Callum Murton
Peter Cenek
Russell Kean
Central Laboratories Report 12-5C1617.93
This document and its contents are the property of Opus International Consultants Limited. Any
unauthorised employment or reproduction, in full or part is forbidden.
The document has been prepared solely for the benefit of the NZ Transport Agency. No liability is
accepted by Opus International Consultants or any employee or subconsultant of this company
with respect to its use by any other person. This disclaimer shall apply notwithstanding that the
document may be made available to other persons for an application for permission or approval or
to fulfil a legal requirement.
© Opus International Consultants Limited 2013
Central Laboratories Report 12-5C1617.93
Executive Summary
This report presents an assessment of ground-borne vibrations resulting from the construction of
the Basin Reserve Transportation Improvements project and from traffic once it becomes
operational. The assessment has been predicated on the results of ground vibration
measurements made at various sites around the Basin Reserve on the 26th and 30th of April 2012
and application of predictive models contained in various standards and technical references.
The measured and estimated vibrations were assessed from the perspectives of human comfort,
cosmetic building damage and reduced serviceability of underground services using guidelines
given in British Standard BS 5228 2:2009, Code of practice for noise and vibration control on
construction and open sites – Part 2: Vibration and German Standard DIN 4150-3:1999, Structural
vibration – Part 3: Effects of vibration on structures.
The primary conclusions arising from this assessment of ground vibrations generated by the
construction and operation of transportation improvements around the Basin Reserve are as
follows:
1. There may be some short term disturbance to occupants of nearby buildings resulting
from construction activity. However, these disturbances are likely to be acceptable if
proven vibration management methods are applied, such as selection of appropriate
equipment and construction methodology and keeping affected parties informed as to
when vibration generating activity is to take place and its duration.
2. The existing environment around the Basin Reserve is exposed to low level traffic-
induced vibrations from State highway 1. These vibrations are considered to be
acceptable as they are within recognised guidelines for human comfort applied
internationally. The Project, once operational, will not result in any worsening of
existing traffic-induced vibration levels.
3. Buried services are expected to be exposed to maximum vibration levels of between 4
mm/s and 16 mm/s peak particle velocity (PPV) during construction and about 6 mm/s
PPV once the Project is operational. By comparison, the maximum level of intermittent
and transient vibrations that underground services should be subjected to is 30 mm/s
PPV if in good condition or 15 mm/s PPV if old or dilapidated according to British
Standard BS 5228-2:2009. Therefore, ground vibrations generated by construction
activities can be easily tolerated if the buried pipework is not old or in a dilapidated
condition. Because of the historic nature of the brickwork Waitangi Stream culvert, it
would be prudent to perform condition surveys pre and post construction of the Project
to ensure no change to its structural integrity takes place. In addition, vibrations should
be monitored, as detailed in the Construction Noise and Vibration Plan (CNVMP),
whenever piling activity occurs in close proximity to the culvert to ensure vibrations
measured on the culvert are below levels that could cause structural damage or
settlement of the ground surrounding the culvert. Once the Basin Bridge becomes
operational, all the buried services will be exposed to traffic induced vibrations that will
be of the same magnitude as a present.
4. Foundations for the two proposed new buildings, one to be erected within the Basin
Reserve immediately adjacent to the RA Vance Stand (northern gateway building) and
the other to be erected at the intersection of Ellice Street with Kent Terrace
immediately adjacent to the Grandstand Apartments (building under the bridge), will
most likely need to be piled. Therefore, care will have to be taken in selecting a method
Basin Bridge Project: Technical Report 8
Assessment of ground vibration effects
May 2013 8-i
Central Laboratories Report 12-5C1617.93
Contents
List of figures
Figure 8.1: Project Area showing the proposed roading layout and land to be designated .............. 3
Figure 8.2: Proposed traffic directions for the Project ...................................................................... 4
Figure 8.3: Urban and landscape zones for proposed works outside of the traffic lanes ................. 7
Figure 8.4: Histogram of peak particle velocities (mm/s), due to traffic-induced vibrations, within
each 10-second period at testing Site S4 on the southern side of Paterson Street........................ 19
Figure 8.5: Annoyance due to vibrations in dwellings plotted against calculated statistical maximum
values for weighted velocity, vw,95 (NS 8176.E:2005) ..................................................................... 21
Figure 8.6: Location of historic Waitangi Stream Culvert relative to Basin Reserve northern
gateway building ........................................................................................................................... 32
Figure 8.7: One Market Lane construction site .............................................................................. 37
List of tables
Table 8.1: Test sites and test types ............................................................................................... 14
Table 8.2: Guidance on effects of vibration levels (from British Standard BS 5228-2:2009, Annex B)
..................................................................................................................................................... 15
Table 8.3: Guideline values for vibration velocity to be used when evaluating the effects of short-
term vibration on structures (from German Standard DIN 4150-3 1999) ....................................... 16
Table 8.4: Guideline values for vibration velocity to be used when evaluating the effects of long-
term vibrations on structures (from German Standard DIN 4150-3 1999) ...................................... 17
Table 8.5: Guideline values for evaluating the effects of construction-related vibration on buried
services (from British Standard BS 5228-2:2009).......................................................................... 17
Table 8.6: Guideline values for vibration velocity to be used when evaluating the effects of short-
term vibration on buried pipework (from German Standard DIN 4150-3:1999) .............................. 18
Table 8.7: Common ground vibration levels .................................................................................. 18
Table 8.8: Measured peak particle velocities (mm/s) due to traffic-induced vibrations ................... 20
Table 8.9: Estimated site specific attenuation coefficients ............................................................. 22
Table 8.10: Measured vibration magnitude attenuation parameters due to vibrations caused by
sandbag drops .............................................................................................................................. 24
Table 8.11: Estimated vibration levels at properties most effected by bore piling operations ......... 27
Table 8.12: Estimated vibration levels at properties most affected by vibratory roller activity ........ 28
Table 8.13: Estimated vibration levels at properties most affected by bored pile activity associated
with the northern gateway building ................................................................................................ 33
Table 8.14: Highest vibration levels measured during vibratory and oscillatory piling activity at One
Market Lane site ........................................................................................................................... 37
Table 8.15: Estimated vibration levels at properties most effected by bore piling operations if
vibration levels measured at One Market Lane could be replicated for the Project ........................ 38
1 Introduction
This report presents an assessment of ground-borne vibrations resulting from the construction of
the Basin Bridge project (hereafter referred to as the Project) and from traffic once it becomes
operational. In carrying out this assessment, no consideration of either construction or operational
induced vibrations at 28 Ellice Street has been made based on the assumption that the existing
residential building at this site will be removed to maintain the car park space at St Joseph’s
Church at present levels. This is discussed in greater detail in section 2.3 of this report.
The assessment has been predicated on the results of ground vibration measurements made at
various sites around the Basin Reserve on the 26th and 30th of April 2012. The measurements were
undertaken to:
• quantify the current vibration magnitudes induced by traffic;
• establish how quickly the traffic vibrations decay with distance for the main soil types found
around the Basin Reserve; and
• derive site specific predictor curves for estimating the magnitude of ground vibrations from
impact related construction activity.
The principal objectives of measurements were to provide an indication of existing traffic-induced
vibration levels (the baseline case) and the expected vibration magnitudes that will arise as a result
of the construction of and traffic flow over the proposed bridge to be constructed as a part of the
Project.
The measurement of the traffic-induced ground-borne vibrations and their attenuation were carried
out using either an array of four accelerometers evenly spaced along a line perpendicular to the
road, or a single accelerometer at a point of interest that could not accommodate the full array. The
traffic-induced ground-borne vibrations were recorded at each site investigated for a period of 15
minutes.
The array of four accelerometers was also used to derive the predictor curves. In this case,
vibrations were induced by dropping a 25 kg sandbag from a height of 1 m at a location in-line with
the accelerometer array, and at a specified distance from the end of the array. Three drops were
recorded at each end of the array, resulting in six measurements in total for each location
investigated.
The measurement of the ground vibrations conformed to the following International Organisation
for Standardisation (ISO) standards:
• International Standard ISO 8041:2005, Human response to vibration - Measuring
instrumentation, and
Basin Bridge Project: Technical Report 8
Assessment of ground vibration effects
May 2013 8-1
Central Laboratories Report 12-5C1617.93
• International Standard ISO 4866:2010, Mechanical vibration and shock – Vibration of fixed
structures – Guidelines for the measurement of vibrations and evaluation of their effects on
structures.
