LOW VOLTAGE WORK BOQ

AS PER ORDER
S. No. DESCRIPTION OF ITEM Quantity Unit Rate Amount

Note - Pl refer EPC Tender for List of Makes and Technical Specification.

(A) DATA NETWORKING/ IPBX/ CCTV (ACTIVE COMPONENT)

1.0 Supply, Installation, Testing and Comissioning of IP Based Central IPABX as per technical specifications to be supplied. It should be of initially capacity of 2000
Telephones & expandable up to 10000 telephones shall be located at a central location in the Hospital OPD block at PDDU-UHS-Karnal. All the Telephone in the
Complex will be IP Based and will use the existing LAN Network for the communication within the complex as well as for outside the complex. All Rack Panels of 1 Set
Individual buildings shall be connected to Central EPABX system through Optical Fiber Cableand complience of detail tender specification.

2.0 Supply, Installation, Testing and Comissioning of Type 4 IP Phone . Should be an integrated system with at least 22 to 24 inch LCD/TFT screen,1080P resolution
(16:9), HD camera and with speakers for wide band audio output. The Codec should be a part of the unit. No separate Codec's are preferred. The LCD/TFT screen
should be a touch screen to provide a touch interface to the user as per detail tender specification. To be used for President, Director, Medical Superintendent, Dean, 6 Each
Principal, Auditorium Conference Room, etc.

3.0 Supply, Installation, Testing and Comissioning of Type 3 IP Phone . The phone should support Power over Ethernet IEEE 802.3af class 1/2/3 and should also have
AC power adapter option The phone should have 2 x 1GE ports, one for the LAN connection and the other for connecting to PC/laptop as per detail tender 6 Each
specification. To be used for HODs, Chairman, Conference Room etc.

4.0 Supply, Installation, Testing and Comissioning of Type 2 IP Phone - The phone should have two Ethernet ports of at least 10/100/1000 BASE-T Ethernet ports, one
for the LAN connection and the other for connecting to PC/laptop as per detail tender specification. To be used for Security room, Server Room, Fire Control Room, 797 Each
etc.

5.0 Supply, Installation, Testing & Commissioning of Router should be a modular aggregation platform. It should support broadband aggregation for voice, video, data,
and mobility services with QoS scaling to a large number of queues per device. Router should have 8 nos. of 10/100/1000 Base-T ports and 4 nos. SFP based ports.
Router should have at least 1 open slots for additional LAN/ WAN modules other then asked ports. Router should have 4x10 Gigabit SFP+ ports from day 1, Router
should have minimum 4 GB RAM from day 1. Router should have DES, 3DES and AES Standards through dedicated encryption module/processor. Should support
IPSec with IKEv2 and Suite-B Encryption, Router shall have hot swappable 1:1 redundant internal power supply, Router should have a minimum performance of 15
Mpps and 10 Gbps of bandwidth, Scalable to 20 Gbs in future. Router should support static Routes, OSPFv2, OSPFv3, BGP4, MBGP, BFD, Policy based routing, 2 Each
IPv4 and IPv6 tunneling, MPLS LDP, MPLS L3VPN, MPLS L2VPN , MPLS TE, FRR Link & Node Protection, LDP, MPLS Static label, MPLS VRF-aware static
labels, LDP - Session Protection, LDP - Graceful Restart, MPLS L2VPN Pseudo wire Redundancy with TE/FRR protection, Support for QinQ to Ethernet/VLAN
Ethernet/IP interworking, MPLS VPN -Carrier Supporting Carrier (CsC), CsC with IPv4 BGP label distribution (RFC 3107) as per technical specifications.

6.0 Supply, Installation, Testing & Commissioning of Core Switch - The proposed Switch should be a chassis based and have minimum 8 interface slots and 1
supervisor engine and 2 power supply. Switch should have 24 X 1/10G SFP+ Ports, 24 x 1G/10G Base-T RJ45 and 16 x 40 Gig QSFP+ (for switch to switch inter
connectivity) ports spread across two cards. 24 Nos. of single mode LR transceivers should be populated from day 1. Switch should have minimum 1.2 TB per
interface slot throughput & 950 Mpps forwarding rate on Day 1. Switch should be scalable to support additional 192 x 10G Ports or 128 x 40G Ports or 48 x100G
Ports at line rate performance. The proposed line-cards must have non-blocking and wire-speed performance for all packet sizes for IPv4 & IPv6 traffic and should
have distributed forwarding architecture. It Should have redundant and replaceable Supervisor / CPU, Management Modules, Replaceable Fabric Modules/ Power
Supply and Fans to provide full redundancy and high availability. The performance of the switch should not degrade in case of any failure. Chassis should support
100G interface line-cards for future connectivity requirement without any replacement in hardware configuration. Switch should have IPv4 & IPv6 static routes,
OSPF, OSPFv3, PBR, PIM-SM / DM, BGP, VRF and SDN. Should support Layer 2 protocols 802.1d, 802.1s, 802.1w and 802.3ad. Switch should support minimum 2 Each
8 hardware queues per port for applying various traffic prioritizations through QoS. Switch should support minimum 2K ACL's, minimum 2K/4K Multicast and 200K
Unicast Routes for IPv4 and IPv6. Should support Port Security and RADIUS / TACACS+ integration. Should be upgradable to support Open Flow or equivalent
functionality, to support SDN (Software Defined Networking). The SDN functionality shall be native to switch. Should have NetFlow/sflow functionality for traffic
monitoring. The proposed switch should be IPv6 logo certified. Should have compatibility to work in atmospheric tempemperature range -5 degree C to 50 degree C.
7.0 Supply, Installation, Testing & Commissioning of Distribution Switch - Switch should support 40 Gbps of stacking bandwidth, Should have compatibility to work in
atmospheric tempemperature range -5 degree C to 50 degree C. Switch ports should be populated with 24 x 1G loaded with 12 x Multi Mode (SX) transceiver for
access layer uplinks & with 4x10G Single Mode Transceivers (LR) for core layer and distribution ring uplinks from day 1. The proposed interfaces must have non-
blocking and wire-speed performance for all packet sizes for IPv4 & IPv6 traffic and should have distributed forwarding architecture. Should be supplied with hot
swappable redundant internal Power Supply. Switch should have dedicated 1 x 10/100/1000 Base T port for Out of band Management port. Switch should have IPv4
& IPv6 static routes and support for OSPF, Should support Layer 2 protocols 802.1d, 802.1s, 802.1w and 802.3ad & RFC 3619/G.8032 for sub 50ms failover, Switch
should support minimum 8 hardware queues per port for applying various traffic prioritization through QoS. Switch should support SP Queuing, minimum 1K ACL's,
2K/4K Multicast and WRED/WTD. Network OS, 400 Unicast Routes, IPv4 and IPv6 compliant. Should support Port Security and RADIUS / TACACS integration. 2 Each
Should be upgradable to support Open Flow or equivalent functionality, to support SDN (Software Defined Networking). Switch should support port security, DHCP
snooping, Dynamic ARP inspection, IP Source guard, BPDU Guard, Spanning tree root guard. IPv6 RA guard Should have MAC security – Lockdown & Limit and
MAC address tracking with syslog & SNMP notification, Multicast traceroute. Should support NetFlow/sflow functionality for traffic monitoring. The proposed switch
should be IPv6 logo certified. Desirable: EAL2 / NDPP / NDcPP certification. Should have direct OEM 24x7x365 TAC support and Advanced hardware replacement
warranty.

