Professional Documents
Culture Documents
This chapter reviews the types of air compressors used in industrial plant design, their dif-
ferent characteristics, and applications. Keep in mind a quote from William O’Keefe in his
publication “Compressed-Air System Design,” Power, November 1978:
Today, compressor type selection seems to depend more on individual preference than on
analysis. There are several reasons for this. For one, developments in oil removal equipment
have made it possible for systems to deliver low-oil air from lubricated compressors.
Second, increased emphasis on compressed air—its cost, reliability, and quality—has led
more attention to past performance records of compressors. Because few plants have enough
compressors of various types to allow build-up of reliable information and cost data on them,
the decision among competing types can fall to an engineer who has favorable memories of one
type or another. If his auxiliary equipment is right, the type can probably be made to operate
successfully in most systems.
A third reason may be the confusing nature of data supplied by manufacturers. There is
considerable room for differences of opinion and presentation in a data package containing
purchase price, installation cost, efficiency at part and full load, cost of maintenance and repair,
reliability, and life expectancy.1
Startup engineers must know what type of compressor they are commissioning, its char-
acteristics and behavior, and the relationship between the machine and system. The manu-
facturer provides the compressor, not the system. It is the startup engineer’s responsibility
to make them work in harmony together, not the manufacturer nor the design engineer.
Positive-Displacement Compressors
Reciprocating
The reciprocating compressor has been, for long periods of time, the workhorse for the
power industry because of its wide capacity range, ease of control, and especially its oil-
free air delivery. They are common in large fossil-fuel-fired stations requiring large, reliable
oil-free instrument air systems. They are, however, generally more expensive than other
compressors in the medium- to high-capacity range and are more expensive to maintain for
all capacity ranges. Because of the reciprocating action, they create vibration that requires
special mounting considerations and corresponding higher installation cost, plus higher
maintenance costs. The reciprocating compressor is a relatively constant-volume machine,
Single-acting Double-acting
single-stage single-stage
Crosshead
Double-acting
two-stage, intercooled
Intercooler
making it ideal for instrument air systems. However, it is also a variable-pressure machine
and must be controlled within a range suitable for system requirement (see Fig. 1-1).
To understand the control of recip compressors, first realize that the machines fall into either
the single-acting or double-acting type and also into either the single-stage or multistage type.
Figure 1-1 (sic) gives a quick review of the essential elements of this classification.
Single-acting machines are, in general, small units, inherently compact because of the
trunk-piston design. Compression occurs only in one direction of stroke. In the double-acting
machine, the piston has an easier time, because lateral load is less, with the crosshead’s bearing
surface helping to take the load. This bearing surface is outside the cylinder, so it can be given
special design provisions for load-carrying and lubrication.
The number of stages in which a compressor reaches its delivery pressure is also important.
For plant-air service requiring 90–125 psig air, a compressor can be single-stage or two-stage.
The single-stage machine, doing all the work in a single compression, generates high heat, and
is less efficient than if the work occurs in two separate stages, with cooling of the air between
stages.
The general rule is that a compressor should be double-acting and water-cooled to be con-
sidered a continuous-duty unit. For plant air, such a machine will be two-stage-or perhaps even
three-stage, if pressures around 200 psig are needed.
Double-acting machines, with more extensive cooling and design for longer life, provide
more efficient air compression, more reliability and less sensitivity to abuse and dirt, but they
are relatively expensive to install and are heavy and bulky.2
Rotary
The rotary compressor is also a constant displacement type with variable discharge pressure.
The following sections describe the different types of rotary machines.
Screw compressor (Fig. 1-2) and sliding vane (Fig. 1-3) are positive-displacement com-
pressors and can be provided with as high as 2000-scfm capacities. They can be oil-
entrained or oil-free air delivery. The oil-entrained air compressor uses oil to lubricate the
cylinder of the compressor to reduce heating. The oil-free compressor relies on material
construction and jacket cooling to achieve the same results. Single-stage units will gener-
ally supply 50 psig, while two-stage units can provide up to 150 psig. The screw type is a
relatively noisy machine, and therefore, noise abatement has to be taken into consideration
in packaging and installation.