The measured vibrations were assessed using guidelines given in British Standard
BS 5228-2:2009, Code of practice for noise and vibration control on construction and open sites –
Part 2: Vibration and German Standard DIN 4150-3:1999, Structural vibration – Part 3: Effects of
vibration on structures.
The report has been structured as follows:
• Section 2 presents an overview of the Project. Key aspects of the Project from a vibration
perspective are also highlighted.
• Section 3 describes the vibration measurement methods utilised.
• Section 4 details the criteria by which the measured vibrations were evaluated from the
perspectives of human comfort and cosmetic building damage.
• Section 5 summarises the key results from the measurement programme.
• Section 6 discusses baseline conditions and identifies possible issues related to
construction and operational traffic vibrations generated from the Project along with
suggested remedial actions.
• Section 7 lists the main conclusions resulting from the assessment.
• Appendix A shows aerial views of each vibration monitoring site and were the
accelerometers were placed.
• Appendix B gives all the predictor curves derived from the sandbag drop tests.
• Appendix C investigates the effect of different drop-weight characteristics on drop test
results.
2 Project Description
The Project proposes to construct, operate and maintain new transport infrastructure for State
Highway 1 at the Basin Reserve. A key component of the proposal is a multi-modal bridge that
connects Paterson Street with Buckle Street. The bridge will provide a two lane one-way
carriageway for SH1 westbound road users and includes a shared walking and cycling path on its
northern side.
Proposed at-grade road improvements include changes to Dufferin Street and sections of Paterson
Street, Rugby Street (including the intersection with Adelaide Road), Sussex Street, Buckle Street
(SH1), Taranaki Street, Vivian Street (SH1), Pirie Street, Cambridge Terrace, Kent Terrace (SH1),
Ellice Street and Hania Street. The overall road layout is shown diagrammatically on Figure 8.1
below.
Figure 8.1: Project Area showing the proposed roading layout and land to be designated
The Project also provides urban design and landscape treatments. These include new landscaped
open space areas, a new building under the bridge, a new entrance and Northern Gateway
Building to the Basin Reserve, an improved streetscape entrance to Government House and
adjacent schools, a revised car park for St Joseph’s Church, dedicated bus lanes and bus stops
around the Basin Reserve, as well as new walking and cycling paths.
Proposed landscaping and urban design treatments include low level plantings, raingardens, trees,
terracing, architectural bridge design including sculptured piers, furniture and paving. These
measures aim to contribute to the overall integration of the proposed bridge structure into the
surrounding urban environment.
The bridge soffit will be up to 7.3m above the ground surface and the top of the guard rail will up to
10.5m high above the ground. The bridge is approximately 263m long or 320m long if abutments
are included. It will be supported by six sets of piers (2 are double piers) and six smaller diameter
piers to support the western end of the shared pedestrian and cycleway. The bridge has a
minimum width of approximately 11.3m and a maximum width of approximately 16.7m. There are 2
bridge joins, one at each end.
The Project proposes changes to the SH1 westbound route, the SH1 eastbound route, and other
roads on the network where they connect with SH1, including clearways on the eastern part of SH1
Vivian Street (from Tory Street to Cambridge Terrace). These propose to improve the efficient and
safe movement of traffic (including buses), pedestrians and cyclists through intersections and
provide entry and exit points for SH1. Supplementary works on the existing local road network are
also proposed to be undertaken to take advantage of the additional capacity created by the SH1
improvements.
The Project proposes new pedestrian and cycling routes throughout the Project area as well as
improvements to existing infrastructure. The majority of the works to improve the walking and
cycling routes are located on the north side of the Basin Reserve and connect with Mount Victoria,
Mount Victoria Tunnel and schools on Dufferin Street. These improvements will also connect with
the National War Memorial Park which is currently under construction and also with potential future
duplication of Mount Victoria Tunnel.
A reduction in state highway traffic on the roads around the Basin Reserve allows for more efficient
northbound and southbound movements from Kent and Cambridge Terrace to Adelaide Road.
Accordingly, new dedicated bus lanes are proposed to provide for better public transport
movements around the Basin Reserve.
The key traffic flows around the Basin Reserve following the implementation of the proposed
Project are shown in Figure 8.2 below and described thereafter.
• Public Transport - new dedicated bus lanes are proposed on Ellice Street, Dufferin Street
and Buckle Street, and the southbound bus stop is proposed to be relocated from Adelaide
Road onto Rugby Street; and
• Public Transport - existing priority for buses from Kent Terrace onto Ellice Street is
retained.
For further detail on the proposed transport improvements refer to Volume 3: Technical Report 4:
Assessment of Transportation Effects of these documents. Details of the road design layouts are
shown in Volume 5: Plan and Drawing Set.
Figure 8.3: Urban and landscape zones for proposed works outside of the traffic lanes
These are briefly described for the urban and landscape zones below:
• Zone 1 Cambridge/Buckle Bridge Interface Zone - proposed landscape treatments to land
between Cambridge Terrace and the NWM Park, which includes rain gardens and wetland
plantings for stormwater treatment. This landscape area has been designed as a
continuation of NWM Park. The terracing in the NWM Park starts from Kent and
Cambridge Terraces and are reflective of the cultural heritage of the area, as cultivation
terraces. Wetland planting reflects the former Waitangi Lagoon which is now the Basin.
The landscaping also provides an interface with the curtilage of the newly relocated Home
of Compassion Crèche (former)1.
• Zone 2 Kent/Cambridge Basin Gateway: proposed landscaping between Kent/Cambridge
Terrace responds to tangata whenua values in relation to the proposed historical wetland
ecology and provides a safe and enlarged public access and gathering area relative to the
Basin Reserve entrance. The proposed landscape aims to facilitate gathering and includes
reconfigured pedestrian crossings, bus stops and Basin Reserve entrance.
• Element 2.1 Entrance to the Basin Reserve – proposes a combination of planting
(pohutakawa trees) and a new Northern Gateway Building on the northern boundary within
1
The Home of Compassion Crèche (former) is being relocated as part of the National War Memorial Park project.
the Basin Reserve. The combination of new Northern Gateway Building and pohutakawa
trees screen the bridge from general views from within the Basin Reserve. The new
Northern Gateway Building is designed to specifically remove potential views of traffic on
the bridge from the views of batsmen (facing bowlers from the north). The new Northern
Gateway Building) would provide space for player facilities and includes a wider entrance
for visitors to the Basin Reserve that is aligned with the new entrance plaza located
between Kent and Cambridge Terrace.
The new structure will occupy the space between the RA Vance Stand and the existing
toilet block at the edge of the northern embankment. The new structure will be up to 65m
long and up to 11.2m high and includes a screen that covers the gap between the new
building and the RA Vance Stand. This option is preferred by the Basin Reserve Trust.
Alternative mitigation proposals entailing a 45m long structure and a 55m long structure
and consequent increases in proposed tree planting have also been considered and are
assessed within this report.
• Zone 3 Kent/Ellice Integrated building zone – proposes a new building under the proposed
bridge at the corner of Kent Terrace and Ellice Street which would be made available for
commercial use. It is intended to re-establish the historical built / street edge in this location
and the building helps incorporate the bridge into the built urban environment. A green
screen is proposed to be located above the new building to provide a level of screening for
the adjacent apartment building and assist to visually integrate the bridge with the buildings
at this corner.
• Zone 4 Paterson/ Ellice/Dufferin Interface zone – proposes to continue ground landscape
linking from across Kent/Cambridge Terraces and additional tree planting around the Basin
Reserve’s outer square.
The Project proposes works within St Joseph’s Church property using land that is currently
used for car parking. Thus, the Project proposes to remove the existing building at 28
Ellice Street and to adjust the existing carpark and provide landscape improvements for
the Church within the remaining space. All of these works are located on land owned by
the Church.
• Zone 5 Dufferin/Rugby Streets, Schools/Church/Government House Interface zone which
serves as a vehicular and pedestrian access area serving key adjacent land uses of the
schools and Government House. Proposed works include the re-allocation of space in the
roading corridor, layout modification and urban design and landscape treatments.
