Close-Spacing and
Restricted Airflow Situations
20-120 CGAM, 50-60 Hz
Air-Cooled Scroll Chillers
General Information
Air-cooled chillers are frequently applied in situations where close spacing of multiple chillers is
required. They are also applied in situations that result in restricted airflow due to walls and other
obstructions. The air-cooled CGAM chiller offers an advantage over competitive equipment in
many of these situations. Performance is minimally affected in many restricted airflow situations
due to its unique condensing coil geometry. Also, through its advanced Adaptive Control™
microprocessor logic, the chiller will attempt to stay on-line whereas competitors’ chillers may shut
down. Adaptive Control microprocessor logic describes the ability of the control system to
understand the operating environment of the chiller and adapt to it by first optimizing its
performance and second, attempting to stay on-line through abnormal conditions. For example,
high ambient temperatures combined with a restricted airflow situation will generally not cause
unit shutdown. Competitor’s chillers would typically shut down on high pressure cutout in these
conditions.
General Information
The CGAM chiller has 3 coil configurations that minimize performance effects in close spacing and
restricted airflow situations. The coil configurations, shown in Figure 1, has a number of distinct,
engineered advantages. First, the coil face velocity is practically constant over the entire surface,
optimizing heat transfer performance. Second, the subcooler is integrated into the condensing
surface, again optimizing performance. Competitors’ coil configurations can produce uneven air
distribution over the condenser coils and “pinch” the airflow to portions of the condenser and
subcooler.
The Slant units have a single coil and do not draw air from the back of the unit. Therefore, they can
be placed as close as 2 feet to a wall or restriction at the back side without significant performance
issues.
Airflow
Airflow
Airflow
Airflow
Airflow
An example of condenser air redistribution when the airflow is restricted is shown in Figure 2. A
wall or other obstruction has been placed close to one side of the chiller and airflow is restricted.
However, the vertical coil nearest the obstruction is able to get the air it requires to operate
normally. The inner coil is able to get the air it requires from the opposite side of the chiller. Air
enters from the unobstructed side and freely distributes itself to the inner condenser coils. Chiller
performance is unaffected
Figure 2. Air redistribution with a wall restricting the air flow
Airflow
Open
Area
Airflow
The remainder of this engineering bulletin describes various commonly encountered close spacing
and restricted airflow installations. The performance changes are in terms of % Capacity (Tons)
reduction and % Compressor Power (kW) increase at full load. Adjust the performance given in the
catalog or selection program using performance adjustment factors taken from the graphs. For
example, assume that a chiller selection is made that gives a catalog capacity of 180 tons at 195 kW
(compressor power). Because of the actual installed conditions, one of the cases given in this
engineering bulletin applies. A 1% capacity reduction and a 2% power increase is taken from the
graphs for that case. The adjusted performance would be:
Adjusted Capacity= (1 - .01) x 180 tons= 178.2 tons
Adjusted Compressor Power = (1 + .02) x 195 kW = 198.9 kW
Increases in power required may limit the maximum ambient the unit is capable of.
In complicated installations, some uncertainty may exist relative to performance and control.
Remember, Trane’s unique Adaptive Control™ microprocessor logic will make as much chilled
water as possible, given the actual installation, and avoid nuisance high pressure cutouts. Consult
with Product Support for any unusual applications not covered by this bulletin.
CG-PRB011-EN 3
Case 1 –Two Chillers Side by Side
The performance effect of chillers placed side by side is small, as shown in Figure 4. As previously
discussed, only one of the two condenser coils of one refrigeration circuit per chiller is affected by
the air recirculation caused by close spacing. All CGAM chillers above 35 tons have two completely
independent refrigeration circuits. The outboard coils are unaffected. Spacing of chillers less than
4 feet is not recommended due to service considerations and air recirculation.
