Professional Documents
Culture Documents
DOI: 10.1049/gtd2.12402
Yuan Wang1 Ruifeng Wang2,3 Kexin Pan1 Yang Xu1 Kevin Rapp4
1
State Key Laboratory of Electrical Insulation and Abstract
Power Equipment, Xi’an Jiaotong University,
Several retrofillings have been performed by different utilities in China. However, there is
Western China Science & Technology Innovation
Harbour, Xi’an, China still insufficient understanding of the retrofilling procedures for minimising residual min-
2
Cargill Bioindustrial, Shanghai International
eral oil and on the effect of the temperature rise of transformers. Following new detailed
Commerce Center, Shanghai, China procedures, an out-of-service S11-M-315/10 (10 kV 315 kVA) and a new S13-M-400/10
3
Department of Electrical Engineering, North (10 kV 400 kVA) distribution transformers were selected to retrofill their mineral oil with
China Electric Power University, Baoding, China FR3, a soybean-based natural ester. A method was proposed to predict the residual min-
4
Cargill Bioindustrial, Plymouth, Minnesota, USA eral oil content, which uses the kinematic viscosity at 60◦ C. This method fills a gap in the
testing of residual mineral oil content. The mass ratios of residual mineral oil were 1.24%
Correspondence for the S11-M-315/10 transformer and 2.05% for the S13-M-400/10 transformer, based
Yang Xu, State Key Laboratory of Electrical Insula- on the procedures in this study. The fire point of the mixed oil after retrofilling was 352◦ C,
tion and Power Equipment, Xi’an Jiaotong University,
Western China Science & Technology Innovation which meets the K-class less-flammable requirements, indicating a proper control of resid-
Harbour, Xi’an, Shaanxi Province 710049, China. ual mineral oil. After retrofilling, the time of reaching the limits of the 1.5 times rated
Email: xuyang@xjtu.edu.cn load was 30% longer than that of the mineral oil transformer. Two retrofilled transform-
ers have been operating in good conditions since November 2019 for the S11-M-315/10
Funding information
Xian Xibian Zhong Te Electric CO, Ltd.; State Grid
transformer and December 2020 for the S13-M-400/10 transformer.
Shaanxi Electric Power Company
This is an open access article under the terms of the Creative Commons Attribution License, which permits use, distribution and reproduction in any medium, provided the original work is
properly cited.
© 2022 The Authors. IET Generation, Transmission & Distribution published by John Wiley & Sons Ltd on behalf of The Institution of Engineering and Technology
dielectric properties at low mineral oil content of 3.95% after TABLE 1 Main parameters of the target transformer
retrofilling mineral oil transformer with synthetic ester [15]. Main parameters S11-M-315/10 S13-M-400/10
C.P. McShane proved that the aging rate of insulation Kraft
Production data 2016.02 2018.12
paper is significantly slower in natural ester than in conven-
tional transformer oil through an experimental comparison Voltage/capacity 10 kV/315 kVA 10 kV/400 kVA
of the thermal aging of mineral oil and natural ester [16] Vector Dyn11 Dyn11
and performed further experiments [17] for clarification. Pro- Seal type Sealed/corrugated Sealed/corrugated
vided that the temperature rise of the natural ester trans- tank tank
former does not exceed the temperature rise of mineral oil by Cooling method ONAN ONAN
more than 21 K, cellulose insulation will last longer in nat- Insulating resistance 5000 MΩ 5000 MΩ
ural ester than in mineral oil transformers [18]. In addition, (HV to LV and
Moore et al. [19] and Pillai et al. [20] found that the reduc- earth)
tion and suppression of moisture buildup in cellulose reduce Insulating resistance 5000 MΩ 5000 MΩ
the aging rate. The Reedy Creek Improvement District reported (LV to HV and
a case of retrofilling a 67 kV transformer to extend its life and earth)
performance [21]. Insulating resistance 5000 MΩ 5000 MΩ
Although retrofillings have been performed in many parts (HV to LV)
of the world, it is still unclear whether retrofilling mineral oil HV winding resistance 3.045 Ω/2.941 Ω 2.283 Ω/2.298 Ω
with natural esters can cause an elevated temperature rise. In (before/after
retrofilling)
the case of retrofilling a 66/11 kV 12.5 MVA power trans-
former with a natural ester, Rajaram Shinde found that the tem- LV winding resistance 2.396 mΩ/2.317 mΩ 1.489 mΩ/1.505 mΩ
(before/after
perature rise is 10–12 K lower than when filling with mineral
retrofilling)
oil [22]. In addition, Santisteban conducted a simulation and
No-load loss 426 W/427 W 383 W/384 W
found that when the insulating liquid velocity is lower than
(before/after
0.78 kg/s, the hot spot temperature of the natural ester trans- retrofilling)
former becomes 9–11 K lower than that of the mineral oil
Load loss (before/after 3776 W/3753 W 4436 W/4332 W
transformer. In addition, when the insulating liquid velocity is retrofilling)
0.9 kg/s, the hot spot temperatures between the two transform-
ers converge to the same value. When the insulating liquid veloc- Abbreviations: HV, high voltage; LV, low voltage.