8.0 Supply, Installation, Testing & Commissioning of 24 Port POE+ Access Switches - Should have minimum 24 x 10/100/1000 BaseTPoE/PoE+ RJ45 Ports (minimum
370W) plus 2x 1/10G BaseX SFP+ Ports populated with 2 nos 1G (SX) SFP. Switch would use 1G uplinks on day 1 and be upgradable to 10G operations in future.
Should have dedicated 40 Gbps of stacking bandwidth proposed with stacking cable. Stacking should support upto 8 Stacking members. Switch should have
dedicated 1 x 10/100/1000 BaseT port for Out of band Management port. Should have compatibility to work in atmospheric temperature range -5 degree C to 50
degree C. Switch should support External/Internal Redundant Power Supply, The proposed interfaces must have non-blocking and wire-speed performance for all
packet sizes for IPv4 & IPv6 traffic and should have distributed forwarding architecture. Should support Layer 2 protocols IEEE 802.1s, 802.1w, 802.3ad, 802.1x,
802.1p, 802.1Q, 802.3, 802.3u, 802.3ab, 802.3z & RFC 3619/G.8032 for sub 50ms failover, Switch should have IPv4 & IPv6 static routes from day 1. Switch should
have minimum 1K ACL‘s and 500 IPv4 and IPv6 multicast groups. Switch should support minimum 8 hardware queues per port for applying various traffic
prioritization through QoS. Switch should support SP Queuing and WRED/WTD. Should support 802.1x authentication, Port Security and RADIUS / TACACS 15 Each
integration. Should have MAC security – Lockdown & Limit and MAC address tracking with syslog & snmp notification, Multicast traceroute. Should be upgradable to
support OpenFlow or equivalent functionality, to support SDN (Software Defined Networking). Should have NetFlow / sFlow/ Equivalent functionality for traffic
monitoring. Switch should support port security, DHCP snooping, Dynamic ARP inspection, IP Source guard, BPDU Guard, Spanning tree root guard and IPv6 First
Hop Security. The proposed switch should be IPv6 logo certified. Should have EAL2/ NDPP/NDcPP certification from Day 1. Should have direct OEM 24x7x365 TAC
support with software update and NBD Advanced hardware replacement warranty.

9.0 Supply, Installation, Testing & Commissioning of 24 Port Access Switches - Should have minimum 24 x 10/100/1000 BaseT RJ45 Ports plus 2x 1/10G BaseX SFP+
Ports populated with 2 nos 1G (SX) SFP. Switch would use 1G uplinks on day 1 and be upgradable to 10G operations in future. Should have dedicated 40 Gbps of
stacking bandwidth proposed with stacking cable. Stacking should support upto 8 Stacking members. Switch should have dedicated 1 x 10/100/1000 BaseT port for
Out of band Management port. Should have compatibility to work in atmospheric temperature range -5 degree C to 50 degree C. Switch should support
External/Internal Redundant Power Supply, The proposed interfaces must have non-blocking and wire-speed performance for all packet sizes for IPv4 & IPv6 traffic
and should have distributed forwarding architecture. Should support Layer 2 protocols IEEE 802.1s, 802.1w, 802.3ad, 802.1x, 802.1p, 802.1Q, 802.3, 802.3u,
802.3ab, 802.3z & RFC 3619/G.8032 for sub 50ms failover, Switch should have IPv4 & IPv6 static routes from day 1. Switch should have minimum 1K ACL‘s and
500 IPv4 and IPv6 multicast groups. Switch should support minimum 8 hardware queues per port for applying various traffic prioritization through QoS. Switch should
support SP Queuing and WRED/WTD. Should support 802.1x authentication, Port Security and RADIUS / TACACS integration. Should have MAC security – 7 Each
Lockdown & Limit and MAC address tracking with syslog & snmp notification, Multicast traceroute. Should be upgradable to support OpenFlow or equivalent
functionality, to support SDN (Software Defined Networking). Should have NetFlow / sFlow/ Equivalent functionality for traffic monitoring. Switch should support port
security, DHCP snooping, Dynamic ARP inspection, IP Source guard, BPDU Guard, Spanning tree root guard and IPv6 First Hop Security. The proposed switch
should be IPv6 logo certified. Should have EAL2/ NDPP/NDcPP certification from Day 1. Should have direct OEM 24x7x365 TAC support with software update and
NBD Advanced hardware replacement warranty.

10.0 Supply, Installation, Testing & Commissioning of 48 Port POE+ Access Switches - Should have minimum 48 X 10/100/1000 BaseT PoE/PoE+ RJ45 Ports (minimum
740W) plus 2x 1/10G BaseX SFP+ Ports populated with 2 nos 1G (SX) SFP. Switch would use 1G uplinks on day 1 and be upgradable to 10G operations in future.
Should have 40 Gbps of stacking bandwidth proposed with stacking cable. Stacking should support upto 8 Stacking members, Should have compatibility to work in
atmospheric tempemperature range -5 degree C to 50 degree C. Switch should support External/Internal Redundant Power Supply, Switch should have dedicated 1
x 10/100/1000 Base T port for Out of band Management port. The proposed interfaces must have non-blocking and wire-speed performance for all packet sizes for
IPv4 & IPv6 traffic and should have distributed forwarding architecture. Should support Layer 2 protocols IEEE 802.1s, 802.1w, 802.3ad, 802.1x, 802.1p, 802.1Q,
802.3, 802.3u, 802.3ab, 802.3z & RFC 3619/G.8032 for sub 50ms failover, Switch should have IPv4 & IPv6 static routes from day 1, Switch should have minimum
1K ACL‘s and 500 IPv4 and IPv6 multicast groups. Switch should support minimum 8 hardware queues per port for applying various traffic prioritization through QoS.
Switch should support SP Queuing and WRED/WTD, Should support 802.1 X authentication, Port Security and RADIUS / TACACS integration, Should have MAC 32 Each
security – Lockdown & Limit and MAC address tracking with syslog & SNMP notification, Multicast traceroute. Should be upgradable to support Open Flow or
equivalent functionality, to support SDN (Software Defined Networking). Should have NetFlow / sFlow/equivalent functionality for traffic monitoring. Switch should
support port security, DHCP snooping, Dynamic ARP inspection, IP Source guard, BPDU Guard, Spanning tree root guard and IPv6 First Hop Security. The
proposed switch should be IPv6 logo certified. Should have EAL2/ NDPP/NDcPP certification from Day 1. Should have direct OEM 24x7x365 TAC support with
software update and NBD Advanced hardware replacement warranty.
11.0 Supply, Installation, Testing & Commissioning of 48 Port Non PoE Access Switches - Should have minimum 48 X 10/100/1000 BaseT RJ45 Ports plus 2x 1/10G
BaseX SFP+ Ports populated with 2 nos 1G (SX) SFP. Switch would use 1G uplinks on day 1 and be upgradable to 10G operations in future. Should have dedicated
40 Gbps of stacking bandwidth proposed with stacking cable. Stacking should support upto 8 Stacking members. Switch should have dedicated 1 x 10/100/1000
BaseT port for Out of band Management port. Should have compatibility to work in atmospheric temperature range -5 degree C to 50 degree C. Switch should
support External/Internal Redundant Power Supply, The proposed interfaces must have non-blocking and wire-speed performance for all packet sizes for IPv4 &
IPv6 traffic and should have distributed forwarding architecture. Should support Layer 2 protocols IEEE 802.1s, 802.1w, 802.3ad, 802.1x, 802.1p, 802.1Q, 802.3,
802.3u, 802.3ab, 802.3z & RFC 3619/G.8032 for sub 50ms failover. Switch should have IPv4 & IPv6 static routes from day 1. Switch should have minimum 1K ACL‘s
and 500 IPv4 and IPv6 multicast groups. Switch should support minimum 8 hardware queues per port for applying various traffic prioritizations through QoS. Switch
should support SP Queuing and WRED/WTD. Should support 802.1x authentication, Port Security and RADIUS / TACACS integration. Should have MAC security – 30 Each
Lockdown & Limit and MAC address tracking with syslog & snmp notification, Multicast traceroute. Should be upgradable to support Open Flow or equivalent
functionality, to support SDN (Software Defined Networking). Should have NetFlow / sFlow/Equivalent functionality for traffic monitoring. Switch should support port
security, DHCP snooping, Dynamic ARP inspection, IP Source guard, BPDU Guard, Spanning tree root guard and IPv6 First Hop Security. The proposed switch
should be IPv6 logo certified. Should have EAL2/ NDPP/NDcPP certification from Day 1. Should have direct OEM 24x7x365 TAC support with software update and
NBD Advanced hardware replacement warranty.

