Professional Documents
Culture Documents
JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, VOL. XX, NO. XX, XX XXXX 1
Abstract—
—The single-line-to-ground faults with line breaks due to meteorological disasters, overloading wires; and me‐
(SLGFs-LBs) occur more and more frequently in distribution chanical disruptions [3], single-line-to-ground faults with
networks and can cause major safety accidents. It is difficult to
line breaks (SLGFs-LBs) occur more and more frequently in
distinguish the single-line-to-ground faults (SLGFs) in resonant
grounding systems and ungrounding systems due to the same recent years. SLGFs-LBs exhibit the same voltage and cur‐
electrical characteristics at the source side and uncertain opera‐ rent characteristics as SLGFs before the fault point, so it is
tion conditions of distribution networks. This paper proposes a difficult to distinguish them at substations. SLGFs-LBs can
method for distinguishing SLGFs-LBs and SLGFs. First, the go undetected for hours in small-current grounding systems
source-side and load-side voltage characteristics of SLGFs and but the consequences caused by SLGFs-LBs, such as over‐
SLGFs-LBs are analyzed, and the phase difference between the
voltages of the fault phase and non-fault phase at the load side voltages [4] and step voltages [5], are serious. Moreover, the
is selected as the identification criterion. Phasor measurement resulting fires and electric shocks could cause injuries and
units (PMUs) are selected as measuring devices. Then, the ef‐ even deaths. Therefore, the effective SLGF-LB identification
fects of operation conditions and external devices in distribu‐ is the key to reducing its threat to lives and property of peo‐
tion networks on the proposed method are discussed, and the ple.
phase errors caused by them are calculated to correct the identi‐
fication method. Finally, the field testing and simulation experi‐ Researchers have already paid much attention to various
ments are conducted to verify the effectiveness and robustness short-circuit faults and made many achievements [2], [5],
of the proposed method. [6]. However, due to the unobvious fault characteristics and
Index Terms— —Distribution network, single-line-to-ground lack of relevant experience on SLGF-LB in the actual opera‐
fault with line breaks (SLGF-LBs), single-line-to-ground fault tion of distribution networks, few studies have been conduct‐
(SLGF), identification method, influencing factor. ed on the SLGF-LB identification and there is no relay pro‐
tection device for SLGFs-LBs in distribution networks [7].
In recent years, with the increasing frequency of SLGFs-LBs
I. INTRODUCTION and development of distribution automation systems, SLGFs-
F AULTS in distribution networks are the root cause of LBs have gradually aroused the attention of researchers. So
more than 80% of outages in power systems [1]. There‐ far, two kinds of identification method for SLGFs-LBs have
fore, small-current grounding systems, including resonant been proposed. One is based on the combination of electrical
grounding systems and ungrounding systems, are widely parameters, which could be calculated by theoretical deriva‐
used in medium-voltage distribution networks around the tion at different locations in the distribution network. For ex‐
world, since they can keep running for a few hours after sin‐ ample, in [3], the source-side sequence currents are used as
gle-line-to-ground faults (SLGFs), which account for 80% of the criterion to locate and identify the fault lines and the
total number of faults in distribution networks [2]. However, source-side and load-side three-phase voltage amplitudes are
selected to detect SLGFs-LBs. References [7] and [8] take
the amplitudes and phases of three-phase currents before and
Manuscript received: May 11, 2021; revised: September 17, 2021; accepted:
January 2, 2022. Date of CrossCheck: January 2, 2022. Date of online publica‐ after a fault as the main criterion to detect SLGFs-LBs, and
tion: XX XX, XXXX. the amplitudes of three-phase voltages are taken as an auxil‐
This work was supported in part by National Science Foundation of China un‐ iary criterion to identify whether the fault is grounded or not
der Grant (No. 51707117).
This article is distributed under the terms of the Creative Commons Attribu‐ and the location of grounding point. Reference [9] studies
tion 4.0 International License (http://creativecommons.org/licenses/by/4.0/). the electrical characteristics of negative-sequence current, ze‐
Y. Liu (corresponding author), Z. Li, Y. Yan, G. He, K. Li, and X. Jiang are ro-sequence current, and the three-phase voltages at the load
with Institute of Intelligent Power Transmission and Distribution. Shanghai Jiao
Tong University, Shanghai 201100, China (e-mail: lyd@sjtu. edu. cn; side when SLGFs-LBs occur based on the actual operation
lzc940872816@sjtu. edu. cn; yanyingjie@sjtu. edu. cn; heguanghui@sjtu. edu. cn; data of distribution networks. The other one is to process
fjenglish@163.com; 397455963@qq.com). monitored electrical data through big data technology or ma‐
J. Fang is with the Electric Power Test Institute of Guangzhou Power Supply
Bureau Co., Ltd., Guangzhou 510420, China (e-mail:: XCjiang@sjtu.edu.cn). chine learning methods. Reference [10] extracts the voltage
DOI: 10.35833/MPCE.2021.000288 and current characteristics at the primary side of distribution
2 JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, VOL. XX, NO. XX, XX XXXX
transformers after SLGFs-LBs occur at the medium-voltage The rest of this paper is organized as follows. Section II
side in the distribution networks and the association-rule al‐ calculates the source-side and load-side three-phase voltages
gorithm is selected as the identification method. However, of SLGFs and SLGFs-LBs and analyzes their characteristics.
