TEST REPORT

Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1121
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 15 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

1.5 M Wide Corridor SG-01 312 312 1142 16


Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1122
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 15 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

POST OP SG-02 382 382 504 45


Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1123
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 15 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

PRE OP SG-03 266 266 504 32


Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1124
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 20 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

Fmale Change Room SG-04 432 432 358 72


Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1125
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 20 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

Male Change Room SG-08 341 341 378 54


Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1126
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 20 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

1.2M Wide Corridor SG-09 155 155 400 23


Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1127
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 20 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

Scrub Room &


SG-11 107 107 261 25
Sterilization
Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1128
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 20 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

Instrument Washing Area SG-12 82 82 75 66

Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1129
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 20 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

2M Wide Corridor SG-10 389 389 1394 17


Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1130
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 20 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

Autoclave Packing Area SG-05 235 235 641 22


Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Checked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Air Flow Velocity, Volume Testing and Determination of Air Changes per Hour Rates Ø
Customer M/s Chandrakanth Nethralaya Certificate No ACPH/2023-24/1131
Calicut Kerala Date of Test 21.05.2023
Next Due Date 21.11.2023
Test Description:
Determine the average airflow velocity,Air volume supply rate and air changes per hour of the clean room.
Details of Instruments Used for testing
Instrument Used AIR CAPTURE HOOD Instrument Sr. No. T83802211033
Make TSI Calibrated on 23.08.2022
Model 8380 Calibration Due on 23.08.2023
Reference standard ISO -14644/1 Test procedure No SRM/HVAC/001
Details of Specification and Area
Test Specification Specified Air Change/hr NLT 15 Occupancy State "At Rest"
Block / Area 3rd Floor Test Reference ISO 14644/1
AHU Number AHU-06
Ø Obtained Test Results Ø
Measured Supply Air Total Flow Rate In
Room Name Grill/Filter ID No. ROOM VALUME ACPH
CFM CFM

SG-06 239
2.1M Wide Corridor 339 1304 16
SG-07 100
Conclusion :

1. The airflow velocity of above specified clean room measured and the average airflow velocity, air volume supply rate and air
changes are calculated.
2. Air changes per hour of the above mensioned clean room complying with the acceptence limit specified.
Test Conducted By Cheked And approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya

You might also like