BẢN VẼ THI CÔNG ĐẤU NỐI NHỊ THỨ

LẮP ĐẶT RƠ LE F87L (SIEMENS-7SL86) THAY THẾ RƠ LE


F21 (TOSHIBA-GRZ200)
1 2 3 4 5 6 7 8

A A

B B

A 9/06/2021 ISSUE FOR APPROVE

REV. DATE DESCRIPTION

EMPLOYER

C C

WIND POWER HOA DONG COMPANY LIMITED

PROJECT:

110kV HOA DONG WIND POWER PLANT


110kV MY XUYEN SUBSTATION
CONTRACTOR:
D D

THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD

DRAWING NAME: WIRING DIAGRAMS FOR 110KV TRANSMISSION LINE BAY STAMP:

REVISION DRAWING FOR/BẢN VẼ CẢI TẠO TỦ BẢO VỆ ĐƯỜNG DÂY:


- +CRP-E03: CONTROL & PROTECTION PANEL FOR 110KV TRANSMISSION LINE
E TỦ ĐIỀU KHIỂN BẢO VỆ NGĂN LỘ ĐƯỜNG DÂY 110kV E03 E
*NỘI DUNG CẢI TẠO" THAY THẾ RELAY F21 BẰNG RELAY F87L

GHI CHÚ:
- Trang bản vẽ "X": Trang bản vẽ mạch hiện hữu cho relay F21
- Trang bản vẽ "X.a": Trang bản vẽ mới áp dụng cho relay F87L mới.

DRAWING No.: TD/HDMX-E03+CRP3 SHEET No.: A00 QTY OF SHEETS: 21

DRAWN DUC.CX SUBCONTRACTOR:

CHECK. HOANG.NH R
THT TRADING, SERVICE
F F
AND HIGH TECHNOLOGY
APPR. DUNG.NT JOIN STOCK COMPANY
THE HIGH TECH COMPANY

DATE 08/06/2021 REV.:

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

No. PAGE DESCRIPTION REV. X No. PAGE DESCRIPTION REV. X

1 =E03+CRP3/A00 WIRING DIAGRAMS FOR 110KV TRANSMISSION LINE BAY A


A A
2 =E03+CRP3/A01 TABLE OF CONTENTS : =E03+CRP3/A00 - =E03+CRP3/Z12 A

3 =E03+CRP3/A02 LIST OF COMPONENTS A X


BỐ TRÍ MẶT TỦ CRP-E03 SAU CẢI TẠO
4 =E03+CRP3/A03 A
LAYOUT OF CRP-E03 PANEL AFTER EXTENSION
MA TRẬN TRIP HIỆN HỮU
5 =E03+CRP3/A04 A
TRIPPING MATRIX (OLD)
MA TRẬN TRIP MỚI
6 =E03+CRP3/A05 A
TRIPPING MATRIX (NEW)
MẠCH DÒNG ÁP RƠ LE F21 HIỆN HỮU
7 =E03+CRP3/CR305 A
ANALOG INPUT FOR MAIN RELAY (OLD)
MẠCH DÒNG ÁP RƠ LE F87L MỚI
B 8 =E03+CRP3/CR305.a A B
ANALOG INPUT FOR MAIN RELAY (NEW)
MẠCH CẢNH BÁO RƠ LE F21 HIỆN HỮU
9 =E03+CRP3/CR310 A
ANNUNCIATION FOR PANEL (OLD)
MẠCH CẢNH BÁO RƠ LE F21 HIỆN HỮU
10 =E03+CRP3/CR310.a A
ANNUNCIATION FOR PANEL (OLD)
MẠCH INPUT RƠ LE F21 HIỆN HỮU
11 =E03+CRP3/CR314 A
DIGITAL INTPUT OF MAIN RELAY (OLD)
MẠCH INPUT RƠ LE F87L MỚI
12 =E03+CRP3/CR314.a A
DIGITAL INTPUT OF MAIN RELAY (NEW)
MẠCH OUTPUT RƠ LE F21 HIỆN HỮU
13 =E03+CRP3/CR315 A
DIGITAL OUTPUT OF MAIN RELAY (OLD)
MẠCH OUTPUT RƠ LE F87L MỚI
14 =E03+CRP3/CR315.a A
DIGITAL OUTPUT OF MAIN RELAY (NEW)
C
MẠCH OUTPUT RƠ LE F21 HIỆN HỮU C
15 =E03+CRP3/CR316 A
DIGITAL OUTPUT OF MAIN RELAY (OLD)
MẠCH OUTPUT RƠ LE F87L MỚI
16 =E03+CRP3/CR316.a A
DIGITAL OUTPUT OF MAIN RELAY (NEW)
SƠ ĐỒ KẾT NỐI TRUYỀN THÔNG RELAY F87L
17 =E03+CRP3/D01 A
COMMUNICATION OF 87L
SƠ ĐỒ KẾT NỐI CÁP QUANG PHỐI HỢP BẢO VỆ RELAY F87L
18 =E03+CRP3/D02 A
INTERCOMMUNICATION OF 87L
THAM CHIẾU RELAY F87L
19 =E03+CRP3/Z1 A
REFERENCES LINE DIFFERENTIAL RELAY F87L
THAM CHIẾU RELAY F87L
20 =E03+CRP3/Z2 A
REFERENCES LINE DIFFERENTIAL RELAY F87L
THAM CHIẾU THIẾT BỊ ĐIỀU KHIỂN
21 =E03+CRP3/Z12 A
CONTROLLING DEVICES REFERENCE
D D

