MCCB

Moulded Case Circuit Breakers

MF1-EL series earth leakage circuit breakers is a new designed MCCB, developed and manufactured
adopting international advanced technology. MF1-EL (ELCB/RCCB) rated insulating voltage AC 800V is
suitable for using in the circuit of AC 50Hz /60Hz, rated voltage 400V, rated working current from16A to 630A
to distribute electric power and to protect the line and the equipment from being damaged due to overload,
short current and under-voltage. It can also be used for infrequently switch and starting of motor and for
motor overload, short circuit and under-voltage protections and can protect the electric appliance from
dangerous fire caused by ground faulty current due to the damage of electric appliance
insulation.MF1-EL (ELCB/RCCB) with the advantages of the small volume, high breaking capacity, short
over-arcing, strong anti-vibration and so on. In accordance with the ultimate short circuit breaking capacity
classified into two types: Type M (second high breaking), Type H (high breaking).

The breakers could be installed vertically (upright) or horizontally (transverse)


Adverse wiring of terminal is prohibited, in other words terminals "1", "3", "5" only connect to power
Supply, "2", "4", "6", only connect to load.
MF1-EL MCCB comply with the following standards:
IEC 947-1 and GB/T 14048.1 General
IEC 947-2 and GB/T 14048.2 Low voltage breakers.
Appendix B earth leakage circuit breakers
IEC 947-4 and GB/T 14048.4 Contactors and motor starters.
IEC 947-5.1 and GB/T 14048.5 Electrical equipment of electromechanical control circuit.

fåíêçÇìÅíáçå=çÑ=píêìÅíìêÉ
MCCB Moulded Case Circuit Breakers

j~áå=qÉÅÜåáÅ~ä=`Ü~ê~ÅíÉêáëíáÅ=fåÇÉñ=pÉÉ=q~ÄäÉ=NKOKPKQ
Table 1
Type MF1-100-EL MF1-225-EL MF1-400-EL MF1-630-EL

Frame current Inm(A) 100 225 400 630


(10)162025
Rated current In(A) 100125140160 225250315
3240506380 400500600
180200225 350400
100
Pole number 3 4 3 4 4 4

Rated insulating voltage Ui(V) AC800

Rated working voltage Ue(V) AC400 AC400 AC400 AC400

Rated impulse withstand voltageUimp(V) 8000 8000 8000 8000

Arcing-over distance (mm)  50  50  100  100

Grade of breaking capacity M H M M H M M M

Limiting short-circuit breaking


AC400V 50 85 16 50 85 50 65 65
capacity Icu(kA)

Operating short-circuit
AC400V 35 50 16 35 50 35 42 42
breaking capacity Ics(kA)

Rated surplus action current No-Delay Type 100/300/500 -


I  n(mA) Delay Type 100/300/500 300/500/1000
1
Rated surplus non-action current I  no(mA) få
2

Rated surplus short current making and 1


fÅì
breaking capacityI  m(kA) 4

energized 1500 1000 1000 1000


Operational performance
unenergized 8500 7000 4000 4000
External dimension

W 92 122 107 142 198 280


(mm)

L 150 150 165 165 257 280

H 92 92 90 90 110.0 118.0

Shunt release,      

Under-voltage release,      

Leakage alarm unit mold,      

Auxiliary contact and      

Alarm contacts      

Handle operation mechanism,      

Power-driven operation mechanism.      

Notice: 1.Limiti breaking and arcing -over distance including installed vertically and installed horizontally.
2.When three poles breaker connect with three-phase , negative load can not with neutral wire, otherwise fault action will happen.
3. When three poles breaker connect with single phase, wire of phase connect with left pole, neutral connect with right pole, don not
connect center pole.


