GENERAL ELECTRICAL NOTES E


L
1 SET 3 - 150 SQ. MM THHN CONDUCTOR
1 - 22 SQ. MM THHN CONDUCTOR ( G )
1 SET 3 - 30 SQ. MM THHN CONDUCTOR
1 - 8.0 SQ. MM THHN CONDUCTOR ( G )

AND SPECIFICATIONS: 2 - 300 AT / 500 AF , 3P, 3 PHASE, 230V, 22 kAIC


IN A 75MM Ø SCHEDULE 40 µPVC PIPE IN A 50MM Ø SCHEDULE 40 µPVC PIPE

MOULDED CASE CIRCUIT BREAKER


1...ALL WORKS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION MANUAL TRANSFER SWITCH ASSEMBLY
OF THE PHILIPPINE ELECTRICAL CODE,THE LOCAL ORDINANCES,THE MDP
AFSS PB
RULE AND REGULATIONS OF THE LOCAL ENFORCING AUTHORITY,AND
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. 3 - 37.5 kVA, 1 PHASE, CONVENTIONAL, AMORPHOUS, 1 SET 3 - 175 SQ. MM THHN CONDUCTOR
POLE - MOUNTED, DISTRIBUTION TRANSFORMER 1 - 22 SQ. MM THHN CONDUCTOR ( G )
300 AT
2...ALL WORKS HEREIN SHALL BE DIRECTLY SUPERVISED BY DULY LI- 13.2 kV PRIMARY : 230 V SECONDARY IN A 75MM Ø SCHEDULE 40 µPVC PIPE 3P, 22 kAIC
100 AT
3P, 15 kAIC
CENSED ELECTRICAL ENGINEER AS ENFORCED BY THE NEW ELECTRI- 3 PHASE - BANKED
CAL ENGINEERING LAW OR R.A. 7920. 100 AT 100 AT

3...ALL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE


PLANS AND SPECIFICATIONS.
G FIRE PUMP 01
75 AT 30 AT

02 JOCKEY PUMP

75 AT 125 AT
S S
4...ALL MATERIALS TO BE USED SHALL BE BRAND NEW,OF THE BEST P
A
P
A
QUALITY AND OF THE APPROVED TYPE AND SHALL BEAR THE MANU- 110 kVA / 88 kW STAND - BY POWER C C
E E

FACTURERES NAME INCLUDING THE " PSA" MARK. 230 V - 3 PHASE - 60 HZ


S S
227L FUEL TANK CAPACITY P P
5...POWER SUPPLY TO NDP-PMU 50 SHALL BE 3 PHASE,4-WIRE,230 FEEDER: GENERATOR SET
A
C
A
C
E E
VOLTS. 3 - 150 SQ. MM THHN
6...RACEWAY SCHEDULE SHALL BE AS FOLLOWS; 1 - 22 SQ. MM ( G ) THHN
A...CONCRETE PEDESTAL TO MDP-UPVC PIPE CHEDULE 40. IN A 75MM Ø SCHEDULE 40
B...MDP TO DISTRIBUTION PANEL BOARS-RSC. RIGID STEEL CONDUIT
C...BRANCH CIRCUITS FOR POWER,LIGHTING AND AUXILLIARY- 1 SET 3 - 30 SQ. MM THHN CONDUCTOR 1 SET 3 - 14 SQ. MM THHN CONDUCTOR 1 SET 3 - 38 SQ. MM THHN CONDUCTOR

UPVC SCHEDULE 40 1 - 8.0 SQ. MM THHN CONDUCTOR ( G ) 1 - 5.5 SQ. MM THHN CONDUCTOR ( G ) 1 - 8.0 SQ. MM THHN CONDUCTOR ( G )

MINIMUM SIZE OF RACEWAY SHALL BE 15MM.DIAMETER. IN A 50MM Ø SCHEDULE 40 µPVC PIPE IN A 25MM Ø SCHEDULE 40 µPVC PIPE IN A 50MM Ø SCHEDULE 40 µPVC PIPE
PRIVATE
7...OUTLET BOXES SHALL HAVE A MINIMUM THICKNESS OF GA. #16 CONC.POLE MOTOR CONTROL :
WITH 1/2 KO AND SHALL BE WATT - HOUR BY OTHERS

PAINTED WITH RED LEAD PAINT PRIOR TO INSTALLATION.