E E

X: AUTOMATIC PAGE MODIFIED

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT
F TABLE OF CONTENTS : =E03+CRP3/A00 - =E03+CRP3/Z12 F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. A01
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET A02

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

No. NAME TAG DESCRIPTION MANUFACTORY TYPE Q'TY UNIT NOTE PANEL

27DI 17DO 2xFO IEC 61850 1xSingle Mode Laser 60kM +


1 -F87L LINE DIFFERENTIAL PROTECTION RELAY SIEMENS 7SL86_P1C460309 1 EA =E03+CRP3
1xG703
A A
2 S.87L CAM SWITCH K&N/NEWZEALAND CA10 A221-600 E S0 1 Ea W/NP: 87L: ON - OFF, CONTACT 2A2B =E03+CRP3

B B

C C

D D

E E

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT
F LIST OF COMPONENTS F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. A02
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET A03

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BỐ TRÍ MẶT TỦ CRP-E03 HIỆN HỮU BỐ TRÍ MẶT TỦ CRP-E03 SAU CẢI TẠO
A A
EXISTING FRONT VIEW NEW FRONT VIEW
(WITHOUT DOOR) (WITHOUT DOOR)

CRP.E03 CRP.E03

ANNUCIATOR ANNUCIATOR
MULTI M. VOLT M. MULTI M. VOLT M.

B B
LT HORN LT HORN

110kV 110kV

SW1 Q1 SW1 Q1
Q51 Q51

SW2 Q0
SW2 Q0
Q52 Q52

SW3 SW3
Q9 Q9
Q8
NEW S.87L SWITCH Q8

KHÓA LỰA CHỌN F87L S.87L

C 2 C

EXISTING F21RELAY RƠ LE F87L MỚI 1


RUN ERROR
SIPROTEC SIPROTEC

GRZ200/TOSHIBA 7SL86 / SIEMENS F87L

SẼ ĐƯỢC THÁO DỠ 7 8 9
Ctrl

DI DỜI
4 5 6

I
1 2 3

O
F21 F67 F67
Fn 0 .

F86 F741F742 F86 F741F742


RE RE

D D

PTL PTL

CTT PTT CTT PTT


TB21 TB67 TB21 TB67

E E

NEW DEVICE INSTALLINGS:

No. TAGNAME ITEM NAME MODEL MANUFACTURE REMARKS

01 F87L LINE DIFFERENTIAL RELAY 7SL86, 220VDC, ModbusTCP/DNP3.0/IEC104/IEC61850 SIEMENS

02 S.87L F87L BLOCK SWITCH CA10-A221, 2 POSITION, 2 POLE KRAUSE & NAIMER

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT BỐ TRÍ MẶT TỦ CRP-E03 SAU CẢI TẠO
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE LAYOUT OF CRP-E03 PANEL AFTER EXTENSION PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. A03
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET A04

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

E07-Q0
INTIATE TELE PRO.
PANEL PROTECTION DEVICE INTIATE TRIP F86 OF TRIP F86 OF TRIP F86 OF TRIP F86 OF
F86 50BF INPUT F21 TO
79 OF F21 E01 E02 E04 E05
TRIP COIL 1 TRIP COIL 2 BLOCK CLOSE OF 67 REMOTE END

21Z1, 67N

F21 ANY TRIP (21Z1, 67N)


B B
67/67N
=E03+CRP3
F67 ANY TRIP

50BF

F86 TRIP

F74 741, 742

C C
21Z1
F21
TELE PROTECTION
FROM 67N
REMOTE END

F67 50BF (DTT)