ity is higher than 1.0 kg/s, the hot spot temperature of the nat-
ural ester transformer is 2–3 K higher than that of the mineral
oil transformer [23]. Lee et al. [24], Smith and Barry [25], and Xian Xibian Zhong Te Electric Co., Ltd. An out-of-service S11-
Yang et al. [26] retrofilled different transformers and concluded M-315/10 and a new S13-M-400/10 distribution transformers
that the temperature rises are 4–6, 5–8, and 4.6 K higher than were selected to retrofill their mineral oil with FR3 to study the
those of mineral oil transformers after retrofilling with natural temperature rise of transformers after retrofilling as well as the
ester. Although natural ester transformers have a higher tem- characteristics of mixed oil. Before and after the retrofilling pro-
perature rise than mineral oil transformers in most cases, the cess, oil, temperature rise, and overload tests were performed to
higher temperature rise limits of natural ester transformers are study the method of controlling the mass ratio of the residual
considered [27]. mineral oil. In addition, tests were performed on different ratios
After retrofilling a transformer with a natural ester, the of mineral oil in the natural ester to obtain a convenient method
allowable duration of operation under 1.5, 1.8, and 2.0 of the for confirming the ratio of residual mineral oil in the retrofilled
rated current was increased by 48%, 27%, and 8%, respec- transformer.
tively [28], indicating that it is beneficial to study the overload
capability of transformers after retrofilling with natural ester.
In Zhao et al. [29], two similar transformers filled with min- 2 MATERIALS AND METHODS
eral oil and natural ester were inoperative. The natural ester
has a higher breakdown voltage, and the insulating paper has 2.1 Materials
a higher degree of polymerisation compared with the min-
eral oil transformer, and the transformer filled with natural An out-of-service S11-M-315/10 distribution transformer with
ester had a 1.57 times overload event in its service history. In a 2-year service history and a new S13-M-400/10 distribution
Scatiggio et al. [30], it was found that high temperature insulat- transformer were selected as sample transformers, and the main
ing materials (natural ester and thermally upgraded Kraft) can parameters are listed in Table 1. Both units were filled with the
provide continuous overloading up to 150% of the nominal conventional mineral oil. The purpose of choosing two simi-
rating. lar capacity and voltage transformers was to increase compara-
Detailed procedures for retrofilling transformers with nat- bility. Considering that transformers with service history may
ural esters were implemented after discussion with the have differences after retrofilling compared with the brand-new
technical staff of Cargill, State Grid Shaanxi Electric Power, and transformers, a transformer in service and a brand new one was
17518695, 2022, 10, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.12402 by CochraneChina, Wiley Online Library on [13/06/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WANG ET AL. 1903
selected. The transformer with the service history had been in A new catheter was used to flush the active part and compo-
service for 2 years, which is long enough for oil to impreg- nents with the natural ester at the two flanges of the removed
nate the insulating paper. Based on these considerations, the bushings. The natural ester used in this procedure is usually
State Grid Corporation of China (SGCC) provided an out-of- approximately 10% of the total oil volume.
service S11-M-315/10 distribution transformer and a new S13-
M-400/10 distribution transformer.
A #25 naphthenic mineral oil (Karamay #25 mineral oil, 2.2.4 Draining oil again and replacing the
Karamay, China) and a natural ester FR3 (Cargill Bioindustrial, gaskets
Shanghai, China) were used in this study.
A large amount of mineral oil can remain in the bottom of the
tank during the flushing procedure. The residual oil was drained
2.2 Retrofilling procedures in China again using the method described in Section 2.2.2. The gas-
kets used should meet the requirements for compatibility with
Retrofilling procedures are under discussion and are being pub- natural esters. Silicone rubber, fluororubber, and fluorosilicone
lished. The retrofilling procedures that we used in this experi- rubber seals can be used in transformers with higher thermal
ment are presented in the flow chart in Figure A1. The details classes. Thereafter, the high-voltage bushing should be rein-
of the flowchart are discussed in the following section. stalled to ensure a good sealing condition.