due to the limitation of application scenarios and incomplete The identification method for SLGFs-LBs based on load-
development, big data technology or machine learning meth‐ side three-phase voltages is proposed and its influencing fac‐
ods has not been widely used in the distribution network. tors are listed and calculated in Section III. Section IV con‐
The aforementioned detection methods for SLGFs-LBs se‐ sists of simulation and field testing experiments, and the re‐
lect a variety of electrical parameters at different locations sults verify the effectiveness and robustness of the proposed
as the identification criteria for SLGFs-LBs, and have cer‐ identification method. Section V concludes this paper.
tain reference values. However, the robustness of these iden‐
tification methods could be reduced by influencing factors in II. VOLTAGES CHARACTERISTICS OF SLGFS
practical distribution networks [11], [12]. For example, the AND SLGFS-LBS
practical distribution networks do not operate under ideal
Since the radial distribution networks are the most widely
conditions because problems such as network imbalance and
used around the world [22], the analysis in this paper is
frequency fluctuation are common. In addition, with the de‐
based on the distribution network powered by a single
velopment of distribution networks, load types and their
source. The equivalent circuits of SLGF and SLGF-LB are
switching become more and more frequent, which will lead
shown in Fig. 1(a) and (b), respectively. The SLGF and SL‐
to the frequent and severe fluctuations of three-phase cur‐
GF-LB are both single-line faults, but they are different at
rents and power factor in distribution networks. Some of
fault point F. The fault line of the SLGF is grounded
them can even inject high-order voltage and current harmon‐
through a resistance R 0 at F. However, the fault line of the
ics into distribution networks.
SLGF-LB is broken at F and grounded through resistances
In short, a simple, effective, and robust identification
R 1 and R 2. In Fig. 1, C denotes the three-phase grounding ca‐
method should be proposed to distinguish SLGFs-LBs and
pacitances; O is the zero-potential point; and N is the neutral
SLGFs. Firstly, the suitable parameters should be selected as
point; E A, E B, and E C are the three-phase voltages; and L is
the identification criteria. The fundamental reason for the
the inductance of the arc suppression coil for resonant ground‐
high concealment of SLGFs-LBs is that the electrical charac‐
ing systems, in particular, L is ∞ for ungrounding systems.
teristics of SLGFs-LBs are almost the same as those of SL‐
GFs at the source side, which makes it difficult to distin‐ EA
Load
guish SLGFs and SLGFs-LBs. Therefore, the load-side elec‐ ~
trical parameters could be considered as the identification cri‐ EB
teria. Since the power system frequency monitoring network N
~
(FNET) was proposed in 2005 [13], the construction of wide EC
area measurement system (WAMS) based on advanced local- F
~
area measurements that can realize synchronized measure‐
L R0
ment has made great progresses around the world [13], [14]. C C C
So far, the advanced local-area measurements such as phasor O
measurement units (PMUs) have recently been introduced as (a)
an efficient and powerful tool for real-time monitoring of dif‐ EA
ferent locations of distribution networks [15]. PMUs have en‐ Load
~
tered the field of distribution network automation system, EB
and will definitely serve more application scenarios in the fu‐ N
~
ture [16] - [18]. In addition, considering the huge cost of in‐ EC
stalling PMUs at each bus or each side of lines in distribu‐ ~ F
tion networks [19], the branch PMU, which has multiple
channels and can monitor several branch lines at the same L C C CC1 CC2
R1 R2
time [20], could be installed at the intersection of multiple
branch lines and selected as the measuring device to save O
costs. This paper proposes a criterion to distinguish SLGFs- (b)
LBs and SLGFs based on characteristics of the load-side Fig. 1. Equivalent circuits of SLGF and SLGF-LB. (a) SLGF. (b) SLGF-
three-phase voltages in distribution networks. The phase an‐ LB.
