TEST REPORT

Airflow Velocity Test


Name & Address of customer Page No 1 of 1
M/s.Chandrakanth Nethralaya Report No SRM/23-24/0213/AV-01
Calicut Kerala Date Of Test 20.05.2023
Next Due Date 20.11.2023
Details of Test
Description Airflow velocity and ACPH Test
Purpose To determine the average airflow velocity & air changes per hour
Details of Equipment / Area
Area of Test Operation Theatres Occupancy Status At rest
AHU No 2 Classification ISO 7
Details of Standard Instrument Used
Instrument Used DIGITAL VANE ANEMOMETER S.L.No T.026769
Make LUTRON Model AM-4204
Calibration On 13.09.2022 Calibration Due 13.09.2023
* OBTAINED TEST RESULTS *
Air
Total
Filter Volume Changes/hr
Average airflow Room Acceptan
Grill / Filter /Grill Air Velocity Reading in fpm
velocity
flow
volum volume
(VtX60)/Rv
ce limit Result
Room Name Area rate
Id e
Sq.ft L1 L2 L3 L4 L5 fpm cfm cfm cuft Number Number
SG - 01 7.8 110 100 120 118 114 112 877
SG - 02 7.8 100 98 110 112 116 107 836
SG - 03 7.8 112 96 100 98 100 101 789
Cataract OT - I 4084 2406 102 ≥ 45 Pass
SG - 04 7.8 98 100 98 100 110 101 789
SG - 05 4.0 100 94 98 100 96 98 390
SG - 06 4.0 100 94 98 110 100 100 402

Note: The airflow velocity measured at approximately 150mm to 300mm from the grill face
L-1 L-2

L5

L-3 L-4
Results :
The above specified Clean Room confirms the air flow velocity test as per ISO standard.
Test conducted By: Checked & Approved By Test witnessed by :

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Airflow Velocity Test
Name & Address of customer Page No 1 of 1
M/s.Chandrakanth Nethralaya Report No SRM/23-24/0214/AV-02
Calicut Kerala Date Of Test 20.05.2023
Next Due Date 20.11.2023
Details of Test
Description Airflow velocity and ACPH Test
Purpose To determine the average airflow velocity & air changes per hour
Details of Equipment / Area
Area of Test Operation Theatres Occupancy Status At rest
AHU No 4 Classification ISO 7
Details of Standard Instrument Used
Instrument Used DIGITAL VANE ANEMOMETER S.L.No T.026769
Make LUTRON Model AM-4204
Calibration On 13.09.2022 Calibration Due 13.09.2023
* OBTAINED TEST RESULTS *
Air
Total
Filter Volume Changes/hr
Average airflow Room Acceptan
Grill / Filter /Grill Air Velocity Reading in fpm
velocity
flow
volum volume
(VtX60)/Rv
ce limit Result
Room Name Area rate
Id e
Sq.ft L1 L2 L3 L4 L5 fpm cfm cfm cuft Number Number
SG - 01 7.8 100 98 120 96 114 106 824
SG - 02 7.8 98 98 94 112 100 100 783
SG - 03 7.8 100 96 98 98 120 102 799
Cataract OT - II 4110 1997 123 ≥ 45 Pass
SG - 04 7.8 112 110 98 110 110 108 842
SG - 05 4.0 98 100 114 100 112 105 419
SG - 06 4.0 112 120 110 100 112 111 443

Note: The airflow velocity measured at approximately 150mm to 300mm from the grill face
L-1 L-2

L5

L-3 L-4
Results :
The above specified Clean Room confirms the air flow velocity test as per ISO standard.
Test conducted By: Checked & Approved By Test witnessed by :

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Airflow Velocity Test
Name & Address of customer Page No 1 of 1
M/s.Chandrakanth Nethralaya Report No SRM/23-24/0215/AV-03
Calicut Kerala Date Of Test 20.05.2023
Next Due Date 20.11.2023
Details of Test
Description Airflow velocity and ACPH Test
Purpose To determine the average airflow velocity & air changes per hour
Details of Equipment / Area
Area of Test Operation Theatres Occupancy Status At rest
AHU No 1 Classification ISO 7
Details of Standard Instrument Used
Instrument Used DIGITAL VANE ANEMOMETER S.L.No T.026769
Make LUTRON Model AM-4204
Calibration On 13.09.2022 Calibration Due 13.09.2023
* OBTAINED TEST RESULTS *
Air
Total
Filter Volume Changes/hr
Average airflow Room Acceptan
Grill / Filter /Grill Air Velocity Reading in fpm
velocity
flow
volum volume
(VtX60)/Rv
ce limit Result
Room Name Area rate
Id e
Sq.ft L1 L2 L3 L4 L5 fpm cfm cfm cuft Number Number
SG - 01 7.8 98 112 120 98 114 108 846
SG - 02 7.8 112 100 98 112 100 104 814
SG - 03 7.8 116 114 100 114 120 113 880
Lasik OT 4342 2108 124 ≥ 45 Pass
SG - 04 7.8 116 118 118 110 112 115 895
SG - 05 4.0 114 118 114 112 114 114 458
SG - 06 4.0 118 120 112 100 112 112 450