2.2.1 Transformer check-up before retrofilling 2.2.5 Retrofilling with natural ester and
check-up
The transformer nameplate information should be recorded
with a special focus on the weight of the insulating liquid on In the retrofilling procedure, the pipe must be extended to the
the nameplate. bottom of the transformer to minimise the generation of bub-
The compatibility of materials with FR3 natural esters and bles.
the lowest allowed ambient temperature should be considered. The transformer should be left to stand in the warehouse for
The pour point of FR3 is −21◦ C, which is higher than that of no less than 4 h after retrofilling to wait for the air bubbles in the
mineral oil. This issue may lead to the problem of starting up at ester liquid to be fully dissipated. After retrofilling, the insulating
extremely low ambient temperatures. liquid inside the transformer becomes a mixture of natural ester
The requirements of the inspection on the retrofilled trans- and a small amount of mineral oil.
former are listed in Table A1. Finally, the retrofilled transformer should be inspected again
according to Table A1 to guarantee a successful retrofilling.
a
Exceed the temperature rise limits for the thermal class of 105◦ C, but do not exceed the
limits for the thermal class of 120◦ C.
FIGURE 1 Distribution transformer overload test curve of the State Grid Temperature rise Mineral oil Retrofilled Limits (IEC
Corporation of China (SGCC) for transformer transformer 60076-14)
transformer was in operation for 3 h under 1.5 times of rated High voltage 58.3 62.6 ≤65
winding (K)
load. Whether the temperature rise was steady, the transformer
test proceeded to the next 1.75 times of rated load, as shown Low voltage 58.4 67.2 ≤65
winding (K)
in Figure 1. The total overload tests had five steps and then the
load is cut off after finishing the total 10 h overload test. a
Exceed the temperature rise limits for the thermal class of 105◦ C, but do not exceed the
The temperature rise of the average windings, average oil, and limits for the thermal class of 120◦ C.
top oil were measured at the end of the 1.5 times rated load.
The temperature rise of the top oil was continuously measured
during the test. 3 EXPERIMENT RESULTS AND
ANALYSIS
2.4 Oil tests and prediction of mineral oil 3.1 Temperature rise tests and overload
mass percentage tests
Generally, retrofilling procedures cannot remove all resid- 3.1.1 Temperature rise tests
ual mineral oil, as absorbed oil exists in the solid insulation.
Thus, the insulating liquid in the transformer is a mixture The results of the temperature rise tests are shown in Tables 2
of natural esters and mineral oils. To meet the K-class less- and 3, indicating that the two FR3 fluid retrofilled trans-
flammable requirements, the fire point of the mixed oil should formers have higher temperature rises than the mineral oil
be higher than 300◦ C [7, 32]. Therefore, it is crucial to con- transformers. The top oil temperature rises were higher by 4.1
trol the mass ratio of the mineral oil in the mixed oil. The K (S11-M-315/10) and 5.0 K (S13-M-400/10). The average oil
properties of the insulating oil in the two transformers were temperature rises were higher by 3.3 K (S11-M-315/10) and 4.0
measured before retrofilling, after retrofilling, and after 1 K (S13-M-400/10).
year. The thermal class of cellulose paper immersed in mineral
To confirm the exact mass percentage of mineral oil in the oil is 105◦ C. Thus, the limits in Tables 2 and 3 are the tem-
mixed oil after retrofilling with natural ester, an experiment with perature rise limits for the thermal class of 105◦ C. However,
different mass percentages of mineral oil was designed. The according to IEC 60076-14 standard Annex C [33], as shown in
mineral oil and natural ester were mixed and allowed to stand Table 4, the thermal class of the electrical insulation system can
idle for 2 days to be mixed well. Specifically, 0%–10% mass per- be increased by changing the liquid from mineral oil to natural
centage of mineral oil in 1% steps was blended, as the residual ester, resulting in temperature rise limits of 90 and 75 K for the
mineral oil is generally less than 10%. top oil and average windings, respectively. Therefore, the tem-
The tested properties included water content (IEC 60814), perature rise values of the distribution transformers after retro-
90◦ C dielectric dissipation factor (IEC 60247), 2.5 mm break- filling are up to the temperature rise limits in the IEC 60076-14
down voltage (IEC 60156), DGA (IEC 60599 for mineral oil, standard Annex C. Considering that the thermal class of natural
and IEEE C57.155 for natural ester), kinematic viscosity (ISO ester-immersed cellulose paper is 120◦ C, although the tempera-
2909), open-cup flash point (ISO 2592), and closed cup flash ture rise of the low-voltage windings exceeded the temperature
point (ISO 2719). rise limit of mineral oil, the temperature rise of the low-voltage
17518695, 2022, 10, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.12402 by CochraneChina, Wiley Online Library on [13/06/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WANG ET AL. 1905
TABLE 4 Thermal class of mineral oil and natural ester according to IEC ing was 12.3 and 15.1◦ C, respectively. The ambient temperature
60076-14 was not measured in real time, but only once at the beginning of
Kraft paper with Kraft paper with the test.