gle between the fault phase voltage and the vector sum of
non-fault phase voltages at the load side is used as the crite‐
ria for the identification method, since PMU could realize A. Voltage Characteristics of SLGFs
high-resolution measurement of the phase angle of voltage Figure 1(a) illustrates the equivalent circuit of an SLGF,
[21]. Factors affecting the accuracy of the proposed criterion where the far-right node is connected to the load and phase
such as operation conditions and external devices are consid‐ C is grounded through resistance R0. Assuming that ν is the
ered to improve the robustness of the proposed identification compensation degree of distribution networks, the relation‐
method. ship between the voltage of neutral point UNg and EC is cal‐
LIU et al.: IDENTIFICATION METHOD FOR SINGLE-LINE-TO-GROUND FAULTS WITH LINE BREAK BASED ON PHASOR MEASUREMENT... 3
culated as: As shown in Fig. 2, for SLGFs, the fault phase voltage
EC and the sum of non-fault phase voltages at the load side are
= -1 - jR 0 B C v (1) U Cg and U ABg = U Ag + U Bg, respectively. It can be observed
U Ng
that the phase difference between U Cg and U ABg is θ =
where B C = 3ωC represents the three-phase susceptance of ∠MOP = 90° + α, where α is the angle between UCg and line
the distribution lines. To avoid the resonance during a fault, JK, and JK is the auxiliary line perpendicular to UABg. Since
the power system is over compensated [2], i. e., ν < 0. The R0 and α are greater than 0, we have θ = 90° + α > 90°. Conse‐
term -1 - jR 0 B C v has a negative real part and a negative quently, |θ| is larger than 90° for SLGFs. From Fig. 2, it is
imaginary part due to the overcompensation. Thus, EC is concluded that α will increase from 0° to 90° as zero-poten‐
ahead of UNg by 90°-180°. tial point O moves from M to N.
The vector diagram of SLGFs is shown as Fig. 2. We take
the three-phase voltages EA, EB, and EC as the references. B. Voltage Characteristics of SLGFs-LBs
Thus, the neutral point N is fixed and the location of the ze‐ Unlike SLGFs, a distribution line break due to a SLGF-
ro-potential point O is associated with the grounding resis‐ LB might bring different voltage characteristics at the source
tance R0. When R0 increases from 0 to ∞, the zero-potential and load sides. As shown in Fig. 1(b), the grounding resis‐
point O moves from M to N through a semicircle, and the tances at the source and load sides are R1 and R2, respective‐
trajectory of the zero-potential point O is located at the left ly; the grounding capacitance of fault phase at the source
side of MN. Note that, for SLGFs, the source-side three- and load sides are CC1 and CC2, respectively; and the ground‐
phase voltages to the grounding points UAg, UBg, and UCg are ing capacitance of non-fault phases is C. The relationship be‐
equal to the load-side three-phase voltages due to direct con‐ tween the voltage of neutral point UNb and EC during an SL‐
nection of distribution lines. GF-LB is calculated as:
EC
K = -1 - jR 1 B C v (2)
M U Nb
UCg EC
α where B C = 2ωC + ωC C1.
O Based on (2), considering the overcompensation in distri‐
J bution networks, the vector diagram of the SLGF-LB at the
α
load side is shown in Fig. 3; where U Ab, U Bb, and U Cb are
UNg Capactive area the load-side voltages of phases A, B, and C, respectively.
Inductive area M
UCb EC
N
O
UBg UAg
EB EA
UNb
UBb UAb
EB EA
The equivalent load impedance Zk consists of resistance ble I presents the typical properties of distribution lines and
Rk, inductance Lk, and capacitance Ck. Hence, UCbl is used to overcompensation degree in 10 kV radial distribution net‐
distinguish the load-side voltage of phase C, which can be works. In order to reserve some margin, R min = 125 Ω is se‐
expressed through a simplified model as shown in Fig. 4. lected as the critical point of the minimum grounding resis‐
The simplified load-side model is an RLC circuit formed by tance. When R min = 125 Ω, |θ| for SLGFs and SLGFs-LBs
three elements, namely, Rk+R2, Lk, and Ck. can be calculated as 93.02° and 86.12° by (1) and (4), re‐
Ck
spectively. Note that, according to (4), only the load-side
Lk Rk R2
grounding resistance R2 should be considered in the above
UAb+UBb UCbl calculation process of |θ| for SLGFs-LBs; therefore, θ 1 =
93.02°, and θ 2 = 86.12°. And θ 1 and θ 2 deviate farther from
Fig. 4. Simplified load-side model of SLGF-LB.
each other as Rmin increases. According to the design limita‐
tion of relay protection devices, the identification method
According to Fig. 4, UCbl can be calculated as: mentioned above may fail when the value of grounding resis‐
R 2 (U Ab + U Bb ) tance approaches the critical point.
( )
U Cbl =
2 TABLE I
1 (3)
2πfL k - + (R 2 + R k )2 (cos θ + j sin θ) TYPICAL PROPERTIES OF DISTRIBUTION LINE AND OVERCOMPENSATION
2πfC k DEGREE
nal devices can be summed to obtain θ 1 and θ 2. According which may lead to the overlap of the two criterion intervals.
to the analysis in Section III-A and III-B, the errors caused Therefore, the critical errors should be selected according to
by operation conditions and external devices are summarized the maximum expansion criterion intervals. As shown in Ta‐
in Table II. These errors will result in the expansion of the ble II, factors other than power factor will affect SLGFs and
intervals of θ for distinguishing SLGFs and SLGFs-LBs, SLGFs-LBs in different ways.