D D

E E

Bản vẽ tham chiếu


=COM+SD/SD08
EVN SPC ETC

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MA TRẬN TRIP HIỆN HỮU
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE TRIPPING MATRIX (OLD) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. A04
JOIN STOCK COMPANY
THE HIGH TECH COMPANY THT_HP1_LS+CRP1
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET A05

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

E07-Q0
INTIATE TELE PRO.
PANEL PROTECTION DEVICE INTIATE TRIP F86 OF TRIP F86 OF TRIP F86 OF TRIP F86 OF
F86 50BF INPUT F87L TO
79 OF F21 E01 E02 E04 E05
TRIP COIL 1 TRIP COIL 2 BLOCK CLOSE OF 67 REMOTE END

*
87L, 21Z1, 67N
F87L
B ANY TRIP B

67/67N
=E03+CRP3
F67 ANY TRIP

50BF

F86 TRIP

F74 741, 742


C C

21Z1, 67N *

F87L
TELE PROTECTION
50BF (DTT) *
FROM
REMOTE END

D D

*
TELE PROTECTION BY F87L's FIBER INTERFACE / PHỐI HỢP QUA ĐƯỜNG TRUYỀN SO LỆCH QUANG

E E

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MA TRẬN TRIP MỚI
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE TRIPPING MATRIX (NEW) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. A05
JOIN STOCK COMPANY
THE HIGH TECH COMPANY THT_HP1_LS+CRP1
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR305

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A =E04 A
+MK4

UA22 V3104 1 9 UA22


=E04+MK4/M403.6:E/ /CR306.2:A
-XVB
UB22 2 11 UB22
=E04+MK4/M403.6:E/ /CR306.2:A
UC22 3 13 UC22
=E04+MK4/M403.7:E/ /CR306.2:A
UN22 4 15 UN22
=E04+MK4/M403.7:E/ /CR306.2:B

B B
=E01+CRP1 -F21
-TB21
/CR323.1:A
/CR323.2:B
UA22 V1104 10 -VA
1 1 2 VC1-1 VC1-2
=E01+CRP1/CR105.1:A/
-XVB
UB22 2 12 3 4 VC1-3 -VB VC1-4
=E01+CRP1/CR105.1:A/

UC22 3 14 5 6 VC1-5 -VC VC1-6


=E01+CRP1/CR105.1:A/

UN22 4 16 7 8
=E01+CRP1/CR105.1:B/

+
F213+ 13 14 T4-29
C CR303.2:E/ C
-
F213- 15 16 T4-31
CR303.3:E/ U

+MK3 UL32 VC7M7 3 3 9 10 VC1-7 VS VC1-8


+MK3/M303.5:E/
-XVL

ULN32 4 4 11 12
+MK3/M303.6:E/

D D

IA23 IC7M72 1 1 21 22 VC1-11 -IA VC1-12


+MK3/M304.3:F/
-XCT21
IB23 2 2 23 24 VC1-13 -IB VC1-14
+MK3/M304.4:F/
IC23 3 3 25 26 VC1-15 -IC VC1-16
+MK3/M304.4:F/
IN23 4 4 27 28 VC1-18 -IE VC1-17
+MK3/M304.4:F/

E E

Bản vẽ tham chiếu


MX-18102017
E03+CRP3 / CR305

........ :PHẦN MẠCH THAY ĐỔI


PHƯƠNG THỨC THAY THẾ:
1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH DÒNG ÁP RƠ LE F21 HIỆN HỮU
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE ANALOG INPUT FOR MAIN RELAY (OLD) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR305
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR305.a

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A =E04 A
+MK4

UA22 V3104 1 9 UA22


=E04+MK4/M403.6:E/ /CR306.2:A
-XVB
UB22 2 11 UB22
=E04+MK4/M403.6:E/ /CR306.2:A
UC22 3 13 UC22
=E04+MK4/M403.7:E/ /CR306.2:A
UN22 4 15 UN22
=E04+MK4/M403.7:E/ /CR306.2:B

B B
=E01+CRP1
-TB21 F87L
/CR323.2:B IO1
10
V1
UA22 V1104 1 1 2 B1 B2
=E01+CRP1/CR105.1:A/
-XVB V2
UB22 2 12 3 4 B3 B4
=E01+CRP1/CR105.1:A/
V3
UC22 3 14 5 6 B5 B6
=E01+CRP1/CR105.1:A/