Water jacket
Sliding vane
Inlet
zone
Discharge
Screw zone Sliding vane
Figure 1-2 Screw. Figure 1-3 Sliding vane.
Rotary tooth or lobe compressors are used for small-capacity requirements less than 300 cfm.
They are ideal for plants with relatively small air demand, such as for combustion turbine,
Discharge pressure
(PSIG)
14 (96.6)
12 (82.8)
10 (69.0) Curve II
(1,550 rpm)
8 (55.2)
(2)
Curve I
6 (41.4)
(1,420 rpm)
4 (27.6)
(1)
2 (13.8)
Inlet flow
0 10 20 30 40 50 60 70 80 ACFM (m3/s)
(0.005) (0.009) (0.014) (0.019) (0.024) (0.028) (0.030) (0.038)
Liquid Ring
The Nash compressor used as a vacuum pump in the power industry is a liquid ring com-
pressor that circulates water through a heat exchanger. The water, a compressant, partially
fills the casing and is circulated by a radial blade impeller that is offset in an oval casing.
Centrifugal force drives the water to the outer side of the casing. Figure 1-5 illustrates the
process. These compressors are rugged and very quiet. In one case, a Nash pump was making
Rotor Rotor
Direction
of rotor
rotation Cone
Cone
Discharge Low pressure caused by
Liquid compressant receding of liquid compressant
port
fills rotor chamber from rotor chamber draws air
through inlet port
A B
Air is compressed
by converging
Drive liquid compressant Drive
shaft shaft Body
Body
Rotor
Rotor
Cone Cone
Body casing forces
liquid compressant Liquid compressant
back toward center and compressed air
of rotor chamber are discharged
through discharge
port
C D
Liquid compressant and compressed air flow
unusual noises. During an internal inspection, the pump was found to have ingested welding
rod. The impeller had flattened the rod but was undamaged.
Variable-Displacement Compressors
than 2000 cfm are requirements. It would not be uncommon to find a 3000-hp centrifugal
per unit for sootblowing in a large, multiunit, coal-fired station.
Small machines are relatively quiet with low installation costs. However, inlet air must
be free of abrasive particulate. The centrifugal compressor is a constant-pressure, variable-
capacity machine. Using variable-speed control, the discharge pressure can be held constant
and the capacity varied proportional to speed. See Fig. 1-6a.
Several methods exist for matching the compressor outlet to the plant load. But, in every
case, the acceptable method will result in the compressor characteristic curve intersecting
the load curve at the desired pressure and capacity. Speed control is the best way to obtain
this match because, with variable speed, the compressor can deliver a constant capacity at
variable pressure, variable capacity with constant pressure, or a combination of variable
capacity and variable pressure.1
See Fig. 1-6b.
Surge Control
Surge control is probably the most difficult to solve of all problems relating to centrifugal com-
pressors. It can be compared to the stall of airplane wings. Surge manifests itself in a backflow
(reversed flow), usually accompanied by violent and loud noisy pressure fluctuations, and,
unless reduced, may result in severe structural damage to the compressor. Surge is caused by
reducing flow through the compressor to a point where the pressure restriction in the machine
becomes greater than the pressure ratio developed by the compressor.
Surge limit of a compressor is the minimum flow required for stable operation at a
given speed for inlet throttle valve position. This critical point for a particular compressor
is determined by compressor speed and geometry, and thermodynamic properties of the gas.
“Stonewall” describes the upper limit of capacity.
Although the stability range of a centrifugal compressor is commonly indicated by the
design point to the surge limit, the unit can operate to the right of the design point. Stonewall
occurs when the velocity of the gas approaches sonic velocity (usually at the impeller inlet).