TABLE II
PROPERTIES OF FACTORS AFFECTING θ 1 AND θ 2
θ 1 and θ 2 can be calculated through summing up phase er‐ in field experiments. Therefore, the purpose of field experi‐
rors. Therefore, Errors for θ 1 and θ 2 are calculated as −4.84° ments is to verify the adaptability of the identification meth‐
and − 1.5° , respectively. Referring to Table II, the rounding od in Section II to different topologies and parameters of dis‐
calculation results of θ 1 and θ 2 are 88° and 86°, respectively. tribution networks, i.e., different grounding methods, ground‐
The margins of the selected thresholds are 0.18° for θ 1 and ing points, and grounding resistances.
0.52° for θ 2, which indicate that the thresholds of residuals
between actual values and theoretical calculation values of T0
θ 1 and θ 2 for SLGFs and SLGF-LBs under the combined in‐
fluence of multiple influencing factors. According to the L7 L6 L5 L4 L3 L2 L1
analysis above, the identification method can be corrected PMU PMU PMU PMU PMU PMU
as: ① when |θ| has a range of [89°, 180°], an SLGF occurs; M6-1 M5-1 M4-1 M3-1 M2-1 M1-1
② when |θ| has a range of [0°, 86°], an SLGF-LB occurs.
F
Considering the longest duration of low-voltage ride- T2 T1
through for DERs, |θ|, which is measured with a duration of PMU PMU
at least 20 s after the fault occurs, can be used for distin‐ C4 C3
…
…
M2-2 M1-2
…
…
guish SLGFs-LBs and SLGFs. Compared with the allowable
running time (1-2 hours) of SLGFs in small-current ground‐ Resonant Ungrounding
C2 C1
ing systems, the duration of 20 s is small. Therefore, the pro‐ grounding system
…
system
posed method can effectively reduce the running time of SL‐
GFs-LBs. Fig. 7. Topological structure of testing power system.
IV. EXPERIMENTAL AND SIMULATION RESULTS The PMU used in this experiment is designed by Shang‐
To verify the effectiveness and robustness of the proposed hai Jiao Tong University (SJTU). Typical parameters of each
identification method for SLGFs-LBs, field experiments and PMU are illustrated in Table III. The power supply mode of
simulation experiments are conducted in this paper. Field ex‐ these PMUs is inductive energy acquisition plus lithium bat‐
periments focus on the validation of theoretical results in tery [32]. One PMU is equipped at the beginning of each
Section II, while simulation experiments aim to verify the ro‐ outgoing line. The data collected by the PMUs are transmit‐
bustness of the proposed identification method. ted through wireless communication (4G in this case) to the
workstation. The data are used for fault identification and
A. Experimental Environment and Results the crew is notified of results. For L1 and L2, a PMU is re‐
Field experiments are conducted at a real-world testing quired at the load side. Since the proposed identification cri‐
base in Henan, China. The topological structure of the test‐ teria is three-phase steady-state voltage, the accuracy of mea‐
ing power system is shown in Fig. 7. The rated voltage is 10 surement is not affected by the sampling frequency if the
kV and the power frequency is 50 Hz. For outgoing lines sampling rate satisfies Nyquist sampling theory. According
L1, L2, L3, and L4, three-phase capacitors C1, C2, C3, and to the engineering practical experience [31] and rated param‐
C4 are installed as capacitive loads, respectively, and C 1 = eters of the chosen PMUs [32], the sampling rate of the
2 μF, C 2 = C 3 = 4 μF, and C 4 = 0.8 μF. At L7, the neutral point PMUs is set to be 4 kHz. The fault point F is located on L2.
could be ungrounded or resonant grounded with a − 7.7% Both the source-side and load-side grounding resistances are
compensation degree. Considering the limitations of experi‐ adjustable through the resistance cabinet. The three-phase
mental equipment and the safe operation of the experimental load is purely capacitive. Figure 8 shows the schematic dia‐
distribution system, the influencing factors are not included gram of fault generator and the physical pictures.
LIU et al.: IDENTIFICATION METHOD FOR SINGLE-LINE-TO-GROUND FAULTS WITH LINE BREAK BASED ON PHASOR MEASUREMENT... 7
|θ|/(°)
93.02°
|θ|/(°)
100 0.15
Sam‐ Voltage Current Measure‐ 50 86.12° 0.10
Running Clock syn‐ 0.05
pling measure‐ measure‐ ment
current chronization
frequen‐ ment ment accuracy 0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
(A) mode
cy (kHz) range (kV) range (A) (%) Grounding resistance (Ω) Grounding resistance (Ω)
GPS/ (a) (b)
[1, 4] [0, 30] [0, 600] ≤0.5 [5, 600]
Beidou 200 0.30
150 0.25
96.02° 0.20
|θ|/(°)
|θ|/(°)
100 0.15
Break switch 50 86.12° 0.10
0.05
PMU PMU
M2-1 M2-2 0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
R0(R1) R2 Grounding resistance (Ω) Grounding resistance (Ω)
(c) (d)
|θ| for SLGF; |θ| for load-side grounding SLGF-LB
Fault generator |θ| for source-side grounding SLGF-LB
(a) Fig. 9. Results of field experiments. (a) Load-side grounding SLGF-LB
and SLGF in ungrounded system. (b). Source-side grounding SLGF-LB in
ungrounded system. (c). Load-side grounding SLGF-LB and SLGF in reso‐
nant grounding system. (d). Source-side grounding SLGF-LB in resonant
grounding system.