• Zone 6 The Bridge Element – the horizontal alignment of the Bridge has retained a close
reference to the historic street pattern (the Te Aro Grid) to strengthen and define the Basin
square. The vertical alignment has utilised underlying landform to achieve grade
separation between north-south and east west routes. The width of the bridge has been
kept to a minimum that meets safe traffic design standards for a 50km/h road. Abutments
are integrated and grounded in the form and material of the landscaping. Lighting on the
bridge seeks to minimise glare and spill onto surrounding areas and integrates with the
bridge form and with the adjacent NWM Park. Architectural lighting is provided underneath
the bridge and across the landscape, highlighting forms, surfaces and textures of the
superstructure, undercroft, piers, abutments and landscape. The combination of treatments
and design promote the perception of the bridge being an elevated street rather than
motorway flyover.
The Project will result in a number of transport benefits for the State highway network and the local
road network (including public transport and walking and cycling) as well as new buildings,
structures and landscape treatments for the Basin Reserve area.
Construction of these transportation improvements is currently scheduled to start in 2014/15.
the rougher the road, the more speed affects the vibration amplitude. The effect of the suspension
system type also depends on vehicle speed and road roughness. For low speed and smooth road
conditions, the effect of the type of suspension system is not significant. However, for high speeds
and rough roads, the type of suspension system becomes important.
construction activity and traffic through to careful management of construction activities and traffic
speed and road condition once the Project is operational.
3 Methodology
2
Nyquist rate is the lowest sampling rate that will permit accurate reconstruction of a sampled analog signal.
3
Aliasing is an effect that causes different signals to become indistinguishable from each other during sampling and is
caused in analog to digital conversion by a too low rate of data sampling.
When considering baseline traffic vibration levels, we are interested in determining the range of
vibration levels presently being experienced by occupants of affected residences. Therefore, the
15 minute recording covered not only just traffic on SH1 but when there was also traffic movement
on adjacent local roads.
For all the main soil types encountered by the project, measurements of traffic induced ground
vibrations were able to be made at various distances from the source using the four accelerometer
array. This allowed an assessment of traffic induced vibrations resulting from the Project to be
inferred directly from measured rather than indirectly from predicted vibration levels derived from
vibrations measured at a known distance from the kerb in combination with an attenuation model.
Both BS 5228-2:2009 and DIN 4150-3:1999 provide guidelines based on Peak Particle Velocity
(PPV), which accounts only for vibration magnitude and not the exposure duration. As the
magnitude of traffic induced vibrations are directly a function of vehicle weight and speed (Hunaidi,
2000), a 15 minute measuring time interval was considered to be sufficient to obtain an estimate of
the likely upper limit vibration levels provided it coincided with free flow traffic conditions (i.e. when
speeds were at a maximum) and significant heavy commercial vehicle activity.
For this project, all measurements of traffic induced vibrations were made between 10:00am and
3:30pm, therefore avoiding the morning and afternoon peak time congestions but coinciding with
pick-up and delivery operations of commercial businesses.
With reference to Figure 8.4: and Table 8.8, it was possible to record at each location at least 5
high vibration events caused by the drive-by of heavy commercial vehicles. This is a sufficient
number to have confidence that a representative maximum has been captured.
The dropping of a sandbag was preferred to traffic for inducing ground vibrations used to
determine soil attenuation because the very short duration of the drop test made it much easier to
control for any traffic movements in the vicinity of the test site.
Rather than using a steel plate to replicate the falling weight deflectometer device used by Jackson
et al. (2008), a sandbag was utilised for the drop tests as it better represented the area source
characteristics of a roller compactor and also it minimised the likelihood of the drop weight
bouncing on impact and causing damage to footpaths and roads.
Furthermore, comparative testing involving drop tests using both a 25 kg sandbag and 25 kg metal
rail performed at Opus Central Laboratories prior to the field measurements being carried out
showed that the sandbag provided more reliable estimates of the power rate of attenuation.
Appendix 8C provides a summary of the results of the comparative drop tests performed by Opus
to identify differences between using a sandbag and a steel plate as the drop-weight.
With reference to Table 8.1, measurements were made at site S7 adjacent to a bridge pier of the
Wellington Urban Motorway’s 1335m long Thorndon overbridge to determine the likely magnitude
of traffic-induced vibrations at the foundation of the commercial building to be built at the corner of
Kent Terrace and Ellice Street under the proposed bridge structure. Because of the close proximity
of the vibration measurements to the source, the effect of any differences in soil characteristics
between Thorndon and Basin Reserve will be insignificant. Therefore, so long as concrete bridge
piers are utilised, the vibration levels measured at location S7 can be considered to be
representative.
Aerial photographs showing the approximate locations of the accelerometers at each test site are
included in Appendix 8A.
As previously mentioned in section 2.5, the locations of the accelerometer measurements were
selected to cover the Project areas having the greatest potential for large vibration amplitudes from
construction activity and operational traffic and also special interest areas, such as the Crèche (site
S5).
4 Assessment criteria
The only vibration related policies or rules contained in The Wellington City District Plan relate to
controlled activities in residential and rural areas4. Furthermore, where vibration related criteria
have been incorporated in district plans, these relate to either blasting activity or human comfort. In
the case of human comfort, district plan criteria have been taken from the withdrawn New Zealand
standard, NZS/ISO 2631 (1989): “Evaluation of Human Exposure to Whole Body Vibration, Part 2:
Continuous and Shock Induced Vibration in Buildings (1 to 80 Hz).” This standard considered
continuous, intermittent and transient vibrations as well as time of day. It also specified that
vibrations from traffic passing by should be treated as intermittent vibration in terms of the
standard.
In assessing the effects of vibration caused by the Project from the perspectives of human comfort
and damage to buildings and underground services, vibration guidelines contained in current
international standards were, therefore, used. These guidelines are discussed below.
The vibration levels in Table 8.2 are in terms of peak particle velocity (PPV), which is the vibration
parameter routinely measured when assessing potential building damage.
Although BS 5228-2:2009 is concerned with construction related vibrations, it is valid to apply the
guidance on effects of vibration levels given in this standard to traffic vibrations. This is because
most vibration frequencies associated with construction and traffic are greater than 8 Hz
eliminating any frequency dependency effects. As a result, there is complete agreement between
NZS/ISO 2631 (1989) and BS 5228-2:2009 for vibration levels that are just perceptible in the most
sensitive of situations (0.14 mm/s PPV) and just perceptible in residential environments (0.3 mm/s
PPV).
4
Wellington City District Plan, Volume 1:Objectives, Policies & Rules
• Chapter 5, Residential Rules, clauses 5.2.2.1; 5.2.2.6; 5.4.1.2
• Chapter 6, Suburban Centres, clauses 6.2.2.1; 6.2.3.3A
• Chapter 8, Institutional Precincts, clause 8.2.2.1
• Chapter 12, Central Area, clause 12.2.2.2
• Chapter 15, Rural Area, clause 15.4.1.2
• Chapter 24, Designations, Appendix V:Transmission Gully Motorway Designation, clause 7.10
5
Resonance is the condition occurring when a vibrating system is subjected to a periodic force that has the same
frequency as the natural vibrational frequency of the system. At resonance, the amplitude of vibration is a maximum.
Table 8.4: Guideline values for vibration velocity to be used when evaluating the effects of
long-term vibrations on structures (from German Standard DIN 4150-3 1999)
Guideline values for velocity in mm/s of
Line Type of structure vibration in horizontal plane of highest floor,
at all frequencies
Buildings used for commercial purposes,
1 industrial buildings, and buildings of similar 10
design
Dwellings and buildings of similar design and/or
2 5
occupancy
Structures that, because of their particular
sensitivity to vibration, cannot be classified under
3 2.5
lines 1 and 2 and are of great intrinsic value (e.g.
listed buildings under preservation order)
With reference to Tables 8.3 and 8.4, the German Standard DIN 4150-3 (1999) recognises
commercial buildings can withstand higher vibration levels than residential and historic buildings.
Also, the guideline values for short-term vibration increase as the vibration frequency increases.
Guideline values given in German Standard DIN 4150-3 (1999) for evaluating the effects of short-
term vibration on buried pipework and tabulated in Table 8.6 assume that the pipes have been
manufactured and laid using current technology. The standard also specifies that drain pipes
should be evaluated using the values in line 3 of Table 8.6.
When evaluating the effects of long-term vibration, such as vibrations generated by passing traffic,
German Standard DIN 4150-3 (1999) specifies that the guideline values given in Table 8.6 may be
reduced by 50%.
