MF1-EL series earth leakage circuit breakers is a new designed MCCB, developed and manufactured
adopting international advanced technology. MF1-EL (ELCB/RCCB) rated insulating voltage AC 800V is
suitable for using in the circuit of AC 50Hz /60Hz, rated voltage 400V, rated working current from16A to 630A
to distribute electric power and to protect the line and the equipment from being damaged due to overload,
short current and under-voltage. It can also be used for infrequently switch and starting of motor and for
motor overload, short circuit and under-voltage protections and can protect the electric appliance from
dangerous fire caused by ground faulty current due to the damage of electric appliance
insulation.MF1-EL (ELCB/RCCB) with the advantages of the small volume, high breaking capacity, short
over-arcing, strong anti-vibration and so on. In accordance with the ultimate short circuit breaking capacity
classified into two types: Type M (second high breaking), Type H (high breaking).
fåíêçÇìÅíáçå=çÑ=píêìÅíìêÉ
MCCB Moulded Case Circuit Breakers
j~áå=qÉÅÜåáÅ~ä=`Ü~ê~ÅíÉêáëíáÅ=fåÇÉñ=pÉÉ=q~ÄäÉ=NKOKPKQ
Table 1
Type MF1-100-EL MF1-225-EL MF1-400-EL MF1-630-EL
Operating short-circuit
AC400V 35 50 16 35 50 35 42 42
breaking capacity Ics(kA)
H 92 92 90 90 110.0 118.0
Shunt release,
Under-voltage release,
Alarm contacts
Notice: 1.Limiti breaking and arcing -over distance including installed vertically and installed horizontally.
2.When three poles breaker connect with three-phase , negative load can not with neutral wire, otherwise fault action will happen.
3. When three poles breaker connect with single phase, wire of phase connect with left pole, neutral connect with right pole, don not
connect center pole.
MCCB
Moulded Case Circuit Breakers
Capacity-reducing coefficient for ambient temperature change see following Table 2 please Table 2
Temp +40 +45 +50 +55 +60
Notice: Above capacity-reducing coefficient are all achieved with rated frame current traveling through Protection Characteristic
mêçíÉÅíáçå=`Ü~ê~ÅíÉêáëíáÅë
MF1-EL, ELCB/RCCB provide the feature of inverse time lag being thermodynamic release and the instant
operation being the magnetic release details as shown on Table 3(use of distribution) and Table 4(use for motor
protection circuit breaker) Table 3
Thermodynamic Release (Temp+55) Electromagnetic release action
Rated current of release (A)
1.05In(cold state) non-action(h) 1.30In(hot state)action time(h) current(A)
In 63 1 <1
10In 20%
63 In 125 2 <2
Notice: For MF1-225-EL4 four poles breaker, its neutral electromagnetic release (short current protect) no specification 5In
Table 4
Thermodynamic Release Ambient (Temp+55)
Rated current of Electromagnetic
1.01In(cold state) non- 1.20In(hot state )action 1.50In(hot state )action 7.2In(cold state) non-
release (A) Release Current
action(h) time(h) time(h) action(h)
`Ü~ê~íÉêáëíáÅ=`ìêîÉ
Current-temperature
characteristic
MCCB Moulded Case Circuit Breakers
lîÉê~ää=~åÇ=fåëí~ää~íáçå=aáãÉåëáçå
Overall and Installation Dimension
MF1-400-ELM 150 96 257220.5 224 110 147 38 4.5 3.5 88.6 65 30 198 144 44 194 7 124 172164 8.5 10.5224 267 67.5127.5 32 P 6.5 37 166279 60 83.5106.5 21 M10 M8 129 60 108 58 152 200 8.5
MF1-630-ELM 210 140 280 240 243 118 155 45.3 8 9 81 66 44 280 210 70 243 7 178 248158 16 13 243 295 84 48 P 7 37 183296 61 97 148 16 M12 M8 143 140 210 58 213 283 10
Notice: Picture 1.2.3 show front board wiring and installation aperture dimension
Picture 4.5.6 show rear board wiring and installation aperture dimension
Picture 7. 8 show wiring insertion type and installation aperture dimension