TABLE IV 30 F1 150 F1
PROPERTIES OF SIMULATION MODEL OF OVERHEAD LINE OR CABLE 140
20 F2 130 F2
|θ|/(°)
|θ|/(°)
F3 120 F3
Inductive Capacitive 10 110
Distribu‐ Resistance 100
Property reactance reactance
tion line (Ω/km) 90
(Ω/km) (MΩ·km) 0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
Positive Grounding resistance (Ω) Grounding resistance (Ω)
0.18 3.14 0.20
Overhead impedance (a) (b)
line Zero 30 150
0.23 10.40 0.41 Overhead lines 140 Overhead lines
impedance Cables Cables
20 130
|θ|/(°)
|θ|/(°)
Positive 120
0.22 0.76 0.21
impedance 10 110
Cable 100
Zero 90
2.24 3.02 0.32
impedance 0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
Grounding resistance (Ω) Grounding resistance (Ω)
(c) (d)
Simulation experiments are carried out to analyze |θ| for Fig. 11. Simulation results for different fault locations and distribution
SLGFs and SLGFs-LBs, which occur at different locations lines. (a) |θ| at different fault locations for SLGF-LB. (b) |θ| at different
of the distribution network composed of different distribu‐ fault locations for SLGF. (c) |θ| on different distribution lines for SLGF-LB.
tion lines. Besides, the effects of power factor, network im‐ (d) |θ| on different distribution lines for SLGF.
balance (±4%), frequency fluctuation (±1 Hz), and voltage
harmonic distortion (±4%) on the value of |θ| are also simu‐ lected to make the value of |θ| closer to the threshold values.
lated. In simulation experiments, load-side grounding resis‐ Considering that the maximum error caused by PMUs is lim‐
tance is set as the independent variable from 125 Ω to 5000 ited [32], it can be added directly to results of |θ|. Therefore,
Ω; while other network parameters, such as the overcompen‐ the simulation experiments for measuring devices are not
sation degree and length of distribution lines, are set to the conducted.
critical value presented in Table I, which is − 10% and 20
150 30
km, respectively.
|θ| (°)
|θ| (°)
100 20
The simulation results for different fault locations and 50 10
0
types of distribution lines are shown in Fig. 11. Figure 11(a) 0 1000 2000 3000 4000 5000 20 30 40 50 60 70 80 90
and (b) shows the simulation results of |θ| for overhead line Grounding resistance (Ω) Ratio of reactive load (%)
when single-line faults occur at different locations of distri‐ (a) (b)
bution networks. It can be concluded from Fig. 11(a) and (b) 5 2.02° 0.5 0.3°
Δθ (°)
Δθ (°)
that the location of fault does not affect the trend of |θ| as 0 0
-0.3°
the grounding resistance increases, while the value of |θ| var‐ -5
-2.02°
-0.5
ies with the change of the distance between the fault loca‐ 0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
Grounding resistance (Ω) Grounding resistance (Ω)
tion and PMU. As the distance grows, the value of |θ| gets
(c) (d)
closer to the threshold values, namely 86° for SLGFs-LBs 5 0.6
2.02°
and 89° for SLGFs, since fault characteristics are less obvi‐ 0.4
Δθ (°)
Δθ (°)
0 0.2
ous as the fault gets farther away from the monitoring point. 0
-2.02° -0.2
In addition, since parallel lines have the same voltage, when -5 -0.4
01000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
the fault occurs at F2, according to Fig. 10, |θ| measured Grounding resistance (Ω) Grounding resistance (Ω)
from the PMU will not be influenced by other branch lines. (e) (f )
Figure 11(c) and (d) shows the simulation results of |θ| on |θ| for SLGF-LB; |θ| for SLGF; Δθ for SLGF-LB; Δθ for SLGF
overhead lines and cables for SLGF-LB and SLGF, repec‐ Residual of Δθ for SLGF-LB; Residual of Δθ for SLGF
tively. The fault location is set at F1 in Fig. 10 to make |θ| Fig. 12. Simulation results of θ and influencing factors. (a). |θ|. (b) Power
closer to the threshold values. According to Fig. 11(c) and factor. (c) Network imbalance. (d) Frequency fluctuation. (e) Voltage har‐
monic distortion. (f). Residual analysis.
