Professional Documents
Culture Documents
Objectives:
EQUIPMENT:
Laptop/Desktop Computer
MATLAB/Simulink Software
Marks Obtained
Pre-Lab 15
Lab. Session 40
Report 16
Total Marks 71
Utilities are responsible for the generation, transmission and distribution of electricity to
customers. Part of this responsibility is ensuring a safe but yet reliable power supply to
customers. For the purpose of safety and protecting the transmission and distribution
network from faults, utilities worldwide have sophisticated protective equipment.
Collectively, these are known as secondary equipment and include the current
transformers (CT), potential transformer (PT) and protective relays.
Protective Relays
A protective relay is a device which monitors the impedance, current, voltage, frequency,
or any other type of electric power measurement either from a generating source or to
a load for the purpose of triggering a circuit breaker to open in the event of an abnormal
condition. These relays are referred to in the electrical power System as protective relays.
The function of protective relaying is to cause the quick isolation from service of the
section of a power system under fault conditions or when operating under any abnormal
condition that might cause damage to equipment or otherwise cause interference with
system stability.
1. Use figure 1 to depict and describe how correct co-ordination of distance relays can
be achieved for three zone distance protection of the two line sections AB and CD.
Figure 1
Procedure
1. Draw the power system having a 3-φ source, three single phase circuit breakers,
3-φ VI measurement unit, 3-φ RLC series load and block of 3-φ fault to
implement different types of faults in system. Connect the blocks as shown below.
2. Set the parameters of each block as follows. Accept default values for all other
parameters.
a) Total Simulation Time: 0.25s.
b) Solver: Ode23tb (stiff/TR-BDF2). Also set following solver options. Relative
tolerance: 1e-3 (default), Solver reset Method: Robust
c) System Frequency: 50Hz.
d) Three phase source: Voltage (Phase to Phase): 0.4kV, Internal connection: Y
grounded, Specify impedance using short-circuit level: Check/select box.
(This option is selected to specify internal impedance using the inductive short-
circuit level and XIR ratio, set X/R ratio to 10), 3 phase short circuit level: 1020e6
VA.
g. Three-Phase Series RLC Load: The load is considered to be a motor, rated 110kW,
400V, 0.9 power factor. Configuration: connection: Y grounded; Inductive reactive
power: Calculate; capacitive reactive Power: 0 VAR.
h. Three Phase Fault: Ground fault; External control of fault timing; Initial status of
fault: [0 0 0].
i. Step Sources: There are two step sources used in this model to control circuit the
breaker and fault blocks. The step time and initial values are set in such a way that
the breaker remains closed up to 0.1s and a fault does not occur during simulation
time. Because simulation time is 0.25s and step-time of "Fault Control (Step
source)" is 1s, it means the output of this step source will remain "0" during
simulation time.
Step:
Step time: 0.1
Initial value: 1
Final value: 0
Fault Control:
Step time: 1
Initial value: 0
Final value: 1
3. Run the simulation and observe the current and voltage waveforms on the
Scope. Find the peak value of current and voltage in each phase when the circuit
breaker close and record them in the table below.
la lb le
Va Vb Ve
4. Connect the RMS block in each phase of output current and find rms value of
current in each phase. Different RMS bocks are available in Matlab Simulink
libraries. Select appropriate RMS block that has constant output.
la lb le
6. The RMS value observed in Step 4 is the rated load current of the system. The
System can be overloaded up to 40%. So, the over current relay must not
consider this over load condition as a faulty condition. But as soon as the
current exceed this over load current value, the over current relay must trip
the circuit breakers. To model this condition in Simulink, you compare the RMS
value of currents with a constant. The value of the constant will be 1.4 times
the RMS value of rated load current.
To avoid operation for normal events such as motor starting surges, an S-R Flip-
Flop is used between breaker and relational operator. These flip-flops will retain
the state of the output. Initial condition (state of Q) is set to 'O', so '!Q’ will
be ‘1’.
Mismatch data-type:
The default data-type of output of relational operators, flip-flops and logic
operators is "boolean". To connect the blocks with each other the output data-
type of first block must be consistent with the input data-type of second block.
Input data-type of the breaker is 'double' and in this system, the breaker is
connected at the output of logic AND gate. So to avoid this data-type mismatch
the output data-type of logic AND gate must be 'double'. This can be done either
by connecting "data-type conversion" block at the output of Logic AND gate or
by setting the output data-type of logic AND gate ('double').
NB: You can use the Matlab help function if you don’t know how to do something.
7. Now connect the relay to the system as shown in figure 5. Set the "Step-Time" to
0.1s of fault control (step source). By setting this timing, the fault will occur at 0.1s.
Simulate the following unsymmetrical faults and obtain the graphs at the output of the Over
Current Relay:
1) Single Line to Ground fault
2) Double Line to Ground fault
3) 3-φ Grounded fault
LABORATORY REPORTING
Write a lab report which should include at least the following: (16)
• Objective(s) of the experiment
• Introduction/ Brief Theoretical Background
• Experimental Set-up
• Procedure
• Findings/Results
• Analysis of Results
• Conclusion
NB: Make the cover page of this lab manual your report‘s cover page
(Mandatory).
END