12.0 Supply, Installation, Testing & Commissioning of 10G fiber Modules. 40 Each

13.0 Supply, Installation, Testing & Commissioning of Firewall - The UTM solution should be Hardware based, Reliable, purpose-built security appliance with hardened
operating system that eliminates the security risks associated with general-purpose operating systems. It Should support 1:1 high availability. It Should have
minimum 6 x 10G supporting SFP+ interfaces & 4 x 100/1000/10 BaseT RJ45 ports to cater to connectivity from multiple service providers and load balance them.
The Firewall should have ultra-low latency (~ < 5 micro seconds). The Firewall should support IPSEC & SSL VPN, inbound and outbound both. The IPSEC VPN
should deliver at least 20 Gbps throughput to ensure connectivity with Multiple colleges / University catering to Data / Voice traffic over IPSEC tunnel. The Firewall
should be able to handle very high concurrent sessions like 20 Million or above and at least 400,000 of new sessions per second. The solution should support
Virtualization with 10 Virtual contexts scalable to 250 to help University use the logical Firewalls for internal / student projects run isolated with each other. The
proposed solution should have integrated IPS module with at least 10Gbps of throughput for deep pack inspection of traffic and also should be able to inspect
encrypted SSL traffic. The solution should have at least 5 Gbps of Threat Protection throughput and the so that the entire traffic is scanned before reaching the end 2 Each
user. The antivirus engine should be able to inspect the encrypted traffic like HTTPS, SMTPS, POP3s , IMAPs, FTPs etc. The proposed system should have
integrated Web Content Filtering solution which can be used to block any unwanted sites / category of sites to adhere to University IT guidelines. The Firewall &
IPSEC VPN module shall belong to product family which minimally attain Internet Computer Security Association (ICSA) Certification or equivalent. The proposed
system should have modules / Licenses for integrated Web Content Filtering along with IPS, Application Control, Antivirus / Malware Protection & Anti spam.
Proposed solution should be an Appliance/Virtual Machine based solution. In case of Virtual Machine based, required server must be quoted by bidder. It Should
have direct OEM TAC support.

14.0 Supply, Installation, Testing & Commissioning of AAA Server - Proposed AAA solution should be an Appliance based solution. Proposed solution must support
integration and security for both wired and wireless infrastructure. It should be ready to handle 7000 concurrent Devices from day1 and scalable for up to 12000 end
systems. Devices are mixture of guest users, institute staff, machine endpoints. AAA should support BYOD with Self-service authorization and device provisioning
via open network. It must allow for Machine Authentication (or an appropriate alternative) by AD-joined Windows laptops/tablets allowing wireless connection before
user login. The Solution should have detailed reporting capabilities for historical & real time data. Should be equipped with custom report designer to meet the need
of specific data attributes and periodic email of the same to relevant administrative team. The proposed solution should have Built-in user database with per
device/user credential management and should also provide Seamless backend integration with RADIUS, AD, LDAP. Solution should support agentless and agent-
based assessment to reduce security vulnerabilities with End system Posture assessment. Proposed solution should address (but not limited to) the below 1 Each
requirements: Intuitive user/device management and Unified device visibility and reporting Self-service 802.1X and guest access. Should also have option for MAC
authentication for selective devices and Social Login. Integrated AAA server with key policy definitions. Should also support integration with external AAA server.
AAA should be able to integrate with existing user databases like Microsoft AD/LDAP/local. It should be scalable to enforce device-specific settings for antivirus,
firewall and OS patches, passcodes, NAC, proxies. It should be able to enforce custom user and device privileges. It should have direct OEM 24x7 TAC support with
software upgrade and NBD Advanced hardware replacement warranty.
15.0 Supply, Installation, Testing and Comissioning of Indoor AP's - Wall/Ceiling mounted Wi-Fi access-point suitable for indoor use with at least 2 10/100/1000Mbps
Ethernet ports supporting standard 802.3af/at POE+. 802.11ac AP should operate in 2.4 GHz (450 Mbps or more) and 5 GHz simultaneously and capable of
minimum 1.7Gbps on 5 Ghz for 802.11ac clients supporting minimum4x4 MIMO with 4 spatial streams. It must support minimum 3 concurrent MU-MIMO users.
Should support minimum 16x BSSID per AP. Should have compatibility to work in atmospheric temperature range -5 degree C to 50 degree C. Must have an
dynamic or smart RF Management features which allows WLAN to automatically and intelligently adapt to changes in the RF environment. The access point should
support captive portal and local data base for authentication. Maximum conducted transmit power shall be 24.7 dBm on both 2.4 and 5 GHz with two antennas and
EIRP complying to regulatory requirements. The External antenna gain proposed should be minimum 8 dBi or above on both the bands. Should support 20,40 and
80 MHz Channels. AP should support band steering and load balance across bands and AP's. The access point or the controller should be capable of running a
local DHCP Server. Security mechanisms should be in place to protect the communication between the Access Point controller and the Access Points. Access points
must support a "controllerless" mode where one AP will provide full RF and network management. The access point should support WPA2 enterprise authentication 516 Each
and AES/CCMP encryption. WLAN solution must support personal and enterprise WPA2 authentication for a staff WLAN concurrent with open access public WLAN.
AP should support 802.11k for Radios Resource management and 802.11r for fast roaming. Implement Wi-Fi alliance standards WMM, 802.11d, 802.11h and
802.11e and should support VoWLAN. AP must support L7 Application Identification and spectrum analysis functions. AP should support Minimum -90dB Receiving
sensitivity. AP should support Receiver sensitivity Threshold to reduce noise reception in the AP to increase SNR and performance, 802.11 a/b/g/n/ac wave 2
functionality certified, Wi-Fi alliance Should be approved & certified UL / cUL 60950-1, IEC / EN60950-1, UL2043, RoHS. FCC (USA), EU, TELEC, Medical EMC
standard: EN/IEC 60601-1-2. Should have direct OEM 24x7x365 TAC support with software update and NBD advanced hardware replacement warranty.