Insulating systems mineral oil natural ester The retrofilled 400 kVA transformer had increased tempera-
Cellulose-based thermal 105 120 ture rises for top oil of 7.7 K, average oil of 6.2 K, high voltage
class(◦ C) windings of 5.6 K, and low voltage windings of 11.1 K, when
Temperature rise limits for top 60 90 compared with the mineral oil transformer. These values are
oil (K) beyond the limits as discussed in Section 3.1.1.
Temperature rise limits for 65 75 As shown in Figure 2, the mineral oil and retrofilled trans-
average winding (K) formers exhibited the same trend as the top oil tempera-
ture change in the overload test. The highest temperature rise
value of the top oil occurred at the end of the 2.0 times
TABLE 5 Temperature rise at the end of the 1.5 times rated load of rated load. Furthermore, the highest temperature rise values
S13-M-400/10 transformer of the mineral oil and retrofilled transformers were 109.1 and
121.9 K, respectively. Thus, the temperature values are beyond
Mineral oil Retrofilled
Temperature rise for transformer transformer Limits
the limits as discussed in Section 3.1.1. Accordingly, a con-
ventionally designed mineral oil transformer cannot fulfil the
Top oil (K) 84.0 91.7 ≤60 severe overloading test pattern of the SGCC. Thus, the high
Average oil (K) 67.2 73.4 – overload capacity transformer requires a more specific design,
High voltage winding (K) 95.8 101.4 ≤65 such as thermally upgraded paper or aramid paper for wind-
Low voltage winding (K) 92.5 103.6 ≤65 ings or a lower current density, as per the nameplate power
rating.
S11-M-315/10 S13-M-400/10
fitted curves using 5%–10% ratios and 5%–9% are 325◦ C and
328◦ C, respectively. Two fitted curves have similar fire points at
a 5% ratio, but the latter has a higher R2 . Thus, the ideal fitting
equation for the fire point (y2 ) below 340◦ C is of the following
form:
The fitting equation for the fire point (y2 ) above 340◦ C is as
follows:
4 DISCUSSION
Here, x represents the mass ratio of mineral oil and y1 repre-
sents the kinematic viscosity at 60◦ C values. 4.1 Overload test
The results of the fire points are shown in Figure 4. Owing to
the rapid decrease in the fire point of the mixed oil in relation For the 400 kVA transformer, the hot spot temperature can be
to the percentage of mineral oil at the 5%–10% stage, the fitted calculated according to Figure 2 and IEC 60076-2 as the follow-
curve should be divided into two parts. The first part is a slowly ing formula:
decreasing part with a fire point above 330◦ C. The second part
is the rapidly decreasing part with a fire point below 330◦ C. The Δ𝜃h = Δ𝜃o + Hg (6)
second part is the main discussion point, as the fire point will be
lower than 300◦ C, and does not meet the K-class less-flammable where Δ𝜃h represents the hot-spot temperature rise, Δ𝜃o rep-
requirements. Figure 4 compares the different fitted curves in resents the top oil temperature rise, H represents the hot spot
the second part. Although the fitted curve using 6%–10% ratios factor, and g represents the average winding gradient.
of the mineral oil has the highest R2 , the fire point of this fitted The hot spot factor H is assumed to be 1.1. For the ONAN
curve at a 5% ratio is 315◦ C. The fire point at the 5% ratio of the transformer up to 2500 kVA, the average liquid temperature
first part is 340◦ C, which is significantly higher than the fitted rise above the ambient temperature may be considered as 80%
curve using 6%–10% ratios. The fire points at 5% ratio of the of the top liquid temperature rise. Thus, the average winding
17518695, 2022, 10, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.12402 by CochraneChina, Wiley Online Library on [13/06/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1908 WANG ET AL.