Table 8.6: Guideline values for vibration velocity to be used when evaluating the effects of
short-term vibration on buried pipework (from German Standard DIN 4150-3:1999)
Guideline values for velocity measured on
Line Pipe Material
the pipe, in mm/s PPV
1 Steel (including welded pipes) 100
Clay, concrete, reinforced concrete, pre-
2 80
stressed concrete, metal (with or without flange)
3 Masonry, plastic 50
Both standards fail to state the basis on which the guideline values were obtained, or the
frequencies at which these limits apply with regard to underground structures. However, recent
work by Thusyanthan et al (2006), has found that different pipe materials absorb different amounts
of energy in agreement with German Standard DIN 4150-3:1999.
With reference to Table 8.5 and Table 8.6, it will be noted that the guideline values specified in BS
5528-2:2009 for evaluating the effects of vibration on underground services are more stringent
than those specified in German Standard DIN 4150-3:1999 and so have been employed in this
assessment.
5 Measured vibrations
The recorded data was processed to give the resultant (vector sum) peak particle velocities (in
mm/s) for each triaxial accelerometer. This was done because no one component was consistently
dominant.
The guideline threshold values given in the standards used to assess the measured vibration
levels from the perspectives of human comfort and building damage (BS 5228-2:2009 and DIN
4150-3:1999), are generally based on the peak component (i.e. the worst case of the three axes
monitored). Therefore, by applying peak true vector sum PPV’s to the guideline threshold values is
not in accordance with the standards but results in the assessment of vibration effects being on the
conservative side.
Measured peak true vector sum values hereafter are referred to as peak particle velocities for
simplicity and to avoid possible confusion when applying the vibration criteria given in section 4.
Figure 8.4: Histogram of peak particle velocities (mm/s), due to traffic-induced vibrations,
within each 10-second period at testing Site S4 on the southern side of Paterson Street
Table 8.8: Measured peak particle velocities (mm/s) due to traffic-induced vibrations
Peak particle velocity (mm/s) Distance from road edge (m)
Site Location Event
A1 A2 A3 A4 A1 A2 A3 A4
S1a Corner of Ellice 1 0.36 0.40 0.38 0.52 18 13 8 3
St and Kent Tce 2 0.23 0.34 0.24 0.44 18 13 8 3
3 0.17 0.22 0.24 0.41 18 13 8 3
4 0.17 0.17 0.22 0.39 18 13 8 3
5 0.28 0.23 0.35 0.36 18 13 8 3
S1b Same as S1a 1 0.22 0.33 0.50 0.67 18 13 8 3
(repeat 2 0.25 0.35 0.49 0.52 18 13 8 3
measurement)
3 0.21 0.20 0.34 0.51 18 13 8 3
4 0.24 0.25 0.35 0.49 18 13 8 3
5 0.24 0.24 0.38 0.36 18 13 8 3
S3 Paterson St, 1 0.16 0.17 0.15 0.24 20 15 10 5
northern side 2 0.15 0.17 0.21 0.23 20 15 10 5
3 0.15 0.12 0.16 0.23 20 15 10 5
4 0.18 0.20 0.16 0.23 20 15 10 5
5 0.17 0.16 0.15 0.22 20 15 10 5
S4 Paterson St, 1 0.94 2
southern side 2 0.61 2
3 0.53 2
4 0.52 2
5 0.39 2
S5 Buckle St crèche 1 0.82 4.5
2 0.50 4.5
3 0.45 4.5
4 0.42 4.5
5 0.29 4.5
S6 Tory St 1 0.52 0.48 0.50 0.57 20 15 10 5
2 0.49 0.49 0.44 0.51 20 15 10 5
3 0.32 0.31 0.31 0.32 20 15 10 5
4 0.35 0.26 0.27 0.31 20 15 10 5
5 0.30 0.30 0.32 0.31 20 15 10 5
S7 Interislander 1 0.74 N/A
Ferry terminal car 2 0.66 N/A
park
3 0.59 N/A
4 0.45 N/A
5 0.41 N/A
Note: Columns A1, A2, A3, and A4 represent accelerometers 1, 2, 3, and 4 respectively. The
accelerometer at site S7 was placed adjacent to a load bearing pier beneath the north-bound lane
of the Wellington Urban Motorway (SH1) Thorndon overbridge.
With reference to Table 8.8, the largest peak particle velocities and their corresponding distances
from the road edge for site S1a are 0.52 mm/s at 3 m, 0.38 mm/s at 8 m, 0.40 mm/s at 13 m, and
0.36 mm/s at 18 m. According to the guidelines provided by British Standard BS 5228-2:2009 for
human comfort, all of these values fall above the threshold for perception (0.3 mm/s) but below the
threshold that will likely cause complaint (1.0 mm/s) within a residential environment. The same
was also true for all of the other locations tested.
The largest recorded peak particle velocity (0.94 mm/s) that was attributable to traffic-induced
vibration occurred at Site S4 on the southern side of Paterson St.
According to the guidelines provided by German Standard DIN 4150-3 1999, none of the peak
particle velocities that were attributable to traffic-induced vibration approached even the lowest
magnitude that could cause damage to a structure (2.5 mm/s).
Figure 8.5 shows the percentage of people with four levels of annoyance due to traffic induced
vibrations in dwellings, plotted against calculated statistical maximum values for weighted velocity
as provided by the Norwegian Standard NS 8176.E:2005.
Figure 8.5: Annoyance due to vibrations in dwellings plotted against calculated statistical
maximum values for weighted velocity, vw,95 (NS 8176.E:2005)
The value vw,95 is a statistical maximum calculated from the mean and standard deviation of the
frequency weighted root-mean-square (r.m.s.) vibration velocities. The frequency weightings for
r.m.s. velocities in the frequency range 10 Hz to 60 Hz is approximately 1. Outside of this range the
frequency weightings reduce the effective magnitude of the peak particle velocities. For this
investigation, the statistical maximum values for weighted velocities have not been calculated as
the highest spectral content fell well within the 10 Hz to 60 Hz range.
The peak particle velocities listed in Table 8.8 are the sum of all vibrations within the range 1 Hz to
80 Hz. In order to apply them to Figure 8.5, they must be converted from peak to r.m.s values by
dividing by √2. Furthermore, since they have not been weighted according to NS 8176.E:2005,
applying them to Figure 8.5 to obtain the percentage of building occupants who may be annoyed
by the vibration level, will result in a conservative estimate (i.e. higher percentage).
Considering the highest recorded traffic-induced ground vibration level 0.94 mm/s PPV that
occurred once on the south side of Paterson Street (site S4), this corresponds to a vw,95 value of
about 0.7 mm/s. With reference to Figure 8.5, about 11% of people are likely to be highly annoyed
by this level of vibration, whereas about 60% of people will perceive it.
Equation 8.1
where:
α is the site specific attenuation coefficient,
V1 is the peak particle velocity (mm/s) at distance R1 from the vibration source (m),
V2 is the peak particle velocity (mm/s) at distance R2 from the vibration source (m),
γ is the geometric attenuation coefficient (this is assumed to be 0.5 for Rayleigh waves,
which provides the most conservative attenuation coefficient).
For each test site, individual attenuation coefficients were calculated using every combination of
accelerometer pairs for each sandbag drop. The mean of all of the calculated attenuation
coefficients was then determined to provide the best estimate of the true site specific attenuation
coefficient. Table 8.9 shows the mean site specific attenuation coefficient for each of the test sites
and also when normalised for a frequency of 5 Hz to allow comparison with expected values for the
various soil classifications.
With reference to Table 8.9, the dominant soil frequency values range from 28 Hz to 56 Hz, with
soils displaying low attenuation tending to have higher values of dominant frequency.
Table 8.9: Estimated site specific attenuation coefficients
Attenuation Dominant Attenuation
Site Location Coefficient, Frequency (Hz) Coefficient
-1
α (m ) at 5 Hz
S1a Corner of Ellice St and Kent Tce 0.069 28 0.012
S1b Same as S1a (repeat measurement) 0.091 31 0.015
S2 Ellice St 0.071 38 0.009
S3 Paterson St, northern side 0.065 41 0.008
S6 Tory St 0.049 56 0.004
It should be noted that the second measurement at Site 1 (S1b) was carried out after a period of
rain that lasted multiple days. Due to the fact that the measurements at this site were made on soil,
the value for α determined during the first test (S1a) should be used as it is more conservative.