16.0 Supply, Installation, Testing and Comissioning of Outdoor AP's - Wall/Ceiling/Poll mounted Wi-fi access-point suitable for outdoor use with at least 1
10/100/1000Mbps Ethernet ports supporting standard 802.3af/at POE+. 802.11ac AP should operate in 2.4 GHz (450 Mbps or more) and 5 GHz simultaneously and
capable of minimum 1.3 Gbps on 5 Ghz for 802.11ac clients supporting minimum 3x3 MIMO with 3 spatial streams. It must support minimum 3 concurrent MU-MIMO
users. Should support minimum 16x BSSID per AP. Should have compatibility to work in atmospheric temperature range -5 degree C to 50 degree C. The access
point should be capable of performing security scanning and serving clients on the same radio. It should be also capable of performing RF analysis and security
scanning. Maximum conducted transmit power shall be 24.7 dBm on both 2.4 and 5 GHz with two antennas and EIRP complying to regulatory requirements. The
External antenna gain proposed should be minimum 8 dBi or above on both the bands. Should support 20,40 and 80 MHz Channels. AP should support band
steering and load balance across bands and AP's. The access point or the controller should be capable of running a local DHCP Server. Security mechanisms
should be in place to protect the communication between the Access Point controller and the Access Points. The access point should support WPA2 enterprise 2 Each
authentication and AES/CCMP encryption. AP should support 802.11k for Radios Resource management and 802.11r for fast roaming. Implement Wi-Fi alliance
standards WMM, 802.11d, 802.11h and 802.11e and should support VoWLAN. AP must support L7 Application Identification and spectrum analysis functions. AP
should support Minimum -90dB Receiving sensitivity. AP should support Receiver sensitivity Threshold to reduce noise reception in the AP to increase SNR and
performance. 802.11 a/b/g/n/ac wave 2 functionality certified by the Wi-Fi alliance, Should be IP67 rated and RF transmission power should be approved by WPC.
AP should support up to 100-mph sustained winds and up to 165-mph wind gusts. Should have direct OEM 24x7x365 TAC support with software update and NBD
advanced hardware replacement warranty.

17.0 Supply, Installation, Testing and Comissioning of Wireless LAN Controller - Must be compliant with IEEE CAPWAP for controller-based WLANs or equivalent feature
and it should be appliance based. WLC should support IPv4 and IPv6 including IEEE 802.11a, 802.11b, 802.11g, 802.11d, WMM/802.11e, 802.11n, 802.11ac
standards. WLAN Controller should have minimum 6x of 10/100/1000 Ethernet Ports, 2x USB port and one Console port. WLC should support up to 600 Access
points day 1 and up to 1000 Devices in a single chassis. Standalone controller should support seamless roaming access over L2/L3 network. Should be a dedicated
hardware based appliance with minimum 4 GB RAM and 32 GB storage space. Spinning Hard Drive must be avoided. There should be 100% redundancy for
Primary controller i.e. N: N including Hardware and desired licenses to support AP‘s, WLC should provide air-time fairness between these different speed clients –
slower clients should not be starved by the faster clients and faster clients should not adversely affected by slower clients. WLC Must support an ability to
dynamically adjust channel, power settings and airtime, based on the RF environment. WLC should support L2/L3 discovery for AP's. Should support adhere to the
strictest level of security standards, including 802.11i Wi-Fi Protected Access 2 (WPA2), WPA, 802.1X with multiple Extensible Authentication Protocol (EAP) and
802.1x Authentication. Controller should support WIDS/WIPS includes rogue AP detection, classification and automatic containment feature and prevention for DOS
attacks. WLC should support L2/L3/L4 Access Control and L2 Client Isolation so User cannot access each other‘s devices. Isolation should have option to apply on
AP or SSID's. Controller/System should support Access Control based on Identity/Role/ Device/Time or Application. Must support client roaming in L2/L3 networks
and also across controllers. Controller should support integrated or External AAA servers including Microsoft AD and Linux based open source AAA. The 2 Each
Controller/System should support L7 Application/OS/Device finger printing and device type based policies i.e allow or deny, Bandwidth rate limit, VLAN mapping.
Wireless Network should support deep packet inspection for all user traffic across Layer 4-7 network to analyses information about applications usage. The
controller/System should be able to raise critical alarms by sending an email and/ or SMS. Per SSID or dynamic Per user bandwidth Rate Limiting, Support advanced
multicast features and WMM support to provide best performance on Video applications and should have. Controller/System should have BYOD features and should
support integrated/ and external captive portal integration. System should provide a web-based application that allows non-technical staff to create Guest accounts
with validity for fixed duration like hours or days and restricted to number of devices. Password to guest should be shared over Email and SMS (SMS gateway
services shall be provided by Campus). Proposed solution should be an Appliance based solution. Should have direct OEM 24x7 TAC support with Software
upgrade and NBD Advanced hardware replacement warranty.
18.0 Supply, Installation, Testing and Comissioning of NMS - NMS shall be able to monitor and configure 500 devices (should be proposed against the proposed
devices) and should have scalability to manage up to 2000 devices in future. NMS shall be able to manage both wired (routing/switching) and wireless networks in
single pane of glass management. NMS should be scalable to provide Deep application visibility using AVC, NetFlow/Sflow, NBAR or packet inspection to recognize
a wide variety of applications and SNMP.NMS should be able to provide Network topology . NMS solution should deliver pinpoint visibility into who, what, when,
where, and how of wireless access through its own data collection and key integrations. It should support spatial / floor mapping; integrated location-based tracking
of client, Should provide a customizable at-a-glance summary of all discovered devices and existing network switches to proactively identify problem areas and help
prevent network downtime. The network has to be manageable at Network Operations Center (NOC) and through secured browser. Should be able to discover,
configure, monitor, manage, and deploy configurations to dynamically update groups of devices. Should allow flexible definitions of administrator roles and
responsibilities with RBAC (Role based Access Control) for different teams. Should enable performance management by providing customizable dashboards and 1 Each
historical data visibility, Should be able to generate reports designed to summarize utilization of and traffic patterns on network interfaces. Should allow
administrators to track device configuration changes, enabling viewing, retrieval, and restoration of configuration files, and monitoring of configuration drift for
troubleshooting purposes. The system design should provide access to only authorized users, RBAC and by using Secure Digital Certificates to completely trace
back an individual user, in case of Cyber Crime or any other cyber investigation, as per the Standard Computer Assets and Information Technology (CAIT) Policy.
Should have direct OEM 24x7x365 TAC support with software upgrade and NBD Advanced hardware replacement warranty.

19.0 Supply, Installation, Testing & Commissioning of Appliance based customised ITAM for asset inventory management with ability to map physical locations and exact
rack elevations for audit and support control. Appliance shall be Intel x86 based device with secure intranet server with Linux Based operating system and relational 1 Each
databases for long term storage. Appliance includes license upto 500 units under control.