UN22 4 16 7 8
=E01+CRP1/CR105.1:B/
F87L PS
IO2
+
F213+ 13 14 B1
C CR303.2:E/ C
-
F213- 15 16 B2
CR303.3:E/ U

F87L
IO4 PS
+
A1

-
A2 U
V4
+MK3 UL32 VC7M7 3 3 9 10 B7 B8
D +MK3/M303.5:E/ D
-XVL

ULN32 4 4 11 12
+MK3/M303.6:E/

1
I1
IA23 IC7M72 1 21 22 A1 A2
+MK3/M304.3:F/
-XCT21 I2
IB23 2 2 23 24 A3 A4
+MK3/M304.4:F/
I3
IC23 3 3 25 26
E A5 A6 E
+MK3/M304.4:F/
4
I4
IN23 4 27 28 A7 A8
+MK3/M304.4:F/

........ :PHẦN MẠCH THAY ĐỔI


PHƯƠNG THỨC THAY THẾ:
1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH DÒNG ÁP RƠ LE F87L MỚI
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE ANALOG INPUT FOR MAIN RELAY (NEW) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR305.a
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR310

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A ANNUNCIATION FROM RELAY PANEL A

SC3 /CR311.1:A

-XA 1

/CR317.6:C

/CR317.7:C

/CR317.7:C
/CR315.4:B

/CR315.4:B

/CR315.5:B

/CR315.5:B

/CR315.6:B

/CR315.6:B

/CR315.6:B

/CR315.7:B

/CR320.2:F

/CR320.2:F

/CR320.3:F
B B

/CR302.7:E

/CR302.7:E

AL1

AL2

AL3

AL4

AL5

AL6

AL7

AL8

AL9

AL10

AL11

AL12

AL13

AL14
4
-DB
-SCT3+

-SCT3-
/CR310.a.1 3

-XA 5

C C

INPUT COM EXTERNAL

INPUT COM EXTERNAL

INPUT COM EXTERNAL


F21 67/50/51 TRIP

F21 79/25 CLOSE


F21 ZONE 1 TRIP

F21 ZONE 2 TRIP

F21 ZONE 3 TRIP

F21 ZONE 4 TRIP

F21 TRELE FROT

RELAY FAILURE
F67 50BF TRIP

F741-1 ALARM

F741-2 ALARM
F861 TRIP
F21 SOTF

F67 TRIP

SPARE
SC1

-SCT

A-B A-2:V+ A-3:V- C-1 C-2 C-3 C-4 C-5 D-1 D-2 D-3 D-4 D-5 E-1 E-2 E-3 E-4 E-5 F-1 F-2 F-3

D D

B-13 B12 A-1:GND C-7 C-8 C-9 C-10 C-6 D-7 D-8 D-9 D-10 D-6 E-7 E-8 E-9 E-10 E-6 F-7 F-8 F-9

OUTPUT COMMON
F861 TRIP
RELAY FAILURE

SPARE
F741-1 ALARM

F741-2 ALARM
+
-HORN
E /CR310.a.1 E
-
110 VDC
SC24- /CR311.1:F
Bản vẽ tham chiếu
MX-18102017
E03+CRP3 / CR310
1
17 11 18 19 20
........ :PHẦN MẠCH THAY ĐỔI
PHƯƠNG THỨC THAY THẾ:
1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH CẢNH BÁO RƠ LE F21 HIỆN HỮU
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE ANNUNCIATION FOR PANEL (OLD) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR310
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR310.a

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A ANNUNCIATION FROM RELAY PANEL A