It should also be noted that the attenuation measurements were only made on the northern side of
Paterson Street for logistical reasons (i.e. there was no suitable location on the southern side to
mount the 20 m long array of accelerometers at right angles to the direction of traffic). However,
they are representative because the soil characteristics in this area are fairly consistent (refer the
geology map, sheet GE.2.01, in Volume 5).
With reference to Cenek et al (2012), 5 Hz attenuation coefficient values range between 0.01 and
0.03 for weak or soft soils and between 0.003 and 0.01 for competent soils. Therefore, test site S1
is on a weak or soft soil and test sites S2, S3 and S6 are on competent soils. This is in agreement
with the Project’s geology map (refer Volume 5, sheet GE.2.01, version R0 of NZTA 380PN
drawing issue for specialist assessment, 2 July 2012).
Equation 8.1 can be rearranged to give Equation 8.2. The attenuation coefficients can then be
inserted to calculate the estimated peak particle velocity at a specified distance from the vibration
source (V2 and R2 respectively) given a known peak particle velocity at a known distance from the
vibration source (V1 and R1 respectively).
Equation 8.2
.
When plotting square-root attenuation relationships It is usual to omit the gravitational constant g in
Equation 8.3 when square-root scaling the radial distance d. Therefore, the resulting independent
variable PPV is plotted against has units m/(kg.m)0.5 and is referred to as scaled distance. This
practice has been followed in this report and so the values A and n determined at each test site
and tabulated in Table 8.10 pertain to scaled distance in units of m/(kg.m)0.5.
The plots used to derive the values for A and n for each testing site are included in Appendix 8B.
When using data in Table 8.10 to predict vibrations from impact related construction activities, care
should be exercised as, with reference to Appendix 8C, the resulting levels are likely to be realistic
but may not represent the upper bound.
Table 8.10: Measured vibration magnitude attenuation parameters due to vibrations caused
by sandbag drops
Site Location A n
S1a Corner of Ellice St and Kent Tce 0.50 -1.07
S1b Same as S1a but wet ground 0.55 -1.45
S2 Ellice St 0.17 -1.31
S3 Paterson St, northern side 0.26 -1.11
S6 Tory St 0.19 -1.05
6 Discussion of results
For the Project, the bored piles will require the use of a steel casing to provide support to the soil
surrounding the borehole in order to prevent cave-in of the excavation and destabilising the
surrounding soil formation. The steel casing is typically driven using a vibratory hammer or
hydraulic casing oscillator to minimise noise and vibrations. On reaching the design depth, a
reinforcing cage is introduced and concrete is poured in the borehole and brought up to the
required level.
For the purposes of estimating the lower and upper bound vibration levels expected from bored
piling operations, vibration levels measured by Opus personnel during piling operations in the
Wellington region in similar soil conditions to that of the Project were utilised.
To estimate the lower-bound level, corresponding to a bored pile with oscillated steel casing,
vibration measurements of hard piling operations undertaken along the Waiwhetu Stream in 2009
were used as in this case the steel casing was already in place to secure the borehole. These
measurements covered the three stages of the piling operation: drilling; drill extraction; and drill
relocation (McIver and Cenek, 2009). The maximum vibration level measured at a distance of 5 m
from source was 4 mm/s PPV and the dominant frequency was around 70 Hz.
To estimate the upper-bound level, corresponding to a bored pile with vibrated steel casing,
measurements of a steel pile casing being driven during the construction of the Dowse Interchange
has been used (Sutherland and Cenek, 2007). In this case, a vibration level of 5 mm/s PPV with a
dominant frequency of about 18 Hz was measured at a distance of 14.5 m from the source.
For the Project’s bridge element, it is critical that vibrations generated during the construction of the
piers can be kept at levels that will not cause damage to the buildings that are closest to the piers.
These buildings are tabulated in Table 8.11, along with the estimated distance to the closest pier
and the estimated lower and upper-bound vibration level from the piling operation. Piers for the
pedestrian/cycle ramp in the vicinity of Ellice Street have also been included. The distances have
been scaled from drawings contained in Volume 4 and should be treated as indicative only as the
bridge pier layout plan has yet to be confirmed.
With reference to the lower-bound vibration levels tabulated in Table 8.11, the largest vibration
level is predicted to be 3.4 mm/s PPV and will occur at 15 Ellice Street (i.e. Regional Wines and
Spirits) during piling operations associated with the construction of the pedestrian/cycle ramp. This
level of vibration is significantly less than the German Standard DIN 4150-3:1999 threshold of 10
mm/s PPV for cosmetic damage to commercial buildings and is comparable to vibrations
generated by walking on a lively wooden floor (EPA, 2006). Therefore, it is unlikely that this level of
vibration will have an adverse effect on the operation of this business.
For the remaining buildings and structures of interest that are close to the Project’s bore piling
activity, vibration levels are calculated to not exceed 1.1 mm/s PPV. The estimated vibration levels
tabulated in Table 8.11 indicate that vibrations will reach perceptible levels at the RA Vance Stand
and at residential and commercial buildings in the vicinity of the eastern abutment of the bridge and
may cause annoyance to residents of the Grandstand Apartments (80-82 Kent Terrace) and 21
Ellice Street. However, there is no risk of structural or cosmetic damage.
Considering the upper-bound vibration levels tabulated in Table 8.11, the complaint threshold of 1
mm/s PPV will be exceeded at the Grandstand Apartments (80-82 Kent Terrace), Regional Wine
and Spirits (15 Ellice Street) and 21 Ellice Street. In fact, complaints can be expected from
occupants of buildings that are within 34 m of the piling activity if vibrated steel casings are
employed for the bored piles. There is also a risk of structural or cosmetic damage. Specifically,
the vibration level of 10 mm/s PPV, estimated at 15 Ellice Street is at the German Standard DIN
4150-3:1999 damage threshold for long-term vibration of commercial buildings whereas estimated
vibration levels at all the other buildings and structures considered are below the 5 mm/s PPV DIN
4150-3:1999 damage threshold for long-term vibration of residential buildings.
Table 8.11: Estimated vibration levels at properties most effected by bore piling operations
Location Property Distance to Estimated Vibration Level
Relative to Closest Pier (m) (mm/s PPV)
Bridge Lower-bound Upper-bound
Abutments
Western The Crèche 50 0.1 0.3
Abutment Relocated CS Dempster 192 <0.1 <0.1
Gate, Basin Reserve
RA Vance Stand, 22 0.7 2.6
Basin Reserve
Grandstand Apartments 16 1.1 4.5
(80-82 Kent Terrace)
Eastern Abutment St Joseph’s Church 54 <0.1 0.2
9 Dufferin Street 54 <0.1 0.2
Regional Wines & Spirits
(15 Ellice Street)
(i) Main bridge 24 0.6 2.2
(ii) Pedestrian/Cycle Ramp 8.5 2.4 10.0
21 Ellice Street:
(i) Main bridge 28 0.4 1.6
(ii) Pedestrian/Cycle Ramp 18 1 3.7
Taken overall, this analysis highlights the need to carefully manage any piling activity associated
with piers for the pedestrian/cycle ramp due to the close proximity of 15 and 21 Ellice Street and
piers 2, 3 and 4 of the SH1 bridge due to their closeness to the Grandstand Apartments. This will
require the selection of appropriate piling equipment and monitoring of the resultant vibrations as
detailed in the Construction Noise and Vibration Management Plan (CNVMP) contained in
Volume 4. It is also obvious from the above analysis that non-impact related piling operations such
as steel screw-in piling6 and bored piling using oscillators are preferable to impact related piling
operations such as drop mass impact hammer and vibratory hammer piling when piling is to take
place in close proximity to buildings as the magnitude of the resulting vibrations will be
considerably less.
Regarding typical road construction activity, such as breaking road surfaces, levelling ground and
earth removal etc., vibratory compaction is likely to be the main source of construction vibration
with the potential for adverse effects. With reference to BS 5228-2:2009, vibrations from vibratory
compaction are a function of the number of vibrating drums the roller has as well as the width and
amplitude of vibration of the drums. For example, vibrations measured at a distance of 5 m for a
10.5 tonne Sakai SV91T vibrating roller were about 8 mm/s PPV at low setting and 5 mm/s PPV at
high setting. By comparison, vibrations measured at the same construction site and distance from
source for a 7.5 tonne Hamm HD75 vibrating roller were 1 mm/s PPV at low setting and 2 mm/s
PPV at high setting (McIver and Cenek, 2011). This serves to illustrate that operation of vibratory
rollers at the high setting does not necessarily result in the magnitude of the induced ground
6
Screw piles are a type of deep foundation that can be installed quickly with minimal noise and vibration. Screw piles are
wound into the ground, much like a screw is wound into wood. This is an efficient means of installation and coupled with
their mechanism of dispersing load, provides effective in-ground performance in a range of soils, including earthquake
zones with liquefaction potential.
vibrations being greater than operation at the low setting. Therefore, equipment selection and
settings are important considerations when trying to mitigate construction related vibrations.
