You are on page 1of 1

Application Information

Cable Size

Cooling only
FDN80HV1 FDN100HV1
Model Unit
RN80HY1 RCN100HY1
Indoor 220 - 240V / 1Ph / 50Hz +
Voltage range**
Outdoor 380 - 415V / 3Ph / 50Hz + N +
Power supply cable size*
a) Indoor Unit mm2 1.0 1.0
b) Outdoor Unit mm2 2.5 2.5
c) Total mm2 2.5 2.5
Number of conductors
a) Indoor Unit - -
b) Outdoor Unit 5.0 5.0
Interconnection cable size* mm2 1.0 1.0
Number of conductors 4.0 4.0
Recommended fuse/
circuit breaker rating*
a) Indoor Unit A 6.0 16.0
b) Outdoor Unit A 32.0 32.0
c) Total A 32.0 40.0

FDN125HY1 FDN150HY1 2FDN200HY1


Model Unit
RCN125HY1 RCN150HY1 RCN100HY1 x 2
Indoor 380 - 415V / 3Ph / 50Hz + N +
Voltage range**
Outdoor 380 - 415V / 3Ph / 50Hz + N +
Power supply cable size*
a) Indoor Unit mm2 1.0 1.0 1.0
b) Outdoor Unit mm2 4.0 10.0 2.5
c) Total mm2 4.0 10.0 -
Number of conductors
a) Indoor Unit 3.0 3 .0 5.0
b) Outdoor Unit 5.0 5.0 5.0
Interconnection cable size* mm2 1.0 1.0 1.0
Number of conductors 4.0 4.0 1.0
Recommended fuse/
circuit breaker rating*
a) Indoor Unit A 4.0 6.0 10.0
b) Outdoor Unit A 40.0 50.0 32.0
c) Total A 40.0 50.0 -

11

You might also like