(d), the types of distribution lines do not influence the trend
of |θ| as the grounding resistance increases. However, the val‐
ue of |θ| is related to the type of distribution lines. When the Figure 12(a) shows the simulation results of the relation‐
cable is selected, the value of |θ| is closer to threshold values ship between |θ| and load-side grounding resistance, regard‐
because the capacitance of cable is greater than that of over‐ less of errors caused by operation conditions and external de‐
head line, which is reflected by BC of (1) and (2). It could vices. The ratio of reactive load is set as 90%. It can be ob‐
be calculated that the value of |θ| tends to approach 90° as served from Fig. 12(a) that the range of |θ| is always within
BC increases, regardless of faults types, which is consistent the limit of thresholds for SLGFs and SLGFs-LBs. In addi‐
with simulation results in Fig. 11(c) and (d). tion, as the load-side grounding resistance increases, |θ| in‐
The simulation results of influencing factors are illustrated creases for SLGFs and decreases for SLGFs-LBs, consis‐
in Fig. 12. According to the simulation results shown in Fig. tent with Fig. 9(a) and (c), respectively.
11, the fault location is set at F1, and the overhead line is se‐ Figure 12(b) shows the simulation results of the influence
LIU et al.: IDENTIFICATION METHOD FOR SINGLE-LINE-TO-GROUND FAULTS WITH LINE BREAK BASED ON PHASOR MEASUREMENT... 9
of power factor on |θ| for SLGFs-LBs, since power factor on‐ may become invalid when the value of grounding resistance
ly affect |θ| for SLGFs-LBs. The load-side grounding resis‐ is around R min.
tance is set as 125 Ω . The ratio of reactive load is set as 3) To enhance the robustness of the proposed method, the
90%, 80%, 60%, 40%, and 25%. It can be concluded that as errors resulted from operation conditions and external devic‐
the ratio of reactive load decreases, |θ| for SLGFs-LBs de‐ es are calculated. After correction, the upper boundary of |θ|
creases. In addition, the simulation results of |θ| for SLGFs- is 86° for SLGFs-LBs; while the lower boundary of |θ| is
LBs do not exceed 83.66°, consistent with theoretical results 89° for SLGFs.
from (4) and Section III-C.
Figure 12(c)-(e) illustrates the effect of different influenc‐ REFERENCES
ing factors. The ratio of reactive load is set as 90%. From [1] M. Gholami, A. Abbaspour, M. Moeini-Aghtaie et al., “Detecting the
Fig. 12(c)-(e), it can be concluded that ∆θ caused by differ‐ location of short-circuit faults in active distribution network using
ent influencing factors is always within the range of theoreti‐ PMU-based state estimation,” IEEE Transactions on Smart Grid, vol.
11, no. 2, pp. 1396-1406, Mar. 2020.
cal thresholds. For example, |∆θ| caused by network imbal‐ [2] Y. Du, Y. Liu, Q. Shao et al., “Single line-to-ground faulted line detec‐
ance and voltage harmonic distortion does not exceed 2.02°; tion of distribution systems with resonant grounding based on feature
fusion framework,” IEEE Transactions on Power Delivery, vol. 34,
and the influence of frequency fluctuation on |θ| is always no. 4, pp. 1766-1775, Aug. 2019.
within the limit of ±0.3°. Moreover, the three factors men‐ [3] Z. Li, Y. Liu, Y. Yan et al., “An identification method for asymmetric
tioned above have the opposite impacts on |θ| for SLGFs- faults with line breaks based on low-voltage side data in distribution
networks,” IEEE Transactions on Power Delivery, vol. 36, no. 6, pp.
LBs and SLGFs. In addition, the influence of those factors 3629-3639, Dec. 2021.
on |θ| decreases as load-side grounding resistance increases. [4] A. Kalyuzhny, “Analysis of temporary overvoltages during open-phase
The basic reason is that the fault current also decreases as faults in distribution networks with resonant grounding,” IEEE Trans‐
actions on Power Delivery, vol. 30, no. 1, pp. 420-427, Feb. 2015.
the load-side grounding resistance increases. [5] Z. Lv, B. Ning, W. Luo et al., “A real time monitoring method for sin‐
The residual analysis is selected to verify the superposi‐ gle-line break fault based on dual-terminal information of distribution
tion principle of different kinds of errors. The simulation ex‐ network with fault tolerant,” in Proceedings of 2019 IEEE 3rd Confer‐
ence on Energy Internet and Energy System Integration (EI2), Chang‐
periment is conducted when the influencing factors reach the sha, China, Nov. 2019, pp. 2587-2592.
extreme conditions at the same time. Theoretical values indi‐ [6] Z. Cong, Y. Liu, J. Fang et al., “Root-cause identification of single
cate numerical sum of ∆θ based on results from Fig. 12(b)- line-to-ground fault in urban small current grounding systems based
(e), while measured values represent simulation sum of ∆θ on correlation dimension and average resistance,” IEEE Transactions
on Power Delivery, vol. 35, no. 4, pp.1834-1843, Aug. 2020.
in this experiment. According to Fig. 12(f), even under ex‐ [7] Q. Kang, W. Cong, M. Wang et al., “Analyses and judgment methods
treme conditions, the residual of Dθ for SLGFs and SLGFs- of single-phase broken-line fault for loaded distribution line,” in Pro‐
ceedings of 2016 IEEE PES Asia-Pacific Power and Energy Engineer‐
LBs are not beyond the margins. Therefore, the superposi‐ ing Conference (APPEEC), Xi’an, China, Oct. 2016, pp. 482-486.