MCCB
Moulded Case Circuit Breakers

 Capacity-reducing coefficient for ambient temperature change see following Table 2 please Table 2
Temp +40 +45 +50 +55  +60

Temp coefficient Capacity-reducing Capacity-reducing Capacity-reducing Capacity-reducing Capacity-reducing


Coefficient Coefficient Coefficient Coefficient Coefficient
MF1-100-EL 1.1In 1.08In 1.04In 1In 0.92In
MF1-225-EL 1.06In 1.04In 1.02In 1In 0.96In
MF1-400-EL 1.14In 1.12In 1.06In 1In 0.94In
MF1-630-EL 1.14In 1.10In 1.06In 1In 0.94In

Notice: Above capacity-reducing coefficient are all achieved with rated frame current traveling through Protection Characteristic

mêçíÉÅíáçå=`Ü~ê~ÅíÉêáëíáÅë
MF1-EL, ELCB/RCCB provide the feature of inverse time lag being thermodynamic release and the instant
operation being the magnetic release details as shown on Table 3(use of distribution) and Table 4(use for motor
protection circuit breaker) Table 3
Thermodynamic Release (Temp+55) Electromagnetic release action
Rated current of release (A)
1.05In(cold state) non-action(h) 1.30In(hot state)action time(h) current(A)

In  63 1 <1
10In  20%
63 In  125 2 <2

125 < In  630 2 <2 5In  20% 10In  20%

Notice: For MF1-225-EL4 four poles breaker, its neutral electromagnetic release (short current protect) no specification 5In

Table 4
Thermodynamic Release Ambient (Temp+55)
Rated current of Electromagnetic
1.01In(cold state) non- 1.20In(hot state )action 1.50In(hot state )action 7.2In(cold state) non-
release (A) Release Current
action(h) time(h) time(h) action(h)

10  In  400 2 2 8min 2s=Y=Tp  20s 12In  20%

`Ü~ê~íÉêáëíáÅ=`ìêîÉ

MF1-100-ELM H time/current MF1-225-ELM H time/current


characteristic curve characteristic curve
(current distribution) (current distribution)
Current-temperature
characteristic

Current-temperature
characteristic



MCCB Moulded Case Circuit Breakers

lîÉê~ää=~åÇ=fåëí~ää~íáçå=aáãÉåëáçå
Overall and Installation Dimension

Front board wiring Rear board wiring Insertion type wiring


Type

W W1 L L1 L2 H H1 H2 H3 H4 E F G W2 W3 A B fd L8’ L8´ L9 t fd2 L3 L4 H5 H6 fD M fd1 H7 L5 L6 H8 H9 H10H11 M1 M2 J K K´ L7 W4 W4´ fd3

H 92 60 150 100 132 92 110 28.5 10


MF1-100-ELM 4 50 22 17.6122 90 30 129 4.5 72 102 90 132 164 53 93 22 M8 5.5 35 90 168 50 64 76 17.5 M8 M6 56 60 90 41 94 125 6.5
t1
H 107 70 165132.5 144 90 110 24 5
MF1-225-ELM 4 62 22 22 142 105 35 126 45 87 122 93 5 8.5 144 173 55 100 24  P 5.5 35 88 183 50 71.5 86.5 17.5 M8 M6 54 70 105 51 110 145 6.5

MF1-400-ELM 150 96 257220.5 224 110 147 38 4.5 3.5 88.6 65 30 198 144 44 194 7 124 172164 8.5 10.5224 267 67.5127.5 32  P 6.5 37 166279 60 83.5106.5 21 M10 M8 129 60 108 58 152 200 8.5

MF1-630-ELM 210 140 280 240 243 118 155 45.3 8 9 81 66 44 280 210 70 243 7 178 248158 16 13 243 295 84 48  P 7 37 183296 61 97 148 16 M12 M8 143 140 210 58 213 283 10

Fig .1 Fig .2 Fig .3

Fig. 4 Fig. 5 Fig. 6 Fig. 7 Fig. 8

Notice: Picture 1.2.3 show front board wiring and installation aperture dimension
Picture 4.5.6 show rear board wiring and installation aperture dimension
Picture 7. 8 show wiring insertion type and installation aperture dimension