It is estimated that a minimum separation distance of 10 m from buildings will be required to keep
the resulting ground-borne vibrations below the complaint threshold of 1 mm/s PPV and to 4 m
(separation distance) to keep the resulting ground-borne vibrations below the cosmetic damage
threshold of 2.5 mm/s PPV. These separation distances are only indicative as they have been
derived assuming the lowest measured soil attenuation factor of 0.049 (i.e. worst case) and a
source vibration level of 2 mm/s PPV at a distance of 5 m, this being representative of excavators
and rollers operating in residential environments.
The only buildings located at a distance closer than 5 m from vibratory roller activity are in
Paterson Street and Dufferin Street. The specific buildings are listed in Table 8.12.
Table 8.12: Estimated vibration levels at properties most affected by vibratory roller activity
Estimated Vibration Level from Roller
Distance (mm PPV)
1
Building from
Vibratory Mode
Source (m) Static Mode
Representative Lowest Expected
St Marks
3.6 2.5 1.3 0.4
(Paterson St frontage)
St Joseph’s Church
4.2 2.3 1.2 0.3
(Paterson St frontage)
11 Dufferin St 4.6 2.1 1.1 0.3
St Marks Church Hall 4.6 2.1 1.1 0.3
With reference to Table 8.12, none of the buildings closest to vibratory roller activity will be at risk
of structural or cosmetic damage. However, the potential for these effects will need to be managed
through careful selection and operation of equipment as detailed in the CNVMP given in Volume 4.
For example, by using the lowest expected source vibration level of 1 mm/s PPV at a distance of 5
m (i.e. a Hamm HD75 vibrating roller operating at the low setting), the complaint threshold of 1
mm/s PPV may still be marginally exceeded during vibratory roller activity. If there is a desire to
maintain vibrations to below levels that may cause annoyance to building occupants (i.e. < 1 mm/s
PPV), then the only mitigation option available will be to operate the rollers in static mode (i.e. the
drum is not vibrated).
From McIver and Cenek (2011), the measured ground vibration at 5 m for rollers operated in static
mode ranged between 0.2 and 0.3 mm/s PPV, irrespective of roller mass. The upper value of 0.3
mm/s PPV and soil attenuation factor of 0.049 have been used to derive the static roller induced
vibration levels given in Table 8.12.
In considering the vibration levels tabulated in Table 8.12, it should be noted that these are
representative of new (i.e. greenfield) road construction and so are likely to be on the conservative
side when applied to realignment and resurfacing of existing roads, such as in the case of Dufferin
and Paterson Streets, since the same degree of compaction may not be required.
As Downers are the contractors for both the Memorial Park project and the Basin Bridge project, It
is recommended that the opportunity be taken to monitor vibration levels generated by vibratory
roller activity on the Memorial Park project to ensure that the magnitude of ground vibrations
generated by Downers preferred choice of vibratory roller are below the representative values
tabulated in Table 8.12.
Basin Bridge Project: Technical Report 8
Assessment of ground vibration effects
May 2013 8-28
Central Laboratories Report 12-5C1617.93
We can conclude that whilst the Project is within a dense urban environment and, therefore, results
in construction activity being very close to existing buildings, the only intrusive type of activity
identified has been associated with bore piling for the pedestrian/cycle ramp and compaction using
vibratory rollers in the vicinity of Paterson and Dufferin Streets. Fortunately, both construction
activities are of short duration (days rather than weeks). Therefore, if equipment selected by
Downers for these activities generate vibrations above the complaint threshold of 1 mm/s PPV in
the vicinity of occupied buildings, the activities should be timed, where practicable, so as to not
interfere with the occupants of the affected buildings. For example, the works could be undertaken
at night (Regional Wine and Spirits and St Marks School) or during school holidays (St Marks
School) or the residents provided with the option of staying somewhere else if they are given
sufficient prior warning as to when the potentially disturbing construction activity is to take place
(21 Ellice Street and 9 and 11 Dufferin Street).
In the case of vibratory roller activity in Paterson and Dufferin Streets, the vibratory roller could
alternatively be operated in static mode in this Project area (areas 5 and 6 in Table 8.1), resulting
in vibration levels that will be just perceptible but achieved at the expense of the construction of the
road taking longer to complete.
The CNVMP contained in Volume 4 explains how construction methodologies will be chosen and
how effects will be managed in accordance with the above.
building occupants will not become annoyed. For example, at 0.4 mm/s PPV, about 32% of
building occupants will be highly, moderately and slightly annoyed by this vibration level, whereas
at 0.8 mm/s PPV, this percentage increases to about 44%.
5 .
()*+,-).&/ 4 1 1 .45 Equation 8.4
3
14.5 .
.66+,-).&/ 51 1 .45
8. Equation 8.5
3
9%:: 3 !<=>?@ A:B# =BC:@ #?=C:! ?B$ $:BC! =C:A?@ #
Table 8.13 tabulates expected vibration levels at structures closest to the bored pile activity
associated with the northern gateway building calculated from equations 8.4 and 8.5.
Three different building lengths for the northern gateway building were considered: 45 m; 55 m;
and 65 m. The effect of increasing building length with respect to ground vibrations is to reduce the
separation distance to the nearest inhabited building, Grandstand Apartments, from 46 m to 41 m.
As can be seen from table 8.13, this results in the upper bound vibration level increasing from
0.4 mm/s PPV for the 45 m scenario to 0.5 mm/s PPV for the 55 m and 65 m scenarios. This
upper-bound value of 0.5 mm/s PPV is just above the perception threshold of 0.3 mm/s PPV but
below the complaint threshold of 1 mm/s PPV.
The other structure affected by the length of the northern gateway building is the historic Waitangi
Stream culvert, which is constructed from brick. Assuming that separation distances to the culvert
are measured along the ground, the 45 m scenario has a separation distance of about 12 m, the
55 m scenario is very close at 1.5 m and the 65 m scenario straddles the culvert (refer Figure 8.6).
British Standard BS 5528-2:2009 suggests that the maximum vibration level old brickwork
underground services should be subjected to is between 15 and 24 mm/s PPV. With reference to
table 8.13, only the 45 m scenario will result in the upper-bound vibration levels being below this
guidance value. Therefore, particular care will need to be taken with the foundations of the 55 m
and 65 m scenarios with respect to the location of the piles and the piling technique used to ensure
the historic Waitangi Stream culvert is subjected to vibration levels that will not result in adverse
effects. For example, if bored piling is to be used, a minimum slope distance of 6 m will need to be
achieved.
Figure 8.6: Location of historic Waitangi Stream Culvert relative to Basin Reserve northern
gateway building
Table 8.13: Estimated vibration levels at properties most affected by bored pile activity
associated with the northern gateway building
Estimated Vibration
Building Distance from Piling Level (mm/s PPV)
Location of Interest
Scenario Activity (m) Lower- Upper-
bound bound
RA Vance Stand 45 m, 55 m & 65 m 1 12 47
45 m 46 <0.1 0.4
Grandstand Apartments
55 m & 65 m 41 0.1 0.5
The Crèche 45 m, 55 m & 65 m 62 <0.1 0.1
Waitangi Stream Culvert 45 m 12 2 7
55 m 1.5 9 36
65 m 1 12 47
It is clear that it will be difficult to eliminate any risk of the structural integrity of the Waitangi Stream
culvert being comprised by the 55 m and 65 m scenarios for the northern gateway building. For this
reason it is recommended that if either of these scenarios proceeds, condition surveys should be
performed pre and post construction. As an extra precaution, vibration levels at the culvert should
be monitored during any piling activity associated with the foundation of the northern gateway
building to ensure guidance thresholds for structural damage are not exceeded.
With reference to Table 8.13, the only other building that will be affected is the RA Vance Stand.
The lower-bound vibration level at the RA Vance Stand is below the 20 mm/s PPV German
Standard DIN 4150-3:1999 damage threshold for short-term vibration of commercial buildings
(refer Table 8.3) but slightly above the 10 mm/s PPV German Standard DIN 4150-3:1999 damage
threshold for long-term vibration of commercial buildings (refer Table 8.4).