Shock waves result, restricting flow and causing either a choking effect or a rapid drop in
discharge pressure with a slight increase in volume flow.1
0 50 100 0 50 100
Flow, percent by volume Flow, percent by volume
(a)
Discharge
pressure (PSIA)*
240
220
200 (4)
I
ve
S4
ur
C
180
Constant
y
II
nc
pressure
ve
160
icie
ur
system
%
C
(2)
72
Eff
S1 curve
140
III
e
(1)
v
ur
C
120
cy
(5)
en
y
ci
100
nc
fi
ef
ie
fic
%
(3)
ef
78
80
%
y
nc
76
S3
e
ci
60
fi
ef
%
ve
74
40 Cur
tem n)
Sys ic io
t
20
s t ly fr
(Mo
Flow
0 1 2 3 4 5 6 7 8 9 10 11 12 (103 lbm/hr)*
Centrifugal compressor curves
(b)
Figure 1-6 Centrifugal compressor curves (a) reciprocating versus centrifugal curves, (b) centrifugal
speed-capacity curves.3
120
100
–25°
Percent of rated head
80
60
Zero
+25°
40
+40°
20 +55°
+75° +65°
0
20 40 60 80 100 120 140 160
Percent of rated volume flow
Figure 1-7 Effect of inlet guide vanes on capacity and head of a centrifugal
compressor.4
It becomes obvious that a compressor operating on a constant pressure curve must be kept
to the right of the surge limit curve. Early systems used inlet control and discharge dump
valves to unload the compressor if it entered the surge region. If the compressor load
demand suddenly drops, the inlet valve closes and the dump valve opens. From the curves
in Fig. 1-7, it can be seen that the inlet guide vanes can move the compressor curves, push-
ing the surge limit to the left. This reduces capacity to meet the reduction in demand. From
the variable-speed curves, Fig. 1-6, the same effect can be seen, but without a change in
discharge pressure.
Sootblower Controls
Sootblowing operation must be controlled so that the compressors operate in their optimum
load range. This is the key to the success of centrifugal compressor operation and a chal-
lenge for startup engineers. Using past experience and trial and error operation of the soot
blowers, soot blower demand can be kept to the right of the surge limit of the compressor
capacity curve.
Programmed microprocessor coordinates the operation of 276 sootblowers in three boilers and
one scrubber to cut air consumption and boost sootblower efficiency…. The control program is
written so that each sootblower operates on a specific-time basis and can be blown more often
if actual furnace conditions indicate the need. The number of sootblowers operated at any one
time is automatically held within the capacity of the air compressors in service.
See the accompanying figure.5 The use of surge tanks will dampen system spikes generated
from on/off blower operation.
Variations in inlet-air temperature normally are not controllable, and they can have a signifi-
cant effect on compressor performance. The adverse impact of warm air on efficiency empha-
sizes the importance of selecting a compressor with a steep curve and a high rise from working
pressure to the surge point at standard conditions.6
Therefore, it is important that matching of the system capacity curve to the compressor
capacity curve include ambient temperature change.
It is imperative that centrifugal compressors operate above the minimum flow condition at
all times. Flow should never drop below the surge limit/minimum flow on the performance
curve. Systems that have conditions with demand requirements that can reduce flow into
the surge region must be studied thoroughly by the startup engineer. This includes all
system controls, compressor controls, and performance curves. Surging can be extremely
violent, and catastrophic failure of the compressor can occur. Centrifugal gas compressors
for combustion turbines are especially susceptible to this during startup when unit trips can
be expected. This will cause the compressor to go from a loaded condition to zero flow
instantly.
Constant-speed centrifugal compressors operate at full load all the time, similar to
positive-displacement pumps, unless the they have inlet flow control valves. To maintain
constant design conditions, flow capacity that is not being used by the process can be
bypassed back to the first stage inlet or dumped to atmosphere through a silencer. These
machines may have high-frequency pulsations that can be in resonance with the natural
frequency of the piping system and system or compressor components. It can excite high
machine shaft as well as system component vibration. For variable-speed machines, the
vibration can be eliminated by simply avoiding speeds at which the vibration occurs, which
is usually at a low speed close to the surge limit. That is, the surge limit line should be
moved to the right of the original design point. Remember, this type of vibration is caused
by blade-pass-pulsation phenomena and is not turbulent flow related. Flow turbulence can
cause low-frequency vibration and can be corrected by adding guide or turning vanes in the
compressor inlet. This fix will not correct blade-pass-induced vibration.