(B) DATA NETWORKING/IPBX/CCTV (PASSIVE COMPONENT)

1.0 Supply, Installtion, Testing and Comissioning of CAT 6A UTP cable solid copper conductors as per technical specification. 175000 Meter
2.0 Supply, Installtion, Testing and Comissioning of CAT6A UTP information outlet (I/O) for Data, Voice & Wi-Fi rack end as per technical specification. 2920 Each

3.0 Supply, Installtion, Testing and Comissioning of loaded 24 port CAT 6A jack panel for CAT6A cable termination as per technical specification. 18 Each

4.0 Supply, Installtion, Testing and Comissioning of loaded 48 port CAT 6A jack panel for CAT6A cable termination as per technical specification. 76 Each

5.0 Supply, Installtion, Testing and Comissioning of CAT 6A Shielded patch cord 3 feet for rack side switch termination for user end as per technical specification. 2920 Each

6.0 Supply, Installtion, Testing and Comissioning of CAT 6A UTP patch cord 7 feet for user termination to information outlet Rack End as per technical specification. 2920 Each

7.0 Supply, Installtion, Testing and Comissioning of 1, 2 and 4 port face plate white for I/O fixing at user side as per technical specification. 2920 Each

8.0 Supply, Installtion, Testing and Comissioning of 42 U (800W/1000D) floor mount rack with fans , 2 cable managers , satationary shelf , 2 Nos of hardware pkts, 12
Socket PDU with MCB as per technical specification. 2 Each

9.0 Supply, Installtion, Testing and Comissioning of 42 U (800W/8000D) floor mount rack with fans , 2 cable managers , satationary shelf , 2 Nos of hardware pkts as
per technical specification. 14 Each

10.0 Supply, Installtion, Testing and Comissioning of 12U wall mount rack with fans , 2 cable managers , satationary shelf , 2 Nos of hardware pkts., 6 Socket PDU with
MCB as per technical specification. 6 Each

11.0 Supply, Installation, Testing & Commissioning of 12 Core, Single Mode, OS2 etc as complete as required and as per technical specification. 200 Meter

12.0 Supply, Installation, Testing & Commissioning of LC-LC, Single Mode, OS2, Patch Cord, 10 Feet 50/125etc as complete as required and as per technical
specification. 20 Each

13.0 Supply, Installation, Testing & Commissioning of 12 port LC multimode loaded LIU including pigtail etc as complete as required and as per technical specification. 10 Each

14.0 Supply, Installation, Testing & Commissioning of 6 Core, Single Mode, OS2 etc as complete as required and as per technical specification. 3400 Meter

15.0 Supply, Installation, Testing & Commissioning of LC-LC, OS2 SM Patch Cord, 10 Feet etc as complete as required and as per technical specification. 60 Each

16.0 Supply, Installation, Testing & Commissioning of 6 port LC Single mode loaded LIU including pigtail etc as complete as required and as per technical specification. 40 Each

(C) CCTV

1.0 Supply, Installation, Testing and Commissioning of 5 MP or higher Bullet Camera - The camera shall capable of resolutions up to 2560x1920 @ 30 fPS, while
optimizing network usage with either H.264, H.265 or MJPEG compression, 1/1.8" progressive CMOS or Better, 2560x1920 @ 30 fPS & 1080x1920@60fps with
H.264/H.265, 2560x1920 @ 12 fps and 1080x1920@30fps with MJPEG, 100 dB or Better, 4-9mm/P-IriS Remote focus and zoom, Color mode: 0.04 lux @ F 1.3,
Black-and-white mode: .001@ f 1.3, 45° to 84° (horizontal) 34° to 62° (vertical), 64° to 113° (diagonal). The camera supports up to five user-defined privacy regions.
Any video within a privacy region is masked in the video stream. Digital in x 1 & Digital out x1, Audio in x 1 & Audio out x1, Number of streams, Should support
simultaneously H.265, H.264, or MJPEG video stream. Each Video streams can be configured with Individual resolution, quality and frame rate setting, The cameras
provide true day/night functionality, and include an infrared (IR) filter that automatically switches to night mode in lowlight scenes. This should be setup Automatic, 298 Nos.
manual, scheduled. Micro SD, H.264 & Motion JPEG and H.265 (Smart Stream). ONVIF & profile G& S for standard based interoperability, 1/5 sec. to 1/32,000 sec,
IPv4, IPv6, TCP/IP, HTTP, HTTPS, UPnP, RTSP/RTP/RTCP, IGMP, SMTP, FTP, DHCP, NTP, The camera should support tamper feature when any of the following
events occur and persist for a designated period: The IP camera view is changed, The IP camera view is blocked, The IP camera view is substantially out of focus,
Differentiated services code point (DSCP) marking and class of service (CoS) marking, IP67 & IK10 rated Enclosure and Mounting bracket for outdoor mounting.
2.0 Supply, Installation, Testing and Commissioning of PTZ Camera - 1/3" Progressive CMOS or Better, 1920x1080 (2MP), 20x Optical Zoom, Auto Focus, f= 4.7 ~ 94
mm, DC- iris, Removable IR-cut filter for day & night function, WDR Pro, True WDR or Better, 3° ~ 55° (Horizontal) , 2° ~ 33° (Vertical), 0.05° ~ 450°/sec. 360° Pan
Range, 0.05° ~ 450°/sec, 220° (-110° ~ +110°) Tilt Range, H.264, H.265 & MJPEG, 30 fps @ 1920x1080 in all compression mode, Micro SD, Four simultaneously
Streams, Full duplex Audio and G.711, G.726 Compression codecs, Should support for ONVIF 2.0 allows for standards based interoperability, Five-window video
motion detection, Auto-tracking on moving object, IP66, IK10, NEMA 4X, -40 to 50°C, CE, FCC Class A, NEMA4X, The PTZ IP camera should automatically track an
object that is larger than a configured threshold. When tracking, the IP camera uses its pan and tilt features to keep the object in its field of view. If there are several 2 Nos.
objects that are travelling in different direction within the field of view, the IP camera identifies each object that is larger than the configured threshold and tracks the
object that is closest to the top left of the field of view. RJ-45 cable connector for Network/PoE connection Audio input & Audio output. Time stamp, text overlay, flip &
mirror; Configurable brightness, contrast, saturation, sharpness, White balance,exposure control gain,backlight compensation, privacy masks ; Scheduled profile
settings, EIS, 3DNR, defog, Manual trigger, system boot, recording notification, motion detection.

3.0 Supply, Installation, Testing & Commissioning of ONVIF Video Management Software, VMS software & recording & Management server should be from same OEM,
All the software & hardware should be provided with 3 year support as per technical specifications. 1 Nos.

4.0 Supply, Installation, Testing & Commissioning of Central Core Server for Surveillance Operation & Management Application at DC: Management server should be an
enterprise-class server in a 1RU form factor, Should have Intel Xeon processor (Preferably E5-2600 family) with atleast 2.3GHz speed & with 6-core CPU, Should
support atleast 4 Number of Hot-swappable SAS drive and Server should be populated as per solution need, Dual Gigabit Ethernet Port, 2 ports (USB 3.0), 1 VGA
video port, Should have RAID controller card, Dual-redundant fans and hot-swappable, redundant power supplies, Should have atleast 16GB DDR4 RAM, Server 1 Nos.
should be supplied with VSM licenses for Management & Operation license, which should be able manage atleast 15 recording servers & 300 camera's

5.0 Supply, Installation, Testing & Commissioning of Recording of Media Server Specification for Data Center: Recording server should be an enterprise-class server in
a 2RUform factor, Should have dual Intel Xeon processor (Preferably E5-2600 family) with atleast 2.3GHz speed & with 6-core each CPU, Should support atleast 12
Number of Hot- swappable SAS drive and Server should be populated with 500 TB HDD to record the video. Dual Gigabit Ethernet Port, 2 ports (USB 3.0), 1 VGA
1 Nos.
video port, Should have RAID controller card, Dual-redundant fans and hot-swappable, redundant power supplies, Should have atleast 16GB DDR4 RAM, Server
should be supplied with VSM licenses

6.0 Supply, Installation, Testing & Commissioning of Recording of 54" Full HD LED Display Monitor as per technical Specifications. 13 No.
(D) FIRE DETECTION AND PA SYSTEM

a) Fire Panel & Annunciators

1.0 Supply, Installation, Testing & Commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with
minimum 600 characters LCD display, 4000 event plus 1000 alarm log history events, QWERTY keypad for programming. The panel should be equipped with
sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 300 analog addressable devices. The panel
shall work in degrade mode in case of CPU failure, Products not having this feature may offer Redundant CPU. Four access levels, flash EPROM, 240 volts AC
power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. The panel shall be
complete with Integrated 8 channel Digital Voice Evacuation System Controller capable of broadcasting Evacuation Messages on same peer-to-peer Network and 2
ways Communication Fire Fighters System capable of supervising all the speaker circuits with adequate zone control and accessories. Failure of Fire Panel CPU
shall not result in failure of DVC operation. The Fire Fighters Telephone System shall be capable of having minimum 30 Telephones in conference in multiple FFT
Risers. Designed to meet UL864, 10th Edition.