8...WIRES AND CABLES SHALL BE OF THE APPROVED TYPE AND BEAR-
METER M
ING THE " PSA " mark unless specified of indicate otherwise.all power and light- 10 HP - 230V - 3PHASE - 60 HZ
LP2S/PP2S
ing conductors shall be insulated for 600 volts minimum.
ELEVATOR
9...WIRING DEVICES SHALL HAVE MINIMUM RATING OF 10 APERES,250
VOLTS. 125 AT

10...PANEL BOARS SHALL CONFORMED TO THE LOAD SCHEDULE AS LP1G/PP1G 3P, 15 kAIC

SHOWN ON PLANS WITH RESPECT TO BREAKER PHASE


ARRANGEMENT, 15 AT 15 AT

RATING,CAPACITY AND SHORT CIRCUIT CONSIDERATION. 100 AT


LIGHTING SYSTEM 01 02 LIGHTING SYSTEM

11...FIRE ALARM DEVICES SHALL COMPLY WITH THE NFPA PROVISIONS 3P, 15 kAIC
15 AT 15 AT

LIGHTING SYSTEM 03 04 LIGHTING SYSTEM


AND SHALL BEAR THE " UL ".
15 AT 15 AT 15 AT 15 AT
12...ALL NON-CURRENT CARRYING METALLIC PARTS,CABINETS AND LIGHTING OUTLET 01 02 LIGHTING OUTLET LIGHTING SYSTEM 05 06 LIGHTING SYSTEM
EQUIPMENT FRAMES SHALL BE PROPERLY GROUNDED. 15 AT 15 AT 15 AT 15 AT

LIGHTING OUTLET 03 04 LIGHTING OUTLET LIGHTING SYSTEM 07 08 LIGHTING SYSTEM


13...MOUNTING HIEGHTS SHALL BE AS FOLLOWS:
15 AT 15 AT 20 AT 20 AT

A. WALL SWITCHES 1400 MM AFF TO CENTER OF DEVICE LIGHTING OUTLET 05 06 LIGHTING OUTLET CONVENIENCE OUTLET 09 10 CONVENIENCE OUTLET

B. WALL OUTLETS 300 MM AFF TO CENTER OF DEVICE 15 AT 15 AT 20 AT 20 AT

LIGHTING OUTLET 07 08 LIGHTING OUTLET CONVENIENCE OUTLET 11 12 CONVENIENCE OUTLET


C. COUNTERTOP OUTLETS 150 MM TOP OF COUNTER TO CENTER OF DEVICE
20 AT 20 AT 20 AT 30 AT
D. INTERCOM OUTLETS 1400 MM AFF TO CENTER OF BOX CONVENIENCE OUTLET 09 10 CONVENIENCE OUTLET CONVENIENCE OUTLET 13 14 SPECIAL POWER OUTLET
E. CONTROL CABINETS 1500 MM AFF TO TOP OF ENCLOSURE (VERTICAL) 20 AT 20 AT 20 AT 30 AT

F. MANUAL STATION 1400 MM AFF TO CENTER OF DEVICE CONVENIENCE OUTLET 11 12 CONVENIENCE OUTLET CONVENIENCE OUTLET 15 16 SPECIAL POWER OUTLET
G. BELL 200 MM BELOW BEAM OR FINISHED CEILING 20 AT 30 AT 30 AT 30 AT

CONVENIENCE OUTLET 13 14 SPECIAL POWER OUTLET SPECIAL POWER OUTLET 17 18 SPECIAL POWER OUTLET
H. EMERGENCY LIGHT 300 MM BELOW BEAM OR FINISHED CEILING
I. EXIT LIGHT 150 MM ABOVE DOOR JAMB 30 AT 30 AT 30 AT 30 AT

SPECIAL POWER OUTLET 15 16 SPECIAL POWER OUTLET SPECIAL POWER OUTLET 19 20 SPECIAL POWER OUTLET

30 AT 20 AT 30 AT 20 AT

SPECIAL POWER OUTLET 17 18 SPARE 1 SPECIAL POWER OUTLET 21 22 SPARE 1

20 AT 20 AT 20 AT 20 AT

SPARE 2 19 20 SPARE 3 SPARE 2 23 24 SPARE 3

GROUND FLOOR SECOND FLOOR

SINGLE LINE DIAGRAM


SCALE: 1:100 MTS

PREPARED BY: CHECKED BY: CHECKED/REVIEWED BY: PROJECT TITLE: RECOMMENDING APPROVAL: RECOMMENDING APPROVAL: APPROVED BY: SHEET No.

CONSTRUCTION OF EMERGENCY OPERATION E-7 48


ALVIN JOHN P. HALLARSIS, UAP JAKE B. BUENAVISTA ZALDY A. GAYOSA, REA, REB AND TRAINING CENTER CYRUS JOSE J. UBANO, CPA, MBA RUEL C. TIANCHON, MPA, REA, REB ATTY. ELIORDO U. OGENA
ARCHITECT I ENGINEER I CHIEF, PLANNING, DEVELOPMENT CITY HALL COMPOUND, CITY OF KORONADAL CDRRMO CITY ENGINEER CITY MAYOR