tion principle is applicable based on simulation results. [8] F. Shi and W. Cong, “Methodology to differentiate type of single-
In summary, the simulation results show that the ranges of phase line break fault in 10 kV ungrounded distribution networks,” in
Proceedings of 2014 IEEE PES Asia-Pacific Power and Energy Engi‐
|θ| and its errors are consistent with theoretical calculation re‐ neering Conference(APPEEC), Hong Kong, China, Dec. 2014, pp. 1-6.
sults in Sections II and III. Therefore, the proposed identifi‐ [9] S. Mohajeryami, M. Doostan, and Z. Salami, “An analysis of open-
cation method can keep high accuracy and robustness even phase fault in power generation station,” in Proceedings of 2016
North American PowerSymposium (NAPS), Denver, CO, USA, Sept.
in extreme cases based on simulation results. 2016, pp. 1-6.
[10] S. Wu, Y. Zhang, and Y. Su, “The medium-voltage distribution net‐
V. CONCLUSION work fault diagnosis based on data association analysis,” in Proceed‐
ings of 2017 International Conference on Green Energy and Applica‐
In this paper, an identification method based on phase rela‐ tions (ICGEA), Singapore, Dec. 2017, pp. 57-63.
tionship between the fault phase voltage and the vector sum [11] Y. Zhang, J. Wang, and M. E. Khodayar, “Graph-based faulted line
identification using micro-PMU data in distribution systems,” IEEE
of non-fault phase voltages is proposed to distinguish SLGF- Transactions on Smart Grid, vol. 11, no. 5, pp. 3982-3992, Sept. 2020.
LBs and SLGFs in radial small-current grounding distribu‐ [12] M. Pignati, L. Zanni, P. Romano et al., “Fault detection and faulted
tion networks. The conclusions can be drawn as follows. line identification in active distribution networks using synchrophasors-
based real-time state estimation,” IEEE Transactions on Power Deliv‐
1) The source-side voltage characteristics of SLGFs and ery, vol. 32, no. 1, pp. 381-392, Feb. 2017.
SLGFs-LBs are similar, which makes it difficult to distin‐ [13] Z. Zhong, C. Xu, B. J. Billian et al., “Power system frequency moni‐
guish them at the source side. toring network (FNET) implementation,” IEEE Transactions on Power
Systems, vol. 20, no. 4, pp. 1914-1921, Nov. 2005.
2) Due to the difference in electrical structures, the load- [14] Y. Yan, Y. Liu, J. Fang et al., (2021, Oct.). Application status and de‐
side voltages of SLGFs and SLGFs-LBs exhibit different velopment trends for intelligent perception of distribution network.
characteristics. Therefore, the load-side voltages can be used High Voltage. Avialable: https://doi.org/10.1049/hve2.12159
[15] Y. Bansal and R. Sodhi, “PMUs enabled tellegen’s theorem-based
as the criterion to distinguish SLGFs-LBs and SLGFs. The fault identification method for unbalanced active distribution network
phase difference between the fault phase voltage and the vec‐ usingrtds,” IEEE Systems Journal, vol. 14, no. 3, pp. 4567-4578, Sept.
tor sum of non-fault phase voltages at the load side, i.e., θ, 2020.
[16] N. A. S. P. I. (2014 Oct.), “PMUs and synchrophasor data flows in
is selected as the criteria. Without considering influencing north America,” [Online]. Available: http://www. https://www. smart‐
factors, when |θ| has a range of [93.02° , 180° ], SLGFs oc‐ grid. gov/document/pmus_and_synchrophasor_data_flows_north_ameri‐
cur; and when |θ| has a range of [0°, 86.12°], SLGFs-LBs oc‐ ca.
[17] T. Bi, H. Liu, Q. Feng et al., “Dynamic phasor model-based synchro‐
cur. Note that, the minimum grounding resistance could be phasor estimation algorithm for M-class PMU,” IEEE Transactions on
calculated as R min = 125 Ω; and the identification method Power Delivery, vol. 30, no. 3, pp. 1162-1171, Jun. 2015.
10 JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, VOL. XX, NO. XX, XX XXXX
[18] K. Chauhan and R. Sodhi, “Placement of distribution-level phasor versity of Geosciences, Wuhan, China, in 2004. He received his M. D and
measurements for topological observability and monitoring of active Ph.D degrees of electrical engineering from Shanghai Jiao Tong University
distribution networks,” IEEE Transactions on Instrumentation and (SJTU), Shanghai, China, in 2008 and 2012, respectively. Currently, he is
Measurement, vol. 69, no. 6, pp. 3451-3460, Jun. 2020. an Associate Researcher in School of Electronic Information and Electrical
[19] M. Gholami, A. Abbaspour, M. Moeini-Aghtaie et al., “Detecting the Engineering at SJTU. His current research interests include detecting fault
location of short-circuit faults in active distribution network using location and intelligent diagnosis of power equipment.