SC3 /CR311.1:A

-XA 1

/CR317.6:C

/CR317.7:C

/CR317.7:C
/CR315.4:B

/CR315.4:B

/CR315.5:B

/CR315.5:B

/CR315.6:B

/CR315.6:B

/CR315.6:B

/CR315.7:B

/CR320.2:F

/CR320.2:F

/CR320.3:F
B B

/CR302.7:E

/CR302.7:E

AL1

AL2

AL3

AL4

AL5

AL6

AL7

AL8

AL9

AL10

AL11

AL12

AL13

AL14
4
-DB
-SCT3+

-SCT3-
/CR321.1:E 3

-XA 5

C C

INPUT COM EXTERNAL

INPUT COM EXTERNAL

INPUT COM EXTERNAL


F87L 21 ZONE 1 TRIP

F87L 21 ZONE 2 TRIP

F87L 21 ZONE 3 TRIP

F87L 67/50/51 TRIP

F87L TRELE FROT


F87 79/25 CLOSE

RELAY FAILURE
F67 50BF TRIP

F741-1 ALARM

F741-2 ALARM
F87L SOTF

F861 TRIP
F87L TRIP

F67 TRIP

SPARE
SC1

-SCT

A-B A-2:V+ A-3:V- C-1 C-2 C-3 C-4 C-5 D-1 D-2 D-3 D-4 D-5 E-1 E-2 E-3 E-4 E-5 F-1 F-2 F-3

D D

B-13 B12 A-1:GND C-7 C-8 C-9 C-10 C-6 D-7 D-8 D-9 D-10 D-6 E-7 E-8 E-9 E-10 E-6 F-7 F-8 F-9

OUTPUT COMMON
F861 TRIP
RELAY FAILURE

SPARE
F741-1 ALARM

F741-2 ALARM
+
-HORN
E 110 VDC E
-
SC2 /CR311.1:F

1
-XSCA 16 17 11 18 19 20
........ :PHẦN MẠCH THAY ĐỔI
PHƯƠNG THỨC THAY THẾ:
1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH CẢNH BÁO RƠ LE F21 HIỆN HỮU
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE ANNUNCIATION FOR PANEL (OLD) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR310.a
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR314

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INPUT FROM INPUT FROM


MARSHALLING KIOSK PANEL CONTROL PANEL
A A
CR303-3:E /
R13+ R13+
/ CR317-1:B

-X1 1 2
=COM+TELE
3
+MK3

C3201 1

R13+
-XX X

/ +MK3/M309-6:F

/ +MK3/M309-6:F

/ +MK3/M309-7:F

/ +MK3/M309-7:F

/ +MK3/M309-8:F
/ +MK3/M309-5:F
B B
32 34
-KC
/CR307-6:D 31
BI1

BI2

BI3

BI4

BI5
-XX
X
C3201 2 3 4 5 6

-X1 4 5 6 7 8 9 10
C C

4 6 5
1 2

-SW3 -SW2
/CR321-5:C 2 /CR321-6:B 8 7
ON/OFF AUTO/OFF/MAN
673 CR317-1:B
CIRCUIT BREAKER OFF
CIRCUIT BREAKER ON

AUTO RECLOSE ON
SPRING CHARGED

TELE RECEIVED
MANUAL CLOSE
D D
VT LINE 2 OFF

VT BUS 2 OFF

F67/67N TRIP
AUTO CLOSE

SPARE
-F21
/CR323-1:A
13 T2-3 T2-5 T2-7 T2-9 T2-11 T2-13 T2-15 T2-17 T2-21 T2-23

BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11
E 14 T2-4 T2-6 T2-8 T2-10 T2-12 T2-14 T2-16 T2-18 T2-22 T2-24 E

R13-
CR303-3:E /

Bản vẽ tham chiếu ........ :PHẦN MẠCH THAY ĐỔI


PHƯƠNG THỨC THAY THẾ:
MX-18102017 1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
E03+CRP3 / CR314 2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH INPUT RƠ LE F21 HIỆN HỮU
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE DIGITAL INTPUT OF MAIN RELAY (OLD) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR314
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR314.a

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INPUT FROM INPUT FROM


MARSHALLING KIOSK PANEL CONTROL PANEL
A A
CR303-3:E /
R13+ R13+
/ CR317-1:B

-X1 1 3
2 =COM+TELE
+MK3

C3201 1

R13+
-XX X
/ +MK3/M309-6:F

/ +MK3/M309-6:F

/ +MK3/M309-7:F

/ +MK3/M309-7:F

/ +MK3/M309-8:F
/ +MK3/M309-5:F
B B
32 34
-KC
/CR307-6:D 31
BI1

BI2

BI3

BI4

BI5
-XX
X
C3201 2 3 4 5 6
-S.87L
/Z12.1 3

OFF
-X1 4 5 6 7 8 9 10
C C

4 6 5
1 2

-SW3 -SW2
673
/CR321-5:C 2 /CR321-6:B 8 7 / CR317-1:B
ON/OFF AUTO/OFF/MAN

OFF FUNCTION 88L BY SWITCH


CIRCUIT BREAKER OFF
CIRCUIT BREAKER ON

AUTO RECLOSE ON
D D
SPRING CHARGED

TELE RECEIVED
MANUAL CLOSE
VT LINE 2 OFF

VT BUS 2 OFF

F67/67N TRIP
AUTO CLOSE

SPARE
F87L IO3 A1 A2 A7 A8 A9 B10 A10 B1 B2 B3 B4 B9

BI3.1 BI3.2 BI3.3 BI3.4 BI3.5 BI3.12 BI3.6 BI3.7 BI3.8 BI3.9 BI3.10 BI3.11

E E

A3 A4 A5 A6 A11 B8 A12 A13 A14 B5 B6 B7

R13-
CR303-3:E /

........ :PHẦN MẠCH THAY ĐỔI


PHƯƠNG THỨC THAY THẾ:
1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH INPUT RƠ LE F87L MỚI
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE DIGITAL INTPUT OF MAIN RELAY (NEW) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR314.a
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR315