Note: The airflow velocity measured at approximately 150mm to 300mm from the grill face
L-1 L-2

L5

L-3 L-4
Results :
The above specified Clean Room confirms the air flow velocity test as per ISO standard.
Test conducted By: Checked & Approved By Test witnessed by :

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Airflow Velocity Test
Name & Address of customer Page No 1 of 1
M/s.Chandrakanth Nethralaya Report No SRM/23-24/0216/AV-04
Calicut Kerala Date Of Test 20.05.2023
Next Due Date 20.11.2023
Details of Test
Description Airflow velocity and ACPH Test
Purpose To determine the average airflow velocity & air changes per hour
Details of Equipment / Area
Area of Test Operation Theatres Occupancy Status At rest
AHU No 3 Classification ISO 7
Details of Standard Instrument Used
Instrument Used DIGITAL VANE ANEMOMETER S.L.No T.026769
Make LUTRON Model AM-4204
Calibration On 13.09.2022 Calibration Due 13.09.2023
* OBTAINED TEST RESULTS *
Air
Total
Filter Volume Changes/hr
Average airflow Room Acceptan
Grill / Filter /Grill Air Velocity Reading in fpm
velocity
flow
volum volume
(VtX60)/Rv
ce limit Result
Room Name Area rate
Id e
Sq.ft L1 L2 L3 L4 L5 fpm cfm cfm cuft Number Number
SG - 01 7.8 112 116 118 100 114 112 874
SG - 02 7.8 116 112 98 112 116 111 864

Retina & Cornea SG - 03 7.8 112 100 116 114 118 112 874
4408 1632 162 ≥ 45 Pass
OT SG - 04 7.8 118 110 112 110 118 114 886
SG - 05 4.0 112 116 114 118 120 116 464
SG - 06 4.0 112 118 116 112 100 112 446

Note: The airflow velocity measured at approximately 150mm to 300mm from the grill face
L-1 L-2

L5

L-3 L-4
Results :
The above specified Clean Room confirms the air flow velocity test as per ISO standard.
Test conducted By: Checked & Approved By Test witnessed by :

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Airflow Velocity Test
Name & Address of customer Page No 1 of 1
M/s.Chandrakanth Nethralaya Report No SRM/23-24/0216/AV-05
Calicut Kerala Date Of Test 20.05.2023
Next Due Date 20.11.2023
Details of Test
Description Airflow velocity and ACPH Test
Purpose To determine the average airflow velocity & air changes per hour
Details of Equipment / Area
Area of Test Operation Theatres Occupancy Status At rest
AHU No 5 Classification ISO 7
Details of Standard Instrument Used
Instrument Used DIGITAL VANE ANEMOMETER S.L.No T.026769
Make LUTRON Model AM-4204
Calibration On 13.09.2022 Calibration Due 13.09.2023
* OBTAINED TEST RESULTS *
Air
Total
Filter Volume Changes/hr
Average airflow Room Acceptan
Grill / Filter /Grill Air Velocity Reading in fpm
velocity
flow
volum volume
(VtX60)/Rv
ce limit Result
Room Name Area rate
Id e
Sq.ft L1 L2 L3 L4 L5 fpm cfm cfm cuft Number Number
SG - 01 7.8 110 116 120 100 112 112 870
SG - 02 7.8 114 100 116 112 118 112 874
SG - 03 7.8 120 112 116 114 118 116 905
Septic OT 4485 1030 261 ≥ 45 Pass
SG - 04 7.8 112 118 116 112 120 116 902
SG - 05 4.0 120 116 118 118 120 118 474
SG - 06 4.0 110 118 116 112 120 115 461

Note: The airflow velocity measured at approximately 150mm to 300mm from the grill face
L-1 L-2

L5

L-3 L-4
Results :
The above specified Clean Room confirms the air flow velocity test as per ISO standard.
Test conducted By: Checked & Approved By Test witnessed by :

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya