducers
Acceleration measurement on the frame or crosshead guides is sometimes a preferred method and
acceptable as a secondary method of protection. Typically, acceleration is measured with a high sample
rate over a wide bandwidth to quantify impact levels for protection. The many factors associated with
this measurement (sensor resonance, sample rate, mounting, structure resonance), prohibit Ariel from
providing predetermined amplitude limits. Set shutdown and alarms for these devices to a practical level
above normal after normal operation is achieved. Given the variability of acceleration responses, shut-
down and alarms (as a percentage of normal operation) may vary with application. These
measurements can also be sensitive to unloader and pocket activation.
Impact Sensors
Use of crosshead guide impact sensors or accelerometers is optional. Impact sensors monitor and
count peak G levels over a set threshold for a certain number of revolutions, and report the count to the
panel, usually in a 4-20mA current loop. They are typically mounted in the vertical direction on the
crosshead guide or in the horizontal direction on the frame and are acceptable as a second level of pro-
tection.
On high speed separable compressors, crosshead guides have a fairly high impact response in the ver-
tical direction due to normal rod reversals. Sometimes a normal machine response can saturate impact
sensor electronics and cause nuisance alarms and shutdowns. Mount impact sensors on a machined
surface. If a mounting location is not already available, these sensors can be mounted on the lifting eye
machined surface. If a different location is preferred, drill, tap, and spot face the mounting hole. It is crit-
ical to drill the hole straight so the sensor sits flat on the machine.
Mounting sensors on the frame in the horizontal direction at centerline elevation is also acceptable as a
second level of protection. Impact responses from looseness and debris transmit to the sensor effect-
ively in this location. For frame mounting, use the machined frame bosses if possible. One impact sensor
per each pair of throws or in between throws offers adequate protection. Drill, tap, and spot face mount-
ing hole. It is critical to drill the hole straight so the sensor sits flat on the machine.
Impact sensors must be selected based on the intended operating speed of the compressor. Impact
sensors require field tuning with a calibration tool. Consult manufacturer instructions for adjustment. Typ-
ical settings: time the reset level to capture approximately 16 revolutions at normal operating speed. Set
the threshold to 1.25 to 3 times the normal baseline level depending on how unit load changes affect
sensor response.