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A FUNCTION 25&79 ANNUNCIATION FROM RELAY A


/ CR307-8:A FROM MAIN RELAY

/ CR307-1:C

/ CR311-8:A
/ CR307-1:B

/ CR310-3:B

/ CR310-3:B

/ CR310-3:B

/ CR310-4:B

/ CR310-4:B

/ CR310-4:B

/ CR310-5:B

/ CR310-5:B
C13+

253

793

SC3

AL1

AL2

AL3

AL4

AL5

AL6

AL7

AL8
B B

SC3
/ CR317-1:A
C C

C13+
/ CR316-1:A
WD3
/ CR317-8:D

F21 SWITCH-ON TO FAULT

F21 TELE FROTECTION


F21 67/50/51 TRIP

F21 79/25 CLOSE


F21 ZONE 1 TRIP

F21 ZONE 2 TRIP

F21 ZONE 3 TRIP

F21 ZONE 4 TRIP

RELAY FAILURE
D D
253

783

-F21
T3-9 T3-11 T3-15 T3-17 T3-19 T3-21 T3-23 T3-25 T3-27 T3-29 T4-1
/CR323-1:A

BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14

T3-10 T3-12 T3-16 T3-18 T3-20 T3-22 T3-24 T3-26 T3-28 T3-30 T4-2
E E

Bản vẽ tham chiếu ........ :PHẦN MẠCH THAY ĐỔI


PHƯƠNG THỨC THAY THẾ:
MX-18102017 1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
E03+CRP3 / CR315 2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH OUTPUT RƠ LE F21 HIỆN HỮU
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE DIGITAL OUTPUT OF MAIN RELAY (OLD) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR315
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR315.a

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A FUNCTION 25&79 ANNUNCIATION FROM RELAY A


/ CR307-8:A FROM MAIN RELAY

/ CR307-1:C

/ CR311-8:A
/ CR307-1:B

/ CR310-3:B

/ CR310-3:B

/ CR310-3:B

/ CR310-4:B

/ CR310-4:B

/ CR310-4:B

/ CR310-5:B

/ CR310-5:B
C13+

253

793

SC3

AL1

AL2

AL3

AL4

AL5

AL6

AL7

AL8
B B

SC3
/ CR317-1:A
C C

C13+ WD3
/ CR316-1:A / CR317-8:D

F87L SWITCH-ON TO FAULT

F87L TELE FROTECTION


F87L 21 ZONE 1 TRIP

F87L 21 ZONE 2 TRIP

F87L 21 ZONE 3 TRIP

F87L 21 ZONE 4 TRIP

F87L 67/50/51 TRIP

F87L 79/25 CLOSE

RELAY FAILURE
D D
253

793

F87L F87L F87L


IO2 IO3 IO2
B4 B8 B12 B14 C2 C4 C6 C8 C12 C14 B7

BO2.1 BO2.2 BO3.1 BO3.2 BO3.3 BO3.4 BO3.5 BO3.6 BO3.7 BO3.8

B3 B5 B11 B13 C1 C3 C5 C7 C11 C13 B10


E E

........ :PHẦN MẠCH THAY ĐỔI


PHƯƠNG THỨC THAY THẾ:
1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH OUTPUT RƠ LE F87L MỚI
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE DIGITAL OUTPUT OF MAIN RELAY (NEW) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR315.a
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR316

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TRIP F861 START 50BF TRIP COIL 1 TRIP TO PLC


A FROM MAIN RELAY FROM MAIN RELAY FROM MAIN RELAY FROM MAIN RELAY A

CR315-2:D/
C13+ C13+
/ CR319.1:A

CR303-5:E /
R23+ R23+
/ CR317.1:B

=COM+TELE

B B

-XX X X

C3202 3 4

/ CR318.1:A

/ CR319.1:A
/ CR317.1:B
C C
-XT 27 28
TR863

SBF3

TC13

F87L 21 TELE SEND


TRIP COIL 1-3
START BF3
TRIP 863

D D

-F21
/CR323.1:A T3-9 T3-3 T3-5 T3-7

BO1 BO2 BO3 BO4

T3-10 T3-4 T3-6 T3-8

E E

Bản vẽ tham chiếu ........ :PHẦN MẠCH THAY ĐỔI


PHƯƠNG THỨC THAY THẾ:
MX-18102017 1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
E03+CRP3 / CR316 2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH OUTPUT RƠ LE F21 HIỆN HỮU
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE DIGITAL OUTPUT OF MAIN RELAY (OLD) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR316
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET CR316.a

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TRIP F861 START 50BF TRIP COIL 1 TRIP TO PLC