FIGURE 6 Hot spot temperature variations for the mineral oil and
The hot spot temperatures of both the mineral oil and retro-
natural ester transformers under the given over-load test curve
filled transformers reached their limits prior to those of the
top oil temperatures. After retrofilling with natural ester, it took
gradient (g) was calculated using the following formula: 130 min to reach the temperature limit under 1.5 times rated
load, which is 30% higher than when the same transformer is
g = Δ𝜃w − 0.8Δ𝜃o (7) filled with mineral oil. Therefore, the overload capacity of the
1.5 times load was improved by retrofilling. In addition, the
where Δ𝜃w represents the average winding temperature rise and overloading test pattern of SGCC is significantly difficult for
Δ𝜃o represents the top oil temperature rise. conventionally designed transformers, thus requiring a special
The calculated hot-spot temperatures are shown in Figure 6. design.
The highest hot spot temperatures of mineral oil and natu-
ral ester are 149.0◦ C and 167.8◦ C, respectively. The closed-cup
flash point of the natural ester after retrofilling is 209◦ C, which 4.2 Prediction of mineral oil mass
is significantly higher than the hot spot temperature of 167.8◦ C. percentage
However, the closed cup flash point of mineral oil is 140◦ C,
and the hot spot temperature is 9.0◦ C higher than the closed Because the kinematic viscosity at 60◦ C has a good linearity with
cup flash point, which can cause danger during the overload respect to the mass ratio of mineral oil, it is possible to predict
test. This indicates that retrofilling with natural ester can signif- the mass ratio of mineral oil in the retrofilled transformers after
icantly improve the fire resistance of the transformer. In addi- retrofilling with natural ester.
tion, a specially designed mineral oil transformer is required for The prediction results of the residual mineral oil content
an overload test. An overly rigorous overload test required by using the kinematic viscosity are shown in Figure 7. The pre-
SGCC was performed. diction uses prediction bands at the 95% confidence level. The
Retrofilling with a natural ester liquid can improve the over- red bands are the prediction bands, thus the provided kinematic
load capacity of a conventionally designed mineral oil trans- viscosity at 60◦ C has a 95% confidence in the prediction bands.
former. The durations in which the temperatures of the top oil For the S11-M-315/10 transformer, the kinematic viscosity
and the hot spot reached the required limits in IEC 60076–7 at 60◦ C is 18.31 cSt. The prediction result of the mass ratio of
and IEC 60076-14, respectively, with a rated load of 1.5 were residual mineral oil using kinematic viscosity at 60◦ C is 0.53% to
calculated. The duration was chosen as the closest value, and 1.96% at a 95% confidence level, with an average level of 1.24%.
the results are listed in Table 7. For the S13-M-400/10 transformer, the kinematic viscosity at
TABLE 7 Overload capacity of the 1.5 times rated load before and after retrofilling
a
Limits of mineral oil required in IEC 60076-7 and limits of retrofilled transformer required in IEC 60076-14.
17518695, 2022, 10, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.12402 by CochraneChina, Wiley Online Library on [13/06/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WANG ET AL. 1909
60◦ C is 18.12 cSt. The prediction result of the mass ratio of cates that a specially designed mineral oil transformer cannot
residual mineral oil using kinematic viscosity at 60◦ C is 1.39%– fulfil the severe overloading pattern of SGCC, even with retro-
2.75% at a 95% confidence level, with an average level of 2.05%. filling. Thus, transformers with a high overload capacity need
The fire points of the S11-M-315/10 and S13-M-400/10 more specific designs.
transformers were 335◦ C and 338◦ C, respectively. Thus, accord- After retrofilling with natural ester, it took 130 min to reach
ing to Equation (2), the mass ratios of the two transformers the temperature limits under 1.5 times rated load, and the dura-
were 4.7% and 4.5%, respectively. A similar result can be cal- tion was 30% longer than when the same transformer was filled
culated by the flash point according to Equations (4) and (5) for with mineral oil. The overload capacity of the 1.5 times load can
the two transformers by 3.9% and 4.3%, respectively. therefore be improved by retrofilling.
Owing to the low linearity and piecewise equation of fire
point and flash point, it is not recommended to predict the ACKNOWLEDGEMENTS
mass ratio of residual mineral oil using fire points and flash The authors would like to express their gratitude to Dong Han
points, but to judge whether the insulating oil meets the K-class of Xian Xibian Zhong Te Electric CO, Ltd. and Bin Wei of State
less-flammable requirements or not. The insulating oil of two Grid Shaanxi Electric Power Company for their technical sup-
retrofilled transformers remain a K-class less-flammable liquid. port in this study.