4 CG-PRB011-EN
Case 1 –Two Chillers Side by Side
1.6
1.4
1.2
% Capacity Reduction
0.8
0.6
0.4
0.2
0
2 3 4 5 6 7 8 9 10
d - Distance Between Units - Feet
1.6
1.4
1.2
1
% Power Increase
0.8
0.6
0.4
0.2
0
2 3 4 5 6 7 8 9 10
d - Distance Between Units - Feet
CG-PRB011-EN 5
Case 2 – Two Chillers End to End
Control
Control
Panel
Panel
2ft minimum recommended
service clearance
Control
Control
Panel
Panel
4ft minimum recommended working
clearance for control panel is governed by NEC
There is no performance effect for any spacing of chillers end to end. However, minimum spacing
is governed by 1) service clearances, and 2) the working clearance required by the National Electric
Code (NEC) near control panels. A 2-foot clearance is recommended on the end opposite the
control panel.
Article 110-16 of the NEC requires 3 to 4 feet of working clearance, on the control panel end
depending on the actual installed conditions. Refer to the NEC for a detailed discussion of
requirements.
d d
6 CG-PRB011-EN
Case 3 – Three or More Chillers Side by Side
1.8
1.6
1.4
% Capacity Reduction
1.2
0.8
0.6
0.4
0.2
0
0 2 4 6 8 10 12 14 16
d - Distance Between Units - Feet
3.5
2.5
% Power Increase
1.5
0.5
0
0 2 4 6 8 10 12 14 16
d - Distance Between Units - Feet
CG-PRB011-EN 7
Recommended Installation of Multiple Chillers
8’
min
8’ min
d
Wall or
d
Building
Structure H 8’
8 CG-PRB011-EN
Case 4 – Restricted Airflow on One Side
0.9
0.8
0.7
d=6 ft
% Capacity Reduction
d=4 ft
0.6
d=2 ft
0.5
0.4
0.3
0.2
0.1
0
0 5 10 15 20 25 30
H - Wall or Building Height - feet
2.5
d=6 ft
d=4 ft
% Power Increase
1.5
d=2 ft
0.5
0
0 5 10 15 20 25 30
H - Wall or Building Height - feet
CG-PRB011-EN 9
Case 5 – Decorative Walls on All Sides
d
Decorative wall of fence
same height as insatalled
chiller with % free area.
d d
6
d - Distance from Wall to Unit - feet
0
0 5 10 15 20 25 30 35 40 45 50
% Open area of Decofative Wall of Fence
10 CG-PRB011-EN
Case 6 – Pits or Solid Walls Surrounding Unit
d
H d d
CG-PRB011-EN 11
Case 6 – Pits or Solid Walls Surrounding Unit
4.5
3.5
% Capacity Reduction
3 d=8 ft
d=6 ft
2.5 d=4 ft
1.5
0.5
0
0 2 4 6 8 10 12 14
Depth of Pit/Wall Height H - feet
5
% Power Increase
d=8 ft
d=6 ft
4 d=4 ft
0
0 2 4 6 8 10 12 14
Depth of Pit/Wall Height H - feet
12 CG-PRB011-EN
Recommended Installation – Walls/Obstructions
8’ min
Recommended installation
CG-PRB011-EN 13
Recommended Installation – Walls/Obstructions
0.09
0.08
0.07
60 ton LN
120 ton LN
0.06
% Capacity Reduction
0.05
0.04
0.03
0.02
0.01
0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35
External static pressure, in-H2O
0.12
0.1
60 ton LN
120 ton LN
0.08
% Power Increase
0.06
0.04
0.02
0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35
External static pressure, in-H2O
14 CG-PRB011-EN
Recommended Installation – Walls/Obstructions
0.2
0.18
0.16
60 ton LN
0.14 120 ton LN
0.12
% EER Decrease
0.1
0.08
0.06
0.04
0.02
0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35
External static pressure, in-H2O
CG-PRB011-EN 15
Literature Order Number CG-PRB011-EN
Date November 2009
Supersedes New