FROM MAIN RELAY FROM MAIN RELAY FROM MAIN RELAY FROM MAIN RELAY
A A

CR315-2:D/
C13+ C13+
/ CR319.1:A

CR303-5:E /
R23+ R23+
/ CR317.1:B

=COM+TELE

B B

-XX X X

C3202 3 4

/ CR318.1:A

/ CR319.1:A
/ CR317.1:B
C C
-XT 27 28
TR863

SBF3

TC13
D D

F87L
IO1 B10 B12 B14 C2

BO1.1 BO1.2 BO1.3 BO1.4

B9 B11 B13 C1

E E

........ :PHẦN MẠCH THAY ĐỔI


PHƯƠNG THỨC THAY THẾ:
1. TÁCH CÁC MẠCH LIÊN QUAN ĐẾN RELAY F21
2. ĐẤU NỐI TƯƠNG ĐƯƠNG CÁC MẠCH CHỨC NĂNG VÀO RELAY F87L

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT MẠCH OUTPUT RƠ LE F87L MỚI
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE DIGITAL OUTPUT OF MAIN RELAY (NEW) PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. CR316.a
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET D01

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

B B
TỦ +CRP3 TỦ +RTU MAIN

IEC 61850
FO.6
FIBER-LC
RUN ERROR
SIPROTEC SIPROTEC SIPROTEC

F87L SW1 FIBER-SC


ADVANTECH 1 2 3 4 9 10 11 12 17 18 19 20 25 27 SFP SFP

EKI-9226G

C C
CONSOLE

5 6 7 8 13 14 15 16 21 22 23 24 26 28

4
8

5
9

6
Ctrl

I
ETHERNET SWITCH
1 2 3

Fn 0 . O

F87L RELAY

D D

E E

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT SƠ ĐỒ KẾT NỐI TRUYỀN THÔNG RELAY F87L
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE COMMUNICATION OF 87L PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. D01
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET D02

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

TRẠM BIẾN ÁP 110kV MỸ XUYÊN TRẠM BIẾN ÁP 110kV HÒA ĐÔNG

TỦ THÔNG TIN TỦ TELECOM /S00+TE


B B

NMOC FIBER OPGW-FO NMOC


JB JB

FIBER ODF FIBER ODF

C C

FIBER OPTIC FIBER OPTIC


TỦ +CRP3 TỦ E02+WR

RUN ERROR RUN ERROR


SIPROTEC SIPROTEC SIPROTEC SIPROTEC SIPROTEC SIPROTEC

D F87L F87L D

7 8 9 7 8 9
Ctrl Ctrl
4 5 6 4 5 6

I I
1 2 3 1 2 3

Fn 0 . O Fn 0 . O

F87L RELAY F87L RELAY

E E

GHI CHÚ:
THIẾT BỊ THUỘC PHẠM VI DỰ ÁN
THIẾT BỊ HIỆN HỮU

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT SƠ ĐỒ KẾT NỐI CÁP QUANG PHỐI HỢP BẢO VỆ RELAY F87L
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE INTERCOMMUNICATION OF 87L PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. D02
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET Z1

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=E03+CRP3

FUNCTION F87L -7SL86 F87L FUNCTION FUNCTION F87L - 7SS85


A A

IO1 IO1 IO4

C1 A1 + =
A1 (~) Power
PHASE A CURRENT INPUT /CR305.a.6 I1 BO1.4 /CR316.a.7 TRIP TO PLC FROM MAIN RELAY /CR305.a.5 _
= Supply
A2 C2 A2

A3
PHASE B CURRENT INPUT /CR305.a.6 I2
A4

A5 C6 L
PHASE C CURRENT INPUT /CR305.a.6 I3 BO1.5
A6 C4
B B
M
A7 C3
PHASE N CURRENT INPUT /CR305.a.6 I4
N
A8

C10 P
BO1.6
C8

B1 C7
PHASE A VOLTAGE NPUT /CR305.a.6 V1
CB202
B2

B3 C13
PHASE B VOLTAGE NPUT /CR305.a.6 V2 BI1.1
-
B4 D1
C C
B5 C14
PHASE C VOLTAGE NPUT /CR305.a.6 V3 BI1.2
-
B6 D2

B7 D5
VX VOLTAGE INPUT /CR305.a.6 V4 BI1.3
-
B8 D3

D6
BI1.4
-
D4

B9 D7
TRIP F861 FROM MAIN RELAY /CR316.a.3 BO1.1 BI1.5
D - D
B10 D9

B11 D8
START 50BF FROM MAIN RELAY /CR316.a.4 BO1.2 BI1.6
-
B12 D10

B13 D13
TRIP COIL 1 FROM MAIN RELAY /CR316.a.5 BO1.3 BI1.7
-
B14 D11

D14
BI1.8
-
D12

E E

IO202

F87L SIEMENS: 7SL86_P1C460309

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT THAM CHIẾU RELAY F87L
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE REFERENCES LINE DIFFERENTIAL RELAY F87L PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. Z1
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET Z2