Predictions using the prediction bands at a 95% confidence
level for kinematic viscosity provided the most favourable CONFLICT OF INTEREST
results. The prediction results of the residual mineral oil mass The authors declare no conflict of interest.
ratio after retrofilling were 1.24% for the S11-M-315/10 trans-
former and 2.05% for the S13-M-400/10 transformer. This DATA AVAILABILITY STATEMENT
mass ratio of residual mineral oil is significantly lower than the The data that support the findings of this study are available
7% expected residual mineral oil from [1], which should be from the corresponding author upon reasonable request.
attributed to the detailed retrofilling guidance presented in this
study. ORCID
Yuan Wang https://orcid.org/0000-0003-3587-2493
5 CONCLUSION REFERENCES
1. McShane, C.P., Luksich, J. & Rapp, K.J.: Retrofilling aging transformers
Detailed procedures for retrofilling 10 kV distribution trans- with natural ester based dielectric coolant for safety and life extension. In:
formers with natural esters were described in this study. A Cement Industry Technical Conference, TX, US, 4–9 May 2003
method to predict the residual mineral oil content after retro- 2. Pillai R., Havaldar F., Chitnis C.: Natural esters for life and capacity
enhancement of distribution transformers. CIRED - Open Access Pro-
filling mineral oil transformers with natural esters was proposed ceedings Journal. 2017(1), 355–358 (2017)
using kinematic viscosity at 60◦ C. This method addresses the 3. Zheng, Z.Y., Zhang, J.Q., et al.: Performance change analysis of replacing
issue of testing residual mineral oil content. The two retrofilled natural ester insulating oil with mineral insulating oil distribution trans-
transformers had mass ratios of residual mineral oil of 1.24% former. Transformer 56(6), 27–30 (2019)
for the S11-M-315/10 transformer and 2.05% for the S13-M- 4. Liao, R.J., et al.: A comparative study of thermal aging of transformer insu-
lation paper impregnated in natural ester and in mineral oil. Eur. Trans.
400/10 transformer. The mass ratio of mineral oil was believed Electr. Power 20(4), 518–533 (2010)
to be approximately 7% from previous studies. 5. Hosier, I.L., et al.: Aging of biodegradable oils and assessment of their
For the 315 and 400 kVA retrofilled transformers, the tem- suitability for high voltage applications. IEEE Trans. Dielectr. Electr. Insul.
perature rises at rated load of top oil increased by 4.1 and 5.0 18(3), 728–738 (2011)
K, average oil by 3.3 and 4.0 K, and low voltage windings by 7.8 6. Yu, H., et al.: Dielectric and physicochemical properties of mineral and
vegetable oils mixtures. In: IEEE International Conference on Dielectric
and 8.8 K, respectively, compared with mineral oil transform- Liquids, Manchester, UK, 25–29 June 2017
ers. According to the IEC 60076-14 standard, the thermal class 7. IEC 61039 : Classification of insulating liquids. IEC (2008)
of the oil-paper insulation system can be improved by chang- 8. Stockton, D.P., Bland, J.R., et al.: Seed-oil-based coolants for transformers.
ing the oil from mineral oil to natural ester, thus resulting in IEEE Ind. Appl. Mag. 15(1), 68–74 (2008)
the temperature rise limits of the top oil and the average wind- 9. Edmund, L., et al.: Cargill-sustainable electrical energy using natural ester.
In: 2015 Transformer Life Management (TLM) International Conference
ings for the natural ester-Kraft paper system to reach 90 and 75 Shanghai, Shanghai, China, November, 2015
K, respectively. Thus, the obtained temperatures using the tra- 10. Huang, Z.Q., Wang, R.F., et al.: Test comparison study on a natural ester
ditional temperature rise test can meet the limits of retrofilling. retro-filled 220kV power transformer. In: IEEE International Confer-
Retrofilling with natural ester can significantly improve the ence on High Voltage Engineering and Application, Beijing, China, 6–10
fire resistance of a mineral oil transformer. The results of the September 2020
11. IEEE C57:147: IEEE guide for acceptance and maintenance of natural
special overload test of the 400 kVA transformer show that ester fluids in transformers. IEEE (2008)
the highest hot spot temperature of mineral oil was 149.0◦ C, 12. Asano, R., Page, S.A.: Reducing environmental impact and improving
which is 9.0◦ C higher than that of the closed cup flash point, safety and performance of power transformers with natural ester dielec-
causing danger during the overload test. The closed-cup flash tric insulating fluids. IEEE Trans. Ind. Appl. 50(1), 134–141 (2013)
point of the natural ester after retrofilling is 209◦ C, which is 13. Josken, J., Wareham, D.: Seed based oil as an alternative to mineral oil. In:
Rural Electric Power Conference, Scottsdale, AZ, 25–25 May, 2004
significantly higher than the hot spot temperature. This indi-
17518695, 2022, 10, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.12402 by CochraneChina, Wiley Online Library on [13/06/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1910 WANG ET AL.