Both low- and high-frequency vibrations can coexist. At the Edwardsport syngas com-
bined cycle, an air-separation unit with a 15,000-hp compressor had a temporary suction
strainer installed in the third-stage bypass to the first-stage inlet. When the strainer was
removed, the fine-mesh lining was found wadded up in the bottom. Also, there was evi-
dence of vibration wear on the coarse-mesh backing. With the strainer installed, there was
no external evidence of shaft or piping vibration. Therefore, the strainer was removed
because it was only temporary.
Without the strainer, severe piping vibration occurred, and the shaft vibration went from
1 to 4 mils. The inlet elbow did not have turning vanes, so a new elbow was fabricated
with vanes. Also, a flow-restricting orifice was installed in the section where the strainer
had been to recreate the same conditions that existed when the strainer was installed. The
pipe and shaft vibration returned to the original values. However, after only 50 hours of
operation, the orifice failed, and and a large piece was ingested by the first stage. Similar to
the strainer, it showed signs of vibrational flexing, which eventually caused embrittlement
and failure. The elbow turning vanes also had severe cracking and would have eventu-
ally failed. The low-frequency problem was solved but not the blade-pass, high-frequency
vibration.
Dryers
Because the water content in air does not change as the air is compressed, the given per-
centage of water increases as the air is compressed to a smaller volume. Simply stated, air
at less than 100 percent humidity will compress to 100 percent humidity. Most of the free-
water content produced in the process can be removed by mechanical means. However, the
air will remain saturated with moisture. This moisture will condense if cooled below its
dew point by ambient air. Therefore, if the system receives the saturated air at 90°F and the
ambient air is at 70°F, moisture will condense because the compressed, saturated air will
eventually cool to ambient conditions. Therefore, in plant instrument air systems, the dew-
point temperature of the compressed air must be lowered to below the prevailing ambient
air temperature. As a rule of thumb, that is at least 10°F. In freezing climates, plant air
must also be dried to prevent freezing of the air lines. Drying can be accomplished either
by absorption or refrigeration or by a combination of the two.
Refrigerant
Refrigerant air dryers remove moisture from air by cooling it to within a few degrees of the
freezing point of water. Resultant condensed moisture is removed in a separator and drain
trap mechanism located immediately downstream of the refrigerant evaporator. The minimum
pressure dew point possible with this type of dryer is 38°F because there is danger of freeze
up at lower temperatures.7
The obvious shortcoming of this type of dryer is it has a limit to which the dew point can
be lowered. This is because it can only remove aerosol moisture (mist), not vapor (gaseous)
moisture that must be removed by a drying media (desiccant). In tropical climates where
freezing temperatures are not present, this drying method would be ideal because of its
relative inexpensive installation and operation.
“The deliquescent dryer is a non-regenerative type dryer which utilizes an absorption process.
It contains a media, such as sodium carbonate, that absorbs the moisture and dissolves in the
process. They are not standard for the power industry because of daily maintenance and waste
disposal considerations. Because most automatic drains will not handle the deliquescent solu-
tion, the liquid must be drained manually, at least once a day.”7
Compressor Installation
The compression process generates considerable heat, which must be removed. Air-cooled
compressors require considerably more design attention than do water-cooled compressors.
The reason is that the ambient conditions are changed by the very conditions that affect
the product air. A worst-case example would be a compressor located in an inadequately
ventilated space. If the interstage temperature is 350°F with an ambient temperature of
90°F, and the ambient temperature is elevated by the air-cooled heat exchanger to 140°F,
then the interstage temperature will rise proportionally, creating a serious cycle of events.
One can see this happening if the compressor is located in a room or building and the
heat exchanger exhausts into the space rather than outside. Therefore, the design engineer
must consider all operating scenarios regarding air-compressor intake and cooling-air inlet
and exhaust. Because two different disciplines are involved, this is too often overlooked.
The process engineer must coordinate with the heating, ventilating, and air-conditioning
(HVAC) engineer to marry the two into the best installation for operation. For example, the
heat generated by compression can be used for space heating in the winter and exhausted
during summer operation.