1.1 10-loop - With Digital Voice Command Center 3 Nos


1.3 1-loop - With Digital Voice Command Center 2 Nos

2.0 Supply, Installation, Testing & Commissioning of Network Repeater Panel with minimum 10" Color Touch Screen display with QWERTY Keypad, mapping minimum
2,00,000 points on network. The NRP shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel 1 Nos
CPU for operation. Failure of Fire Panel CPU shall not result in failure of NRP operation.

3.0 Supply, Installation, Testing & Commissioning of Digital Audio Amplifier shall be dual channel capable of processing Two of 8 audio channels and total of 100 W at
70.7 VRMS output along with necessary enclosures. The Digital Audio Amplifier shall be fully monitored for fault and alarm reporting. The proposed Digital
Audio Amplifiers shall (be Wall/Panel Mounted) not be rail mounted / dependant on Fire Panel CPU for operation. Failure of Fire Panel CPU shall not result in failure 40 Nos
of Amplifier operation.

b) Software & Gateways

5.0 Supply, Installation, Testing & Commissioning of Graphics User Interface for Monitoring & Control of complete Fire, Voice Evacuation & Telephone Talkback System.
The GUI based main network software shall network with other panels on True Peer-to-Peer network. It shall be capable of graphically representing each facility
being monitored with floor plans and icons depicting the actual locations of the various systems, and / or sensors’ locations. It shall have the facility to change the
sensitivity of any detector. The software shall be capable of monitoring 200 Nodes with 100 Mbps Transmission rate on Fibre Optics Network and 12 Mbps
Transmission on cable and 2,50,000 network points. The software shall be capable to Monitor & Control all the Digital Voice Evactuation as well as 2 way 1 Nos
communication from main control room using voice signals over Fire Network along with the Fire detection signal. The Graphic workstation shall act as an
independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for operation. Failure of Fire Panel CPU shall not
result in failure of GUI and Including PC, monitor etc as complete as required.

6.0 Supply, Installation, Testing & Commissioning of MODbus Interface Gateway for communication with BMS / Other Utilities. MODbus shall support minimum 12000
data points. MODbus Gateway shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for 2 Nos
operation. Failure of Fire Panel CPU shall not result in failure of MODbus Gateway.

c) Detectors

7.0 Supply, Installation, Testing & Commissioning of Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 4.0% obs/ft.The intelligent multi
criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the
event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of
5225 Nos
the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for
360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition.

8.0 Supply, Installation, Testing & Commissioning of Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min. The detector shall have twin bi-colour LED for 360
deg viewing. Addressing shall be with user friendly rotary decimal switches. 28 Nos

9.0 Supply, Installation, Testing & Commissioning of Addressable Duct Smoke Detector. The duct detector shall have an air velocity rating from 100 to 4000 ft/min. The
detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. 37 Nos
10.0 Supply, Installation, Testing & Commissioning of Addressable High Sensitivity Photo Detector with sensitivity level of 0.02% to 2% Obs/Feet. The detector shall have
the optic block to amplify signals from smoke, but diminish stray internal reflections that can cause false alarms. The detector shall have twin bi-colour LED for 360 6 Nos
deg viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition

11.0 Supply, Installation, Testing & Commissioning of Addressable Beam Detector. The beam detector shall be used for High Ceiling application with a detection range
upto 100 mtrs having 4 manual & 2 auto sensitivity settings. The beam detector shall be True addressable installed on the SLC circuite & communicate directly with 2 Nos
the panel without any interface module.

d) Modules

12.0 Supply, Installation, Testing & Commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in
normal state & get steady on activation to monitor the heath status of the device. 168 Nos

13.0 Supply, Installation, Testing & Commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes. The control module shall provide
supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of
the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & 168 Nos
maintenance.
14.0 Supply, Installation, Testing & Commissioning of Addressable Relay Module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third
Party Outputs. The relay module shall provide contact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation
to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for 192 Nos
ease of installation & maintenance.

15.0 Supply, Installation, Testing & Commissioning of Addressable Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor
potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. 87 Nos
Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance.

16.0 Supply, Installation, Testing & Commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can
also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get
steady on activation to monitor the heath status of the device. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. 320 Nos

e) Notification Devices

17.0 Supply, Installation, Testing & Commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for Audible annunciation and 115cd flashintg at 1 Hz for visual
indication. UL Listed 168 Nos

18.0 Supply, Installation, Testing & Commissioning of 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling Mount Speakers. The speakers shall be of same make as that of the
Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms. UL Listed 1822 Nos

19.0 Supply, Installation, Testing & Commissioning of 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Wall Mount Speakers. The speakers shall be of same make as that of the
Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms. UL Listed. 45 Nos

20.0 Supply, Installation, Testing & Commissioning of Addressable Power Supply Unit: 24V DC for Notification Appliances. 15 Nos

21.0 Supply, Installation, Testing & Commissioning of Response Indicator. 3352 Nos

f) Telephone Talkback

22.0 Supply, Installation, Testing & Commissioning of Addressable Fire Fighter's Telephone Jack with suitable supervised/ control module for two way communication
between Remote Fire Fighter & Fire Command Center. 133 Nos

23.0 Supply, Installation, Testing & Commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command
Center. 15 Nos

g) Conduting & Cabling-

24.0 Supply and Fixing of 25 mm dia MS Conduit 2000 Meter

Supply, Laying, Testing & Commissioning of 2Cx1.5 sq.mm LPCB certifed HPSR insulated Fire Survival cable, armored copper conductor as per BS7629,HPSR
25.0 insulated overall sshielded, halogen free sheathed fire test as per BS6387/CWZ, BSEN 50200 including termination. 110000 Meter

S.H-III ACCESS CONTROL SYSTEM


1.0 Supply, Installation, Testing and Commissioning of Access Control System Server Software consisting of Access Control system, Visitor management with all
employee visitor license, Elevator Control, Guard Tour Management , Mantrap, Alarm Document, Alarm management, 3 client License, Graphical layout, Card
Enrollment, Badge designing..All these along with high end security features consist in single package with an option to integrate with CCTV sub system (License Set 1
based ) as per specifications of this tender and directions of Engineer-in-Charge.