At the upper-bound estimate of 47 mm/s PPV, the 10 mm/s PPV German Standard DIN 4150-
3:1999 damage threshold for long-term vibration of commercial buildings is exceeded by a
considerable margin. To satisfy the short-term vibration damage criteria, the frequency of the
vibratory hammer used to drive the steel casing into the ground will have to be at least 85 Hz.
This analysis clearly indicates that if a vibratory hammer is used to drive the steel casing into the
ground, great care will have to be taken to ensure the frequency of vibration is appropriate for the
level of vibration measured at the foundation of the RA Vance Stand to prevent cosmetic damage
from occurring.
Given the proximity of the piling operation to the RA Vance Stand, there is a very high likelihood of
both the short and long term vibration damage criteria of German Standard DIN 4150-3:1999 being
exceeded when measured at the foundation of the RA Vance Stand, particularly if vibratory piling is
used and possibly if oscillatory piling is used. Therefore, it is recommended that a less invasive
form of piling, such as steel screw piles, be also considered for the foundations of the northern
gateway building.
This is also desirable from the perspective of ensuring ground vibrations in the vicinity of the
RA Vance Stand don’t reach levels that can cause consolidation or densification of the surrounding
soil. With reference to British Standard BS 7385:Part2:1993, soils can become vulnerable at PPV
values of about 10 mm/s, which corresponds to the German Standard DIN 4150-3:1999 guideline
value for evaluating effects of long-term vibration on commercial buildings.
As a consequence, selection of the piling technique used in the construction of the northern
gateway building’s foundation will be dictated by considerations of damage to the soil structure and
the RA Vance stand.
7
http://earthquake.usgs.gov/earthquakes/shakemap/background.php
historic Waitangi Stream Culvert for the 55 m and 65 m configurations of the northern gateway
building.
Given that the northern gateway building will butt up against the RA Vance Stand, it is also
advisable that a condition survey of the RA Vance Stand (including the player’s pavilion for the
65 m configuration of the northern gateway building) be carried out by a suitably qualified building
inspector pre and post construction of the northern gateway building as an additional precautionary
measure. Therefore, if any damage occurs from construction activity, whether it is piling or some
other activity, it can be identified and rectified.
Vibratory Piling 3
Oscillatory Piling 1
With reference to Table 8.14, it will be noted that the peak vibration level measured for the
vibratory piling is a factor of 3 higher than for the oscillatory piling confirming the vibration reduction
potential of oscillatory piling over the more commonly used vibratory piling.
More importantly, the measured vibration level of 1 mm/s PPV at a distance of 10 m for oscillatory
piling compares with the 2 mm/s PPV at a distance of 10 m assumed in making the assessment of
oscillatory piling activities associated with the Project. Similarly, the measured vibration level of 3
mm/s PPV at a distance of 10m for vibratory piling compares with the 8 mm/s PPV at a distance of
10 m assumed in making the assessment of vibratory piling activities associated with the Project.
Table 8.15 shows lower and upper bound estimates of vibration levels at properties most affected
by bore piling if vibration levels from vibratory and oscillatory piling operations at One Market Lane
could be replicated for the Project.
Table 8.15: Estimated vibration levels at properties most effected by bore piling operations
if vibration levels measured at One Market Lane could be replicated for the Project
Location Property Distance to Revised Vibration Levels
Relative to Closest Pier (m) (mm/s PPV)
Bridge Lower-bound Upper-bound
Abutments
(Oscillatory (Vibratory
Piling) Piling)
Western The Crèche 50 <0.1 0.1
Abutment Relocated CS Dempster 192 <0.1 <0.1
Gate, Basin Reserve
RA Vance Stand, 22 0.3 0.9
Basin Reserve
Grandstand Apartments 16 0.5 1.6
(80-82 Kent Terrace)
Eastern Abutment St Joseph’s Church 54 <0.1 <0.1
9 Dufferin Street 54 <0.1 <0.1
Regional Wines & Spirits
(15 Ellice Street)
(i) Main bridge 24 0.3 0.8
(ii) Pedestrian/Cycle Ramp 6 1.7 5.0
21 Ellice Street:
(i) Main bridge 28 0.2 0.6
(ii) Pedestrian/Cycle Ramp 18 0.5 1.3
With reference to Table 8.15, it will be noted that the lower bound values are now all well below the
complaint threshold of 1 mm/s PPV apart from 15 Ellice Street, which is a commercial building
(Regional Wine and Spirits). Therefore, if possible, piers associated with the pedestrian/cycle ramp
should be repositioned so that they are at least 10 metres away from 15 Ellice Street to achieve a
vibration level of just below 1 mm/s PPV at this location.
8 Conclusions
The primary conclusions arising from this assessment of ground vibrations generated by the
construction and operation of the Project are as follows:
1. There may be some short term disturbance to occupants of nearby buildings resulting from
construction activity. However, these disturbances are likely to be acceptable if proven
vibration management methods are applied, such as selection of appropriate equipment
and construction methodology and keeping affected parties informed as to when vibration
generating activity is to take place and its duration. These vibration management methods
have been incorporated in the draft Construction Noise and Vibration Management Plan
given in Volume 4.
2. The existing environment around the Basin Reserve is exposed to low level traffic-
induced vibrations from State Highway 1. These vibrations are considered to be
acceptable as they are within recognised guidelines for human comfort applied
internationally. The proposed project, once operational, will not result in any worsening
of existing traffic-induced vibration levels.
3. Buried services are expected to be exposed to maximum vibration levels of between 4
mm/s and 16 mm/s peak particle velocity (PPV) during construction and about 6 mm/s
PPV once the Project is operational. By comparison, the maximum level of intermittent
and transient vibrations that underground services should be subjected to is 30 mm/s
PPV if in good condition or 15 mm/s PPV if old or dilapidated according to British
Standard BS 5228-2:2009. Therefore, ground vibrations generated by construction
activities can be easily tolerated if the buried pipework is not old or in a dilapidated
condition. Because of the historic nature of the brickwork Waitangi Stream culvert, it
would be prudent to perform condition surveys pre and post construction of the Project
to ensure no change to its structural integrity takes place. In addition, vibrations should
be monitored, as detailed in the Construction Noise and Vibration Plan (CNVMP),
whenever piling activity occurs in close proximity to the culvert to ensure vibrations
measured on the culvert are below levels that could cause structural damage or
settlement of the ground surrounding the culvert. Once the Basin Bridge becomes
operational, all the buried services will be exposed to traffic induced vibrations that will
be of the same magnitude as a present.
4. Foundations for the two proposed new buildings, one to be erected within the Basin
Reserve immediately adjacent to the RA Vance Stand (northern gateway building) and
the other to be erected at the intersection of Ellice Street with Kent Terrace
immediately adjacent to the Grandstand Apartments ( building under the bridge), will
most likely need to be piled. Therefore, care will have to be taken in selecting a method
of piling that creates minimum soil disturbance to prevent any vibration-induced
building damage from occurring. An international literature search and New Zealand
experience suggests that both steel screw-in piling and bored piling using oscillators
are two techniques that are able to generate vibration levels that comply with guidance
thresholds in standards for avoiding damage to nearby structures.
5. For the Basin Bridge project, the bored piling operations associated with bridge piers
have the potential to generate problematic vibrations, the driving of steel casings in
particular. Therefore, there is a need to select the most appropriate casing driving
technology for the soil conditions expected to be encountered to ensure any
disturbance of the soil surrounding the pile borehole is minimised. Experience under
Wellington conditions indicates that steel casings driven by a hydraulic casing oscillator
generates vibrations whose magnitude is about a third of those when driven by a
vibratory hammer highlighting the effect equipment selection can have.
6. A draft Construction Noise and Vibration Management Plan has been prepared (refer
Volume 4), which provides a methodology for managing ground vibrations resulting
from construction activities associated with the Project. The objective of this plan is to
minimise damage due to construction vibration by all reasonable and feasible means
possible. Therefore, there is specific consideration of the two activities identified as
having the potential for adverse effects: (i) piling associated with the bridge piers and
foundations of the two proposed buildings and (ii) vibratory compaction. The plan also
considers how the construction vibrations will be monitored to ensure compliance with
the established vibration thresholds for minimising structural damage. Central to this
plan is the need for the contractor to demonstrate that vibration levels assumed in
making the assessments presented in this report will not be exceeded by the
equipment that will be used on the Project.