Air-Compressor Rooms
As in the preceding example, air compressors operating in extreme climates also need special
consideration. For example, air compressors, dryers, and receivers operate more efficiently
at colder temperatures but need freeze protection in the winter. Air can be exhausted from
the building in the summer by ducting the compressor hot exhaust outside. Wall dampers
provide air makeup. In winter months, the air can be recirculated inside by exhausting into
the building. The inside air temperature is best controlled by an outside thermostat. A single
diverter gate can be used as a bypass to reduce pressure drop and, therefore, back pressure on
the cooling fan. Care must be taken to ensure large gates do not experience destructive vibra-
tion when operating. Harmonic oscillation can occur as the damper is moving. The inside air
temperature can be controlled by ventilation air, which is distributed in the building as mix
air. The mix air temperature is controlled by modulating the inlet and mix air dampers. The
minimum makeup and exhaust air should be mechanically set with the damper linkages.
Heat tracing is required for all drains. Radiant electric heaters can be installed for outages
and extreme conditions, to warm the equipment. Also, the compressor aftercooler requires a
temperature control switch so it does not subcool the air, which can cause surface condensa-
tion on downstream piping, aftercooler drains, and air-receiver external surfaces.
If the space is air-conditioned, special sizing and loading considerations are required for
both the compressed air system as well as the HVAC system. In this case, the best scenario
may be to exhaust the cooling air all the time or consider a separate unconditioned room
within the building. Installation of the air receivers in a cold, outside environment to assist
in moisture removal upstream of the dryers can be considered if the benefit is not offset by
seasonal climatic change.
To improve the investment, plant standardization has always been the goal of power
industry engineers. For plants firing natural gas, standardization is highly practical. However,
it is sometimes impractical to enter all possible climate changes and operating conditions
into an iteration that solves for optimum equipment selection for a “standard plant” design
for compressed air system equipment. One exception in the late 1990s was the “standardiza-
tion” of combined-cycle plants in which standards included compressed-air installations.
In short, the startup engineer must analyze the entire installation before trial operation
and determine if the design properly interfaces with the environment. For example, an
environmental design for Houston, Texas, may not be adequate for a plant located in Basra,
Iraq. A good rule of thumb for startup engineers to follow is there is no standard environ-
mental design for compressor package installation. Furthermore, if the startup engineer
issues an environmentally related design change request (DCR), it is very important that
he/she uses HVAC standards and equipment in the submittal.
System Configuration
The compressed-air system conceptual design for power plants is standard for the industry
because there are two basic systems integrated together. The instrument-air system and
plant service-air system are standard systems for the industry. The service-air system is
used for plant maintenance and the instrument-air system for plant controls. The service-
air system is almost always connected to the instrument-air system through a “marshaling”
valve that continuously vents full open from the service-air system to the instrument-air
system. This relief-type valve closes on loss of pressure, shutting off supply to the service-
air system. (In other words, it opens on increasing pressure at the minimum required for
the instrument-air system.) The instrument-air system pressure is thereby maintained if
overuse of the service air system occurs or a failure in either system causes a demand that
is greater than compressor capacity.
Compressor Sizing
Sizing standards based on past experience are the best rule of thumb, especially for
the “standard plant” such as the combined-cycle plants previously mentioned. For first-
generation cola-fired plants, however, this is rarely more than an educated guess based on
usage taken from device specifications, estimated maintenance demand, and past experi-
ence. This is because the vast difference in fuel quality and consistencies dictate vast dif-
ferences in plant equipment selection and design. This in turn can create a vast difference
in compressed-air requirements. It is not uncommon for the startup engineer to find he/
she has to use the standby compressor for continuous service. This is especially true in
the commissioning phase. This is not an easy problem for the design engineer because
oversizing the compressed-air equipment can be as bad as undersizing from a capital
investment point of view. Compressor operation at part load is inefficient and, from an
energy point of view, costly.
Thus, it is extremely important that the startup engineer rigorously follow system com-
missioning procedures. Excessive leakage, incorrect pressure settings, and improper use of
plant air can make a perfectly sized system appear inadequate. Rigorous commissioning
activities include documentation that separates professional analysis from personal opin-
ion. Without it, the design engineer should never be consulted, especially concerning the
adequacy of his/her design.