2.0 Supply, Installation, Testing and Commissioning of PC with 32" Monitor as per following specifications: Server Specification for Access Control Software- Processor -
Intel® Xeon® X5670, 2.93GHz, 12M Cache, Turbo, HT, 1333MHz, OS - Genuine Windows XP/7 Colour Monitor - 17" Flat Panel LCD Monitor, RAM - 4GB DDR2,
667MHz SDRAM, Memory - 500 GB HDD, Graphic Card - Integrated Intel Graphics Media Accelerator X3100 Two(2) PCI-X and Two(2) PCI-Express Expansion
Slots 2/4 USB, 2 serial, and 2 VGA Adaptor, CD/DVD ROM.; USB Keyboard and Mouse Dual Channel Internal Ultra320 SCSI Integrated RAID-1 with hot-spare, Dual Each 1
Integrated 10/100/1000 Ethernet NIC I/O Expansion Option as per specifications of this tender and directions of Engineer-in-Charge.

3.0 Supply, Installation, Testing and Commissioning of controller shall be a 32 bit microprocessor with Linux OS. The controller shall have 128 MB DDR SRAM and 64
MB Flash memory. Support minimum 16 doors with a readers for entry and exit. Support minimum 16 standard Weigand Interface on LONbus. Support minimum 64
I/Os with expandable 4 DI/DO modules on LONbus. Controller level redundancy with Hot Redundant Controller failover without manual intervention. The access
controller shall support minimum Card Holder Memory: 1,00,000 card holders, expandable upto 2,50,000 card holders. The controller shall support minimum 100000
transaction buffer and 10000 event buffer. The controller shall have autonomous clock/calender with geographic time zone support and daylight saving. The Each 25
controller shall have on-board 10/100MB Ethernet connection for TCP/IP connectivity. Controller shall have built-in web server and support web access. Shall
perform in a peer to peer network with other controllers. Controller shall have IPSEC with 3DES encryption on LAN communication. Controller shall have Tamper
protection feature.as per specifications of this tender and directions of Engineer-in-Charge.
4.0 Supply, Installation, Testing and Commissioning of contact-less smart card reader with Read Range- upto 5cm, Mounting- Mullion, Operation Frequency- 13.56MHz,
Reader Output- Wiegand, Card Compatibility- 2KByte, 4KByte I - Class smart cards, Mifare and DESFire. Environmental Rating- IP55, Operating Temp: -35º to 65º
C, Operating Humidity: 5% to 95% relative humidity non-condensing, Power Rating: 5-16VDC, 55mA AVG Current, Certification: CE, UL, FCC as per specifications Each 100
of this tender and directions of Engineer-in-Charge.

5.0 Supply, Installation, Testing and Commissioning of biometric smart card reader Fingerprint Sensor : 500 dpi Optical Sensor, Fingerprint Capacity : 10K templates (5K
users with 2 templates per user), Log Capacity: 50K events, Identification Speed:2000 matches per second, Card Reader: 13.56MHz Mifare, Operation Mode:
Fingerprint, Fingerprint+ Pin/Card, Network Interface: TCP/IP, RS485, Reader output: Wiegand, Display: 128x64 graphic monochrome LCD, Multi - color LED, Each 6
Keypad: 3x4 keypad, 3 navigation keys, Audio: Multi tone Buzzer, Power Supply:12 VDC, Protection Class: IP66, Operating Temp
-20°C to +50°C, Certifications: CE as per specifications of this tender and directions of Engineer-in-Charge.

6.0 Supply, Installation, Testing and Commissioning of single Electromagnetic lock,600 lbs along with magnetic contact complete as required. Each 10

7.0 Supply, Installation, Testing and Commissioning of double Electromagnetic lock,1200 lbs along with magnetic contact complete as required. Each 40

8.0 Supply, Installation, Testing and Commissioning of exit push button complete as required. Each 0

9.0 Supply, Installation, Testing and Commissioning of exit push button break glass enclosure complete as required. Each 50

10.0 Supply, Installation, Testing and Commissioning of Door Contact as required. Each 50

12.0 Supply, Installation, Testing and Commissioning of piezo electric buzzer as required. Each 50

13.0 Supplying and Laying including termination testing and Commissioning of following sizes of cable on surface/ recess/ existing cable tray/ conduit etc. complete as
required.
13.1 3x1.5sqmm power twisted pair copper cable. Meter 2000

14.0 Supply, Installation, Testing & Comissioning of Boom Barrier with Application: Outdoor, Drive: Block able Continuous Torque Motor, Version: Left handed
(changeable to Right Hand), Logic Control: Included, Intelligence: The use of Block able Torque Motor Drive with continues torque Output and the microprocessor
based controller eliminates the need for friction clutches to ensure maintenance free operation. The barrier may be installed at any position. Power Supply: 230 +/-
10% VAC, 50Hz. Colour: Different and distinct colour pattern as decided by owner. The paint used will be anti-corrosive and luminous for night and bad weather.
Boom Specifications: straight or articulated -extruded aluminium alloy. Boom with octagonal profile (straight and articulated 100mm x 55mm x 1.6mm. Housing
Dimension: W300mm, D 350mm, H1040mm, Protection: All Housing and internal parts will be rust & corrosion free metals or alloys of high strength with suitable Set 2
Epoxy coating as applicable. Opening: 1.4 seconds for 4 meters long Boom Barrier. Closing Time: Should be 1.4 Sec approx. Power-Off: Manual Opening Possible,
Operation: Push button type for electro-mechanical operation to open and close the Boom Barrier, Duty Cycle: 100% up to 3 meter Electromechnical Boom barrier
with loop sensor /beam sensor & boom resting post vehicle access barrier & all accessories complete as required as per specifications .

15.0 SITC of 8 Conductor, 18-24 AWG, Overall Shielded, PVC for Card Readers Description : Shielded multi conductor control cable
Conductors : 18/22 AWG 7/32 Strand Tinned Copper, 6 conductors Insulation : Colour coded PVC 0.010"
Colour Code : Black, white, red, green, blue, brown Shielding : 100% aluminium mylar foil shield overall with a 24 AWG 7/32 strand tinned copper drain wire. Meter 2100
Jacket : Gray flame retardant PVC 0.032" Nominal OD : 0.205" Capacitance : 33 pF/Ft between conductors
Ratings : Manufactured in accordance with UL subject 13, type CM Passed UL VW-1 Flame Test UL CM approved

16.0 SITC of 2 Pair, 18 AWG, Individually Shielded, Poly propyene Insulated Signal Cable for Intelligent Controller Communication.Description : 2 pair individually
shielded cable Conductors : 18 AWG 7/30 Strand tinned copper, twisted into 2 pairs Insulation : Colour coded polypropylene, 0.008" Colour Code : Black with red,
Green with white Shielding : Each pair individually shielded with 100% aluminium mylar foiled shield plus 22 AWG 7/30 strand tinned copper drain wire. Meter 1600
Jacket : Gray flame retardant PVC Nominal OD : 0.170" Capacitance : 35 pF/Ft Voltage : UL rated 300 Volts
Ratings : Manufactured in accordance with UL subject 13, type CM Passed UL VW-1 Flame Test UL CM approved

SUB-HEAD 7.0 BMS WORK

All the items listed below shall include supply, installation, testing & commissioning.

1) Software and Operator Workstation

1.1 Host PC comprising core i7 processor or later, 3 GHz, 8.0 GB RAM, 1 TB HDD, DVD drive, 6 nos. USB Port, 18.5" SVGA color flat TFT monitor, keyboard, mouse
and pre-loaded windows 8 operating system and anti virus software, Laserjet printer (A4 size, B/W) 1 NO.
1.2 Supply, installation, testing and commissioning of Layer 2/3 managed switch with 16 or 24 ports (RJ-45) port. The switch shall have 2 RSTP enabled ports to
communicate with other switches to built a ring topology network on CAT6 A cable. The switch shall including SFP modules, rack mountable, SMPS power supply &
other termination accessories (Like Pigtails/LIUs/ Convertors/Splicing equipment, Patch panel, Patch Cord, Etc) complete as per specifications and as required for 1 Lot
BMS DDC Panel Networking. The switch to switch distance shall not exceed beyond 80 meters.
Vendor to decide the quantity of network switches based on their network design.