14. Fofana, I., Wasserberg, V., Borsi, H., Gockenbach, E.: Preliminary investi- 37. IEC 60599 : Mineral oil-filled electrical equipment in service—Guidance
gations for the retrofilling of perchlorethylene based fluid filled transform- on the interpretation of dissolved and free gases analysis. IEC (2015)
ers. IEEE Trans. Dielectr. Electr. Insul. 9(1), 97–103 (2002) 38. Hiramatsu, Y., Kamidani, K., Muramoto, Y.: Effect of water on AC break-
15. Fofana, I., Borsi, H., Gockenbach, E.: Oil filled transformer retrofilled with down properties of vegetable-oil-based insulating fluid mixed with mineral
ester liquid—Facts and arguments. In: 15th International Symposium on oil. In: Proceeding International Symposium Electrical Insulation Materi-
High-Voltage Engineering. ISH, Ljubljana, Slovenia, August 2007 als, Toyohashi, Japan, 11–15 September 2017
16. McShane, C.P., et al.: Aging of paper insulation retrofilled with natural ester 39. Boris, H., et al.: Dielectric behaviour of silicone and ester fluids for use in
dielectric fluid. In: 2003 Annual Report Conference Electrical Insulation distribution transformers. IEEE Trans. Dielectr. Electr. Insul. 26(4), 755–
Dielectric Phenomena CEIDP, Albuquerque, NM, 19–22 October 2003 762 (1991)
17. McShane, C.P., et al.: Natural ester dielectric fluid development. In:
2005/2006 IEEE/PES Transmission Distribution Conference Exhibition,
Dallas, TX, 21–24 May 2006
18. McShane, C.P., et al.: Some considerations for new and retrofil applications
of natural ester dielectric fluids in medium and large power transformers. How to cite this article: Wang, Y., Wang, R., Pan, K.,
In: 2005/2006 IEEE/PES Transmission and Distribution Conference and Xu, Y., Rapp, K.: Detailed procedures of retrofilling
Exhibition, Dallas, May 2006 transformers with FR3 natural ester and residual mineral
19. Moore, S., Kevin, R., Ramona, B.: Transformer insulation dry out as a
oil content testing. IET Gener. Transm. Distrib. 16,
result of retrofilling with natural ester fluid. In: PES Transmission Dis-
tribution Conference Exhibition 2012, Orlando, 21–24 May, 2012 1901–1913 (2022). https://doi.org/10.1049/gtd2.12402
20. Pillai, R., et al.: DGA of natural ester filled transformers: Experience
with retrofilled and new transformers. In: IEEE International Conference
Dielectric Liquids, Manchester, UK, 25–29 June 2017
21. Murphy, J.R., Graham, J.: Distribution utility experience with natural ester
dielectric coolants. In: IEEE Power Energy Society General Meeting, Cal- APPENDIX A
gary, Canada, 26–30 July 2009 Table A1 presents the requirements of retrofilled transformer
22. Shinde, R.: Condition monitoring of a retro-filled power transformer by inspection at the beginning and ending of the retrofill. Figure A1
natural ester Envirotemp FR3 fluid. In: International Conference Cond.
shows the flow chart of retrofilling transformer with FR3 nat-
Assessment Techniques Electrical Systems, Rupnaggar, Punjab, India, 16–
18 November 2017 ural ester. Figures A2 and A3 shows dissolved gas content of
23. Santisteban, A., et al.: Thermal analysis of natural esters in a low-voltage S13-M-400/10 transformer before and after retrofilling.
disc-type winding of a power transformer. In: IEEE International Confer- There are four main parts in the retrofilling procedures: (1)
ence Dielectric Liquids, Manchester, UK, 25–29 June 2017 Preparation before retrofilling; (2) draining oil procedures. (3)
24. Lee, B., Jeong, J., Song, I.: The characteristics of winding temperature for
flush procedures. (4) retrofill procedures.