Air receivers can act as moisture separators and sometimes are installed in cool areas
upstream of the air driers. In other cases, they are installed downstream of the dryers to
eliminate the need for air-receiver water blowdown. Exposure to radiant heat should be
avoided. The air receivers are generally sized for 5 to 10 percent of system demand. They
are used to extend the positive-displacement compressor load/unload cycle and compensate
for sporadic spikes in demand. For the startup engineer, air receivers are an excellent tool
for determining system demand and compressor performance.
Compressed-Air System
Pre-startup Testing
Preparation
1. Read the instruction manual, and copy all sections pertaining to the specific model
being commissioned. Insert the copy into a startup binder for field use. Check that
all spares, consumables, and replacements are available, such as lube oil, desiccant,
filter cartridges, etc. Insert the inventory information into the startup binder. Clean the
compressor skids and have construction personnel, materials, machines, equipment,
and debris removed from the operating area.
Inspection
Do not delegate any of the following preparations. Do it yourself so that you do not rely on
word of mouth, or “coffee locker” inspection reports.
Also, your compressor may have functions and settings that are password-protected,
such as auto restart after reestablishment of voltage after a loss of power. The factory
default may prevent automatic restart and may be password-protected. In this case,
you will need to obtain the password from the factory. It is essential that instrument
air be reestablished automatically as soon as power is reestablished. This, of course,
pertains only to the instrument-air system, not to plant or sootblowing air. There may
be settings for automatic shutdown after a factory-set duration. For example, will the
compressor motor shut down if unloaded for a predetermined interval? Also, will it
automatically shut down at a preset time or date? Is it factory-programmed to shut
down every night or weekend? It might even be set to shut down in a very short interval
for the initial run. Set the internal clock to the local date and time. Call the factory to
clarify any uncertainties about controller functions or settings before the initial start.
3. Compressor Package Cleaning and Inspection
Have a “ShopVac” available. Remove all access panels to completely expose all
compressor components for inspection. Vacuum the package thoroughly yourself or
directly supervise the cleaning. You are the only one who can determine what you
mean by “clean.” Then, remove all desiccant bags from compressor internals. All com-
pressors are shipped with moisture protection. Look in the interstage piping, which is a
good place to put desiccant bags to protect both stages. Remove all shipping restraints.
Check lubricant levels. Check the interstage and discharge automatic drains and ensure
that they will operate properly. If the drains are electronic type traps, test their opera-
tion with the electronic test option if provided. If they don’t operate properly, your
compressor will be damaged. Remember, compressors are water generators by nature
and the water must be removed or severe damage will occur. Ensure air coolers are free
of debris and the cooling fans rotate freely. For water-cooled units, ensure the closed
cooling water system is available. Again, call the factory to clarify any uncertainties
before the initial start. Advice should always be available, but do not call unless you
have thoroughly read the manufacturer’s instructions.
4. Aftercoolers
Check the cooler automatic functions. Do they start and stop when the compressor
motor starts, or are they controlled by a temperature switch? If the room or building
temperature varies with the weather, a temperature switch probably should control
them. This is especially true if there is a chance of subcooling or freezing. Change this
control function if field conditions dictate. Check the discharge drains and ensure they
have a visual means of ensuring proper operation.
5. Water Traps
All suspended free water generated in the compression process must be removed prior
to the air reaching the air dryers. Air dryers are designed to remove saturated moisture,
not free moisture.
6. Dryers
If not done so in the factory, desiccant dryers may have to be filled with an initial
charge. Check the dryer controls to ensure that the moisture option is activated. For
unheated regeneration, the compressor may operate loaded unnecessarily just for
regeneration if the moisture option is not selected. This happens for extended periods
if a timer presets regeneration. For heated regeneration, it can be an energy waste.
7. Filters
Check that the filter cartridges have been installed and differential pressure indication
is available.
