Professional Documents
Culture Documents
For current transformers subjected to high fault currents NP Number of turns primary
or DC components the magnetic cores may saturate. NS Number of turns secondary
For protection cores this is an undesirable effect since Xm Main reactance of the core
particularly under heavy fault conditions a correct re- Rm Magnetic losses of the core
plica of the primary current is required for the protection RB Resistance of the complex burden
relay to function properly. Hence the understanding of XB Reactance of the complex burden
current transformers and the knowledge of all relevant ϕB Burden's phase angle = arctan (XB/RB)
current transformer data is of particular importance to EMF Electromotive Force = inner core voltage
optimize the performance of protection relays as well as US Secondary voltage
the entire power system.
IP Primary current
IS Secondary current
The IEC standard 60044-6 for current transformers
RCT Secondary winding resistance
covers the application for protection relays very
Ie Excitation current
thoroughly. This has been triggered by the extended Figure 2 shows the vector diagram for currents and voltages
possibilities of modern protection relays, which for a linear Xm.
significantly increase the demands on the transient
behavior of current transformers especially under high
currents. Apart from the traditional classes P and M,
Part 6 of IEC 60044 contains the requirements for the
transient performance of current transformers. Class
TPS, TPX, TPY and TPZ current transformers are
specifically suited for modern protection relays, e.g. for
differential protection.
Z = ( R P + jωL P ) ϕ = Tan −1 L P / R P τ = L P / R P
I P = ( 2 * V P / Z * sin(ωt + α − Φ )) ⇒ I AC
−t / τ
+ ( − 2 * V P / Z * sin(α − Φ ) * e ) ⇒ I DC
I DC = max when α − ϕ = −π / 2
First example:
CT saturation
Second example: Due to the differing saturation of the CT's in phase L1,
the relay trips after 80ms. Especially the second
Generator with differential protection and a far away example shows, that in spite of not very high fault
fault. current amplitudes DC offset can cause saturation of
magnetic cores which in turn can result in incorrect
relay tripping.
factor) and the secondary accuracy limit voltage but did Class TPX
not specify the knee point EMF (electromotive force)
and the magnetic residual behavior. The basic characteristics for class TPX current
transformers are similar to those of class TPS current
Within the new IEC 60044-6 standard, current transformers, except for the different error limits
transformers for protection applications are considered prescribed.
very thoroughly. This is also a result of the extended
possibilities of modern protection technology which Like the TPS class this CT has no gapped core. A large
significantly increased the demands on the transient cross section of the magnetic core with a high accuracy
performance of current transformers especially at high limiting factor (ALF) protects the core against
currents. The standard defines TPS/TPX classes for saturation.
closed ring cores and TPY/TPZ classes for gapped
cores (figure 19). The TPX class is defined by the accuracy limit which is
determined by the instantaneous peak value of the error
during a specific transient current sequence. There is
no limit value for the remanent flux. The phase error is
negligible.
U al ≥ KK ssc ( Rct + Rb ) I sn
with:
The TPY class is defined by the accuracy limit which is Ktd at tal1 of CO duty (one cycle):
determined by the instantaneous peak value of the error
during a specific transient current sequence. The limit ⎧⎡ ωT T ⎤ ⎡ − t 'al −t 'al
⎤ ⎫⎪
⎪ Tp
⎥ ⎢e ⎥⎬ + 1
p s
value for the remanent flux is less than 10% of the K td = ⎨⎢ − e Ts
saturation flux. For a C-O-C-O duty cycle, the transient (T
⎪⎩⎣⎢ p − T )
s ⎦⎥ ⎢⎣ ⎥⎦ ⎪
⎭
dimensioning factor will be affected by the ratio of the
secondary time constant Ts=Ls/Rs and the dead time tfr Ktd at tal2 for COCO duty (double cycle):
(figure 21).
⎧ ⎡ ωT T ⎤ ⎡ − t ' − t ' al
⎤ ⎫ − ( t fr + t ''al )
⎪ p s Tp ⎪
K td = ⎨⎢ ⎥ ⎢e − e ⎥ − sin ωt '⎬e
Ts Ts
⎪⎩⎢⎣ (T p − Ts ) ⎥⎦ ⎢⎣ ⎥⎦ ⎪⎭
⎡ ωT p Ts ⎤ ⎡ T pal ⎤
− t '' − t '' al
+⎢ ⎥ e⎢ − e Ts ⎥ + 1
⎢⎣ (T p − Ts ) ⎥⎦ ⎢⎣ ⎥⎦
U al ≥ K td K ssc(Rct + Rb )I sn
Figure 21 TPY with Kr=0.1, Ts = 0.54s; Tfr =0.4s
The IEC formula for the C-O-C-O duty doesn't take into
account that the core may be saturated with the
Class TPZ remanent flux. Figure 23 shows a TPX class CT with
the influence of the remanence and without remanence
The TPZ CT has several air gaps in the core and has like it is calculated according to IEC. This shows that
therefore has a linear magnetizing curve also for very the remanence plays an important role and may not be
high fault currents with high DC offsets. The remanence neglected.
factor Kr is negligible.
IEC 60044-6 includes formulas for the calculation of Ktd. U al ≥ K td K ssc (Rct + Rb )I sn
Ktd at tmax: according IEC 60044-6 A5:
with K td = 12 and K ssc = 20
TP U al ≥ 240 (Rct + Rb )I sn
⎛ Tp ⎞ Ts −T p )
K td = K tf = ωTP ⎜⎜ ⎟⎟ +1
⎝ Ts ⎠
One can see that very high accuracy limiting voltages By reducing the measuring frequency knee point
are necessary to avoid saturation in a non-gapped core. voltages up to 15kV can be measured, although the
This is the reason why a gapped core with a negligible maximum test voltage is limited to 120V. The test
remanence enables smaller and lighter cores. instrument has a weight of less than 8 kg. Figure 25
shows the test arrangement for the ratio test and the
measurement of hysteresis curves at the test laboratory
7. Measurements for Assessing the Transient of KEMA in Arnhem, Netherlands. The small test
Performance of Current Transformers instrument replaces all the equipment shown in figure
25. Similar tests were made with the Physikalisch
The following parameters are important for the assess- Technische Bundesanstalt, Braunschweig, Germany
ment of the proper functioning of protection CT's and to (PTB).
generate the CT model according to figure 8.
The whole test procedure is running fully automatic With the input data (figure 29) the assessment of the
without any change of the wiring. Figure 27 shows the TPS, TPX, TPY and TPZ class CT's is made auto-
wiring for a post type high voltage CT, figure 28 for a matically without complicated calculations.
bushing type CT inside a power transformer. With the
new test method even bushing and SF6 switchgear Figure 30 shows the screen shot of an excitation curve.
CT's can be measured with high precision.
[3] IEC60044-6
"Instrument transformers, Part 6: Requirements for
protective current transformers for transient per-
formance", International Electrotecnical Com-
mission, Geneve, Switzerland, 1992
Such calculated currents and voltages can physically be [7] NetSim, Introductory Examples, OMICRON
injected into a relay using a secondary injection test set electronis, Klaus 2001
such as the CMC 256. Realistic testing of the entire
protection circuit hence can be performed even for
extreme conditions.
9. Conclusion
10. Literature