the natural ester filled transformer up to and including 500 kVA. In: Annual
Report Conference Electric Insulation Dielectric Phenomena, Quebec, In the first procedure ‘preparation before retrofilling’, inspec-
Canada, 26–29 October 2008 tions and test items of transformer in Table A1 should be
25. Smith, S.D., Barry, L.B.: Design and test experience with natural ester fluid inspected and tested and the results should meet the require-
for power transformers update. In: 2009 IEEE Power Energy Society ments of indicated standard. The ambient temperature of
General Meeting, AB, Canada, 26–30 July 2009
approximately 20◦ C and relative humidity of not higher than
26. Yang, T., et al.: Feasibility of directly changing natural ester insulating oil for
conventional mineral insulating oil-filled distribution transformer. Insul. 60% are required. The gas should be released for transformers
Mater. 51(2), 39–43 (2008) with gas relay. Oil should be drained for transformers with an oil
27. Frimpong, G.K., Oommen, T.V., Asano, R.: A survey of aging character- conservator. Valve and drain plug should be opened before and
istics of cellulose insulation in natural ester and mineral oil. IEEE Electr. after draining oil for transformers with butterfly valve. These
Insul. Mag. 27(5), 36–48 (2011)
additional preparations are necessary for different transformer
28. Wang, R.F., et al.: Study on load performance of distribution transformer
before/after filling vegetable insulating oil instead of mineral oil. Trans- constructions to ensure a successful retrofill.
former 56(4), 78–80 (2019) In the second procedure ‘draining oil procedures’, oil should
29. Zhao, Y.H., Qian, Y.H., et al.: In-service ageing comparison study of natu- be drained from the oil vent valve for transformers with oil vent
ral ester and mineral oil filled distribution transformers. In: IEEE Interna- valve, or from the oil level gauge for transformers without oil
tional Conference Dielectric Liquids, Roma, Italy, 23–27 June 2019
vent valve. Note that 1–2 h waiting is valuable. Sufficient waiting
30. Scatiggio, F., Pepe, F., et al.: Increased loadability of transformers
immersed in natural ester. In: IEEE International Conference Dielectric can reduce residual mineral oil after retrofilling. After waiting,
Liquids, Roma, Italy, 23–27 June 2019 the residual oil under the tank should be drained through the
31. IEC 60076-2: Power transformers—Part 2: Temperature rise for liquid- drain valve at the bottom of oil tank, otherwise a suitable angle
immersed transformers. IEC (2011) is necessary to reduce the residual mineral oil.
32. Mazzaro, M., et al.: Fire simulation tests of mineral oil and natural
In the third procedure ‘flush procedures’, if the transformer
esters transformers. In: IEEE International Conference Dielectric Liquids,
Roma, Italy, 23–27 June 2019 cannot be flushed and retrofilled at once after the draining oil
33. IEC 60076-14: Power transformers—Part 14: Liquid-immersed power procedures, the transformer should be filled with dry nitrogen
transformer using high-temperature insulation materials. IEC (2013) gas to cut off with moisture and oxygen in the air. Flush the
34. IEC 60422: Mineral insulating oils in electrical equipment—Supervision windings, core, and oil tank internal surface with natural ester.
and maintenance guidance. IEC (2013)
Then, another hour’s waiting can reduce the oil generated by
35. IEC 62770: Fluids for electrotechnical applications—Unused natural
esters for transformers and similar electrical equipment. IEC (2013) flushing.
36. Robert, C.B., et al.: Evaluation of natural ester retrofilled transformers after In the fourth procedures ‘retrofill procedures’, the trans-
one year of continuous overload. In: IEEE Electrical Insulation Confer- former should be retrofilled with the natural ester to the bot-
ence, Calgary, Canada, 16–19 June 2019 tom. Again, the inspections and test items in Table A1 should
17518695, 2022, 10, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.12402 by CochraneChina, Wiley Online Library on [13/06/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WANG ET AL. 1911
a
The applied voltage during the high voltage test is 80% of the standard voltage.
b
The applied voltage during the high voltage test is 80%-100% of the standard voltage.
Dissolved gas content of the S13-M-400/10 transformer filled with the natural ester (after retrofilling)
Dissolved gas content of the S13-M-400/10 transformer filled with mineral oil (before retrofilling)
FIGURE A2
FIGURE A3
WANG ET AL.