1.3 Supply, installation, testing & commissioning of the following Web Based graphical Software. Providing facilities to create static & animate the graphics, navigation
between the pages, display of logs, changing the time zones, popup alarms with single user license & point capacity as per I-O Summary with 20% spare points
configurable password protection for the system and should be able to communicate with BACnet/M-BUS/LONWORK & MODBUS devices simultaneously. This
software will act as web server & no additional license should require at client side.

1.3.1 Application Software for Building Automation System having facility to to exchange information using SQL database. Software shall have the features to calculate the
total power consumption, total refrigeration load consumed on every day etc. Critical alarms generated in a day and its status should also be mailed along with daily 1 Lot
report.

2) Supervisory Controllers

2.1 Network Area / Supervisory Controller for Building Management System (BMS). Network Area Controller Shall support Communication with AC Plant Controllers
(DDC controllers) & Other Application Controllers on BACnet, Shall support Communication with Integrator Units as defined below on BACnet / MODBUS / 1 Lot
LONWORKS. Router must be compliant with ANSI / ASHRAE 135-2012 (Rev. 1.10)
SUB-HEAD 7.0 BMS WORK

3) Direct Digital Controllers (BACNET / LON Type)

Stand alone, intelligent, UL Listed, BTL listed & BTL tested, ANSI / ASHRAE approved Interoperable DDC as per the specifications. All the Controllers shall be UL /
BTL tested & CE certified. Each controllers shall be equipped with Universal Inputs with a maximum polling speed of 100 ms. DDC Controller shall have a resident
real time clock with a battery back up. DDC must support trending & scheduling at Controller level.The controller shall be housed in a vandal proof, lockable and
secure MS cabinets to be supplied along with controllers. DDC must match BACnet profile B-BC (Building Controller) / B-AAC Profile as per BTL listing. The
controller shall have 15% Extra IO capacity.

Each of the following systems shall have seperate multiple controllers, as required. The DDC selection shall be based on I-O Summary as given in the tender.

3.1 For Chilled water system - Chillers, CHW & CDW Pumps, Cooling Towers, HWG, HW Pumps, Expansion Tank & Headers etc. as required. 1 Lot

3.2 For Air Handling Units (Category A Temperature Control) as per IO Summary as required. (2 Nos. AHU with 1 No. DDC) 47 Lot

3.3 For Air Handling Units (Category B Temperature & RH Control) as per IO Summary as required. (2 Nos. AHU with 1 No. DDC) 16 Lot

3.4 For Air Handling Units (Category C For Recirculated OT) as per IO Summary as required. (1 No. AHU with 1 No. DDC) 12 Lot

3.5 For Air Handling Units (Category D For 100% Fresh Air OT) as per IO Summary as required. (1 No. AHU with 1 No. DDC) 6 Lot

3.6 For All 3 Phase Fans - Fresh Air / Exhaust Air Fan, Airwasher, Scrubber, Pressurisation Fan etc. as required. (4 No. Fans with 1 No. DDC) Excluding Basement
Ventilation Fans 15 Lot

3.7 For Lift Well, Lift Lobby & Staicase Pressurisation Fans (4 Nos. Fans with 1 No. DDC) 5 Lot

3.8 For DG set 1 Lot

3.9 For Electrical System 1 Lot

3.11 For Water Management System, STP etc. 1 Lot

3.12 For Fire Fighting System 1 Lot


SUB-HEAD 7.0 BMS WORK

4) Field instruments As Per I-O Summary

4.1 Immersion Temperature sensor with thermowell for Chilled water system (4 Nos. Chiller Outlet, 2 Nos. Chilled Water Header, 1 No. Condenser Water Return Header,
8 Nos. Hot Water Generator Outlet, 2 Nos. Hot Water Header) 17 No.

4.2 Ambient air temperature and humidity sensor 1 No.

4.3 Current relay for pumps (4 Nos. Primary CHW Pumps, 4 Nos. CDW Pumps, Excluding Pumps on VFD) 8 No.

4.4 Differential pressure switch for various vent. fans excluding Inline & Propeller Fans 86 No.

4.5 Differential pressure switch for AHU blower status 143 No.
4.6 Differential pressure switch AHU Pre, Fine & Hepa Filter status 302 No.

4.7 Temperature sensor for return temperature monitoring (Common for cooling / heating) 94 No.

4.8 Duct Temperature & RH Sensor 31 No.

4.8 Touch Screen based Temperature & RH display with set point adjuster (OT) 18 No.

4.9 Level Switch for Cooling Tower & Tanks 16 No.

4.10 Level switch for DG fuel tanks (Flame Proof) 5 No.

4.11 DC Voltage Transducer 5 No.

4.12 Digital electronic multimeter 2 No.

4.13 Lux Level Transmitter 4 No.

4.14 Temperature, RH & IAQ Monitor

Standalone, Networkable Temperature, RH & IAQ Monitor along with single / multiple Touchscreen Display in each AHU Room which will have Modbus Protocol
inbuilt as a standard, IOT & Webserver Option for Remote Monitoring, inbuilt memory of 1 GB to monitor & datalog CO2 Level (0-5000 ppm), PM1, PM2.5, PM10 , 2
nos. temperature sensor (-10 to 60 Deg C) for AHU supply & return air temperature monitoring i.e. at supply for chilled water modulation & at return air stream for 0 Set
AHU VFD modulation, Humidity Parameters (0-100 % non condensing) & shall work on 24VAC/DC.

SUB-HEAD 7.0 BMS WORK

5) Integrators for third party systems on BACnet/MODBUS/LONWORKS/OPC/M-BUS and other industry standard Open protocols for the following Third Party
Systems.
Chillers onIntegrator should have dedicated one Lon, RS-485 & RS-232 Port with minimum of 96 MB storage.Integrator should be able to store trending to ensure
BACnet/MODbus/LONworks
gap free storage.The Third Party Integrator should be from the same manufacturer as that of DDC.
Variable Frequency Drives on BACnet/MSTP, MODBUS-RTU Over RS-485
Fire Alarm Systems-on BACnet/IP or MODbus-RTU over RS-485
Electrical Energy Meters-MODbus-RTU over RS-485
UPS-MODbus-RTU over RS-485
DG Set-MODbus-RTU over RS-485 1 Lot
LIFT-MODbus-RTU over RS-485
CCTV integration on OPC or any Industry Standard open Protocol
Solar System on Modbus/RS485 or Modbus/IP
STP PLC on Modbus/RS485 or Modbus/IP or Bacnet
ETP PLC on Modbus/RS485 or Modbus/IP or Bacnet
Electronic KWH Meter on BACnet/MODbus/LONworks

6) Cabling and Conduiting

6.1 Communication & Signal Cabling 2C x 1.5 Sq. mm Shielded Tinned Copper Cable. 35500 RMT
6.2 MS Conduit 25 mm for Signal & Communication Cable 30200 RMT

6.3 Supply & Laying of 6 core armoured multimode fibre optic cable in 40mm HDPE Pipe along with all accessories as required.
1500 RMT

TOTAL