8. Piping
Check the drain piping and ensure that all drains are piped separately to an open col-
lection point. It is essential that there is visual proof that each drain is functioning
properly. If they are connected to a common header, which is piped to a single drain,
remove them and re-pipe them separately. Remove permanently any isolation valves
at the drain discard. Also, it is a mistaken notion that check valves installed in the
separate drain legs will ensure proper operation of the header system. They are valves
and, as such, are subject to failure. Failure of a drain check valve can allow water to
severely damage the compressor. Check heat tracing for proper installation and opera-
tion. Remove heat tracing from piping if the local conditions don’t require it. It is best
to have all piping visible for routine inspection. Heat tracing requires insulation and
will cover multiple pipes obscuring the origin of the individual drains.
9. Instrumentation
All field-installed instrumentation must be calibrated and the data sheets inserted into the
startup binder for the system. For preinstalled instrumentation, it is a mistaken notion to
think that “skid”-mounted indicators do not require calibration. It is a fact that factories
do not calibrate indicators unless specified otherwise. They rely on vendor compliance.
And, vendor quality control inspections generally require only “spot” checks for quality
assurance unless specified otherwise. Nonetheless, shipping can be an extremely rough
process for equipment, which can undo any rigorous calibration performed at the origin.
Nevertheless, good judgment must be used. Generally, skid-mounted indicators do not
require a rigorous five point calibration. The reason is they generally provide indication
at a single point or narrow range. It is generally acceptable to ensure the instrument is
calibrated at the design operating point. Remember also, if several indicators measuring
the same parameter are reading differently, it will cause uncertainty, or worse, a sense of
instrument unreliability. All instrumentation providing protection outside the compres-
sor package, but mounted on the skid, must have a calibration check.
10. Electrical
The startup engineer is responsible for correct motor rotation. This must be verified
and the documentation indicating correct rotation must be entered into the startup
binder. Most small compressor packages have their own motor starters; therefore,
the motors must be bumped for rotation using the compressor controller. Caution
should be exercised when trial operating packaged units that have their own internal
“buckets.” Too frequently, during construction, phasing can change at motor control
center (MCC) or load center and go unnoticed because the power for the compressor
originates from a disconnecting device, not a starter. Therefore, the startup engineer
must investigate all MCC outages during startup operations of the equipment to
ensure that phase rotation has not been changed.
Preparation
Generally speaking, the compressor installation can be trial operated with only the air sys-
tem main headers available for operation. This is best for trial operation because the headers
must be blown first before the individual branch lines. Initial operation will pressurize the
air receivers, which will be used for performance and system leak testing. Therefore, it is
recommended that test instrument devices be installed to measure the air temperature and
pressure in the receivers. The receiver pressure will also be used to set the compressor load/
unload range.
Line Blowing
Ear protection is required because of the high noise levels during blows. Install temporary
ball valves at the end of each air system header. The valves will be used to blow the lines
clean. Ball valves are used because they can be rapidly opened by hand. With the air
receiver(s) at capacity blow, the headers use the expansion of air to atmosphere to provide
a high-impulse velocity. Blowing for 10 s several times or until no dust or debris can be
seen at the discharge should be sufficient to clean the lines. Now the device branch lines
can be blown through their isolation valves to atmosphere as they become available from
construction.
Testing
where:
Qscfm = specific volumetric flow rate
Vcf = air receiver volume
t = timed pressure loss in seconds/60
Tst /Tact = standard temperature (60°F)/actual temperature
P/Pst = pressure change/standard pressure (14.7 psia)
An engineering assumption can be made that the compression or expansion of the air
in the receiver is isentropic if an aftercooler is installed upstream. Therefore, differential
temperature is ignored. The basis of the assumption is that the after cooler heat removal
will cancel the heat of compression from P1 to P2.
Leak test the system in the reverse manner. Time system decay for a specific range using
a stopwatch. Determine the leakage with the same equation used for compressor capacity.
As each area in the system is commissioned, time the unloaded cycle of the compressor.
For example, when commissioning the boiler area, note the change in compressor loading.
Test for leakage. Build a historic signature for system leakage and compressor loading and
capacity.
Centrifugal compressor capacity and system demand can be tested by installing a flow
element at the discharge of the surge tank. Or the capacity can be calculated using the
equations in Fig. 1-8. The compressor must have constant flow through the surge tank at
all times. To accomplish this, create a temporary flow path to atmosphere for system tun-
ing and testing.
References