PMU-based state estimation,” IEEE Transactions on Smart Grid, vol.
11, no. 2, pp. 1396-1406, Mar. 2020. Zichang Li received the B.E. degree in electrical engineering and automa‐
[20] Z. Wu, X. Du, W. Gu et al., “Optimal PMU placement considering tion from Shanghai Jiao Tong University (SJTU), Shanghai, China, in 2019.
load loss and relaying in distribution networks,” IEEE Access, vol. 6, Now he is working towards his M.E. degree in High Voltage and Insulation
pp. 33645-33653, May 2018. Engineering in SJTU. His current research interests include fault diagnosis
[21] P. Li, H. Su, C. Wang et al., “PMU-based estimation of voltage-to- and location in the distribution network.
power sensitivity for distribution networks considering the sparsity of
Jacobian matrix,” IEEE Access, vol. 6, pp. 31307-31316, May 2018. Yingjie Yan received the B.E. and Ph.D. degrees from Shanghai Jiao Tong
[22] J. Liu, Y. Zhou, Y. Li et al., “Modelling and analysis of radial distribu‐ University (SJTU), Shanghai, China, in 2011 and 2018, respectively. Now,
tion network with high penetration of renewable energy considering he is working in the Department of Electrical Engineering, SJTU. His cur‐
the time series characteristics,” IET Generation, Transmission Distribu‐ rent research interests include electric power equipment online monitoring,
tion, vol. 14, no. 14, pp. 2800-2809, Jul. 2020. big data methods for fault diagnosis, and condition evaluation of power
[23] IEEE Guide for the Parameter Measurement of AC Transmission equipment and transmission lines in distribution network.
Lines, IEEE Std 1870-2019, 2019.
[24] A. Bendjabeur, A. Kouadri, and S. Mekhilef, “Novel technique for
Guanghui He received the B. S. degree from the University of Electronic
transmission line parameters estimation using synchronized sampled
Science and Technology of China, Chengdu, China, in 2002, and the Ph.D.
data,” IET Generation, Transmission Distribution, vol. 14, no. 3, pp.
degree from Tsinghua University, Beijing, China, in 2007, both in electronic
506-515, Feb. 2020.
engineering. He is current an Associate Professor with the Department of
[25] Y. Xiang, X. Han, L. Wang et al., “Resonance characteristics and
Micro/Nano Electronics, Shanghai Jiao Tong University (SJTU), Shanghai,
damping techniques of grid-connected converter with the distributed
China. His main research interests include high-performance electromagnet‐
capacitance of transmission line,” in Proceedings of 2018 13th IEEE
ic transient simulation, energy efficient algorithms and circuits design for
Conference on Industrial Electronics and Applications (ICIEA), Wu‐
wireless communication and artificial intelligent systems.
han, China, May 2018, pp. 491-496.
[26] IEC Standard Voltages, IEC 60038:2002, 2002.
[27] IEEE Recommended Practice for Monitoring Electric Power Quality, Jian Fang is a Senior Engineer with the Guangzhou Power Supply Bureau
IEEE Std 1159-2019, 2019. Co., Ltd. Electric Power Test Institute. His main research interests include
[28] IEEE Recommended Practice and Requirements for Harmonic Control distribution network operation management, distribution network technology
in Electric Power Systems, IEEE Std 519-2014, 2014. supervision, and distribution network new technology promotion.
[29] IEEE Guide for Identifying and Improving Voltage Quality in Power
Systems, IEEE Std 1250-2018, 2018 Kejun Li received the B. Sc. degree from Shanghai Jiao Tong University
[30] IEEE Standard for Interconnection and Interoperability of Distributed (SJTU), Shanghai, China, in 2016. Currently, he is prusuing his Master De‐
Energy Resources with Associated Electric Power Systems Interfaces, gree in Shanghai Jiao Tong University. His main research interests include
IEEE Std 1547-2018, 2018. fault identification and location in distribution network.
[31] IEEE Guide for Synchronization, Calibration, Testing, and Installation
of Phasor Measurement Units (PMUs) for Power System Protection Xiuchen Jiang received the B.S. degree from Shanghai Jiao Tong Universi‐
and Control, IEEE Std C37.242-2013, 2021. ty (SJTU), Shanghai, China, in 1987, the M.D. degree in electrical engineer‐
[32] X. Wang, X. Xie, S. Zhang et al., “Micro-PMU for distribution power ing from Tsinghua University, Beijing, China, in 1992, and the Ph.D. degree
lines,” CIRED-Open Access Proceedings Journal, vol. 2017, no. 1, pp. in electrical engineering from SJTU, in 2001. He is currently a Full Profes‐
333-337, Jan. 2017. sor with SJTU, where he has been the Director of the Electrical Power De‐
partment since 2002. His main research interests include electrical measur‐
ing technology and electrical apparatus automation.
Yadong Liu received the B.E. in electronic & information from China Uni‐