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=E03+CRP3

FUNCTION F87L -7SL86 FUNCTION F87L -7SL86 F87L FUNCTION


A A

IO2 IO3 IO3


F
+ = S
POWER SUPPLY /CR305.a.5 B1 PS B11 A1
(~)
_ F87L 21 ZONE 1 TRIP /CR315.a.3 BO3.1 BI3.1 /CR314.a.2 CIRCUIT BREAKER ON
= -
B2 B12 A3
S
B13 A2
F87L 21 ZONE 2 TRIP /CR315.a.4 BO3.2 BI3.2 /CR314.a.2 CIRCUIT BREAKER OFF
-
B14 A4
S S
B3 C1 A7
253 /CR315.a.2 BO2.1 F87L 21 ZONE 3 TRIP /CR315.a.4 BO3.3 BI3.3 /CR314.a.3 SPRING CHARGED
-
B4 C2 A5
B B
S
C3 A8
F87L 21 ZONE 4 TRIP /CR315.a.5 BO3.4 BI3.4 /CR314.a.3 VT LINE 2 OFF
-
C4 A6
S
B8 C5 A9
793 /CR315.a.2 BO2.2 F87L 67/50/51 TRIP /CR315.a.5 BO3.5 BI3.5 /CR314.a.4 VT BUS 2 OFF
-
B6 C6 A11
S
B5 C7 A10
F87L 79/25 CLOSE /CR315.a.6 BO3.6 BI3.6 /CR314.a.5 AUTO RECLOSE ON
-
C8 A12
F S
B9 C11 B1
RELAY FAILURE /CR315.a.7 LC F87L SWITCH-ON TO FAULT /CR315.a.6 BO3.7 BI3.7 /CR314.a.5 AUTO CLOSE
-
B7 C12 A13
C C
S
B10 C13 B2
F87L TELE FROTECTION /CR315.a.7 BO3.8 BI3.8 /CR314.a.6 MANUAL CLOSE
-
C14 A14

- B3
B11
BI3.9 /CR314.a.7 F67/67N TRIP
-
B5
B12 BI2.1
B4
BI3.10 /CR314.a.7 TELE RECEIVED
B14 BI2.2 -
B6

B13 BI2.3 B9
BI3.11 /CR314.a.8 SPARE
D - D
B7

B10
Fiber BI3.12 /CR314.a.4 OFF FUNCTION 88L BY SWITCH
DIGSI, IEC61850, DNP3.0,... E 2 x FO -
optical B8

F Spare D5
BI3.13
-
D7
G D-sub 9
D6
BI3.14
H D-sub 15 -
D8

DIGSI 5 J RJ45 Ethernet D11


E BI3.15 E
-
D9
K RJ45
D12
BI3.16
-
D10

PS201
IO207

SIEMENS: 7SL86_P1C460309

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT THAM CHIẾU RELAY F87L
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE REFERENCES LINE DIFFERENTIAL RELAY F87L PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. Z2
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET Z12

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

=E03+CRP3

SELECTION SWITCH "ON/OFF": CA10-A221-600E S0/ K&N

A A
ON X X

OFF X X

1 3 5 7
OFF
ON

Remove Remove
Jump Jump
2 4 6 8
B B

S.87L /CR314.a.4

C C

D D

E E

DRAWN. BY DUC.CX TITLE: BAY No. =E03


110kV HOA DONG WIND POWER PLANT THAM CHIẾU THIẾT BỊ ĐIỀU KHIỂN
F F
CHECKED BY HOANG.NH 110kV MY XUYEN SUBSTATION R
THT TRADING, SERVICE CONTROLLING DEVICES REFERENCE PANEL No. +CRP3
AND HIGH TECHNOLOGY
A 9/06/2021 ISSUE FOR APPROVE APPROVED BY DUNG.NT GEN. CONTRACTOR THANH DAT POWER CONSTRUCTION DESIGNING CONSULTING Co., LTD DRAWING NO.: SHEET No. Z12
JOIN STOCK COMPANY
THE HIGH TECH COMPANY TD/HDMX-E03+CRP3
REV. DATE JOB NUMBER: THT_HDMX_2021 EMPLOYER WIND POWER HOA DONG COMPANY LIMITED NEXT SHEET

1 2 3 4 5 6 7 8