7. Overall, the operation of the Project will not generate any adverse vibration effects,
provided current road maintenance management practices are maintained. Similarly,
no adverse vibration effects are expected to result during the temporary construction
period on account of the Construction Noise and Vibration Management Plan being in
place to ensure compliance with the established vibration thresholds.
The following secondary conclusions have been derived from the vibration measurements made
on 26th and 30th April 2012.
1. According to British Standard BS 5228-2:2009, for human comfort the largest
measured peak particle velocities due to traffic-induced vibration for all testing sites fall
between the threshold for perception (0.3 mm/s PPV) and the threshold that will likely
cause complaint (1.0 mm/s PPV) within a residential environment.
2. According to the guidelines provided by German Standard DIN 4150-3 1999, none of
the peak particle velocities that were attributable to traffic-induced vibration
approached even the lowest magnitude that could cause damage to a structure (2.5
mm/s PPV).
3. The largest peak particle velocities recorded generally represent rare events.
4. Greater care in managing construction and traffic-induced vibrations will be required in
the areas of weak soils (i.e. marginal marine sediments and reclaimed landfill in the
vicinity of Cambridge and Kent Terraces) than competent spoils (i.e. alluvium based
soils in vicinity of Buckle, Sussex and Ellice Streets). This is because impact loads, for
example from vibratory compaction, cannot be accommodated by weak soils as well as
competent soils.
5. Vibrations induced by traffic once the Project is completed are unlikely to be any
different from present provided that the same speed limits and maintenance practices
with regard to road surface roughness are maintained and the separation distance
between a building and the realigned road is at least 4 m (as shown on the drawings).
9 References
Block, J. (2013) Market Lane piling noise and vibration, Memorial Park Alliance Memorandum
dated 7 March 2013.
British Standard, BS 5228.2:2009. Code of practice for noise and vibration control on construction
and open sites – Part 2: Vibration.
British Standard, BS 7385:Part 2:1993. Evaluation and measurement for vibration in buildings. Part
2. Guide to damage levels from groundborne vibration.
Cenek, P.D., Sutherland, A.J. and McIver, I.R.(2012) Ground Vibration from Road Construction,
NZ Transport Agency Research Report 485, downloadable from:
http://www.nzta.govt.nz/resources/research/reports/485/index.html
Dowding, C. H. (2000). Construction Vibrations (2nd ed.) Prentice Hall
EPA (2006). Environmental Management Guidelines: Environmental Management Guidelines in
the Extractive Industry (Non-Scheduled Minerals), Environmental Protection Agency,
Ireland, downloadable from:
http://www.epa.ie/downloads/advice/general/epa_management_extractive_industry.pdf
German Standard, DIN 4150-3:1999. Structural Vibration – Part 3: Effects of vibration on
structures.
Hunaidi, O. (2000). Traffic Vibrations in Buildings, Construction Technology Update No.39, Institute
for Research in Construction, National Research Council of Canada, Ottawa.
International Standard, ISO 26321-2:1989. Evaluation of human response to whole-body vibration
– Part2: Continuous and shock-induced vibration in buildings (1 to 80 Hz).
International Standard, ISO 4866:2010. Mechanical vibration and shock – Vibration of fixed
structures – Guidelines for the measurement of vibrations and evaluation of their effects on
structures.
International Standard, ISO 8041:2005. Human response to vibration - Measuring instrumentation.
Jackson, N.M., Choubane, B., Lee, H.S., Holzschuher, C., Hammons, M.I. and Walker, R. (2008).
Recommended Practice for Identifying Vibration-Sensitive Work Zones based on Falling
Weight Deflectometer Data, Transportation Research Record No 2081, pp.139-149.
McIver, I.R. and Cenek, P.D (2009). Vibration Assessment: Waiwhetu Stream Seaview, Opus
Central Laboratories Report 09-29B38.00.
McIver, I.R. and Cenek, P.D. (2011). Bridge Street Retaining Wall: Assessment of Roller Induced
Ground Vibrations, Opus Central Laboratories Report 11-6CM015.04.
Norwegian Standard NS 8176.E:2005 (2nd ed.). Vibration and Shock. Measurement of vibration in
buildings from landbased transport and guidance to evaluation of its effects on human
beings. Standards, Norway, 2005. English translation version, 2006.
Schilling, R.A. and Harris, S.L. (2011) Fundamentals of Digital Signal Processing Using Matlab
Second Edition, Florence, KY: Cengage Learning, pp. 611-617
Sutherland, A.J. and Cenek, P.D. (2007). Vibration Assessment: Dowse Interchange, Opus Central
Laboratories Report 07-522432.39.
Thusyanthan, N.I., Chin, S.L.D. and Madabhushi, S.P.G. (2006). Effect of Ground Borne Vibrations
on Underground Pipelines. Proceedings of the International Conference on Physical
Modelling in Geotechnics 2006, Hong Kong, pp. 753-758.
Xu,L. (2005). Site Investigation of the Dynamic Behaviour of the ISPAN Floor System, University of
Waterloo, Ontario, Canada, downloadable from:
http://www.totaljoist.com/Assets/pdfs/TechDetails/SIDBR.pdf
y = 0.4974x-1.073
10
0.1
0.01
0.1 1 10
Scaled Distance (m/(kg.m)0.5)
Figure 8B2: Peak particle velocity vs scaled distance – Site S1b – Corner of Ellice St and
Kent Tce
100
Peak Particle Velocity (mm/s)
y = 0.5481x-1.45
10
0.1
0.01
0.1 1 10
Scaled Distance (m/(kg.m)0.5)
10
y = 0.1683x-1.308
1
0.1
0.01
0.1 1 10
Scaled Distance (m/(kg.m)0.5)
Figure 8B4: Peak particle velocity vs scaled distance – Site S3 – Paterson St, northern side
100
Peak Particle Velocity (mm/s)
10
y = 0.2583x-1.105
1
0.1
0.01
0.1 1 10
Scaled Distance (m/(kg.m)0.5)
10
y = 0.1884x-1.053
1
0.1
0.01
0.1 1 10
Scaled Distance (m/(kg.m)0.5)
Table 8C1: Measured vibrations for metal rail and sandbag drop-weights
Impact Hammer
25 kg Metal Rail 25 kg Sandbag
Distance
(m) Scaled Scaled
PPV PPV
Distance Distance
(mm/s) (mm/s)
(m/(kg.m)0.5) (m/(kg.m)0.5)
2 0.60 33.03 0.40 1.63
7 2.09 0.35 1.40 0.31
12 3.58 0.17 0.72 0.14
17 5.07 0.11 3.40 0.11
The following model was fitted to the data summarised in Table 8C1:
! &
A 1 Scaled Distance& Equation C1
√#. %
where:
A is coefficient related to the nature of the impact
d is the radial distance from the vibration source in metres
m is the mass of the impacting body in kg
h is the height that the impacting body is dropped from in metres
n is the power rate of attenuation
Table 8C2 below lists the values A and n determined using measurements from all 4 measured
locations (i.e. covering distances between 2m and 17m from the impact) and from the 3
furthermost locations (i.e. covering distances between 7m and 17m from the impact). The analysis
was repeated with the closest vibration reading removed because the surface or Rayleigh waves
generated by the impact does not fully form until some finite distance from the impact. Therefore,
the effect of excluding the reading at 2m on the model coefficients could be investigated.
With reference to Table 8C2, it will be observed that when the sandbag is used as the impact
hammer there is not a significant change in model coefficients irrespective if all of if just the three
furthermost readings are utilised. Also, there is good agreement between the sandbag derived
value of power rate of attenuation (n) and that derived with the metal rail using the three
furthermost data points. However, Table 8C2 highlights that the value of coefficient A is very much
related to the nature of the impact, with the metal rail giving values 2 to 12 times greater.
On the basis of the results presented in Table 8C2, the sandbag was selected as the preferred
impact hammer for drop tests because, unlike the metal rail, estimates of the power rate of
attenuation were not greatly influenced by the distance to the closest measurement location. The
other advantages of the sandbag were:
• less scatter in the measured PPV values
• no bounce on impact to affect the readings
• less likelihood of damage to surfaces
However, there is need to exercise care when applying predictor curves derived from sandbag
tests as the estimates of expected vibrations, while being realistic, are unlikely to be at the upper
bound.