14. Daily Maintenance

! WARNING
All routine and maintenance on the machine must be carried out solely by qualify-
ed personnel who have experience with this type of equipment. In guarantee peri-
od, DAKIN does not bear the cost for system fault without correct maintenance.

! CAUTION
Please copy appendix 1~3 in this operation manual and fill the daily maintena-
nce record.

Please maintain the unit according to the following list:


No. Item Maintenance requirements Corrective measure
Check running conditions daily. If the noise and vibration become more
The unit should run stably wi- obvious, stop the unit at once, and
thout abnormal noise. contact service personnel.
Check oil level in compressor
If the oil level is lower than 4/5 of the
daily from the compressor oil
lower oil sight glass obviously, stop the
Refrigerating sight glass. The oil level should
unit at once, and contact service per-
1 system be 1/3 above the upper oil sight
sonnel.
maintenance glass.
If there have not oil leakage but have oil
stains on the surface of unit component,
Check the surface of the unit
you may keep running the unit and
weekly to see whether there is
contact service personnel, if there have
oil leakage.
oil leakage, stop the unit at once and
contact service personnel.
If some rust appears on the surface,
Check if there is any rust on the
apply professional anti-rust treatment.
unit surface by impacting every
Good anti-rust treatment can extend the
month.
Unit surface unit’s life expectancy.
2
maintenance Check if there is any obstacle
on unit surface which will re-
Remove the obstacle.
duce the efficiency of air suc-
tion.
Check if there is any impurity in
the water filter, and if the filter Wash the impurity in filter, and change
net is integrity every three mo- the filter net if it is worn.
nth.
Hydraulic
If the water is muddiness, water piping
3 system
should be cleaned by professional per-
maintenance Check if the water quality meets
sonnel. The water in water tank should
the requirements every three
be replaced regularly (once every one to
months.
two years), and cleaning the bottom of
the tank.

©2017 DAIKIN
45

No. Item Maintenance requirements Corrective measure


Air side heat Check if there is any dirt or dust If dirt or dust is found on the surface, the
4 exchanger on the surface of the heat air side heat exchanger should be
maintenance exchanger every month. cleaned by professional personnel.
Rain season might cause some water
Check if any water accumulates flowing into the control cabinet. Stop
Maintenance in the control cabinet, and the power supply first and remove the water
5
in rainy days inspection door should be in the control cabinet. If there have the
closed well. ports for water leakage, please contact
service personnel.
Maintenance Check if any snow accumulates Remove the snow before starting the
6 in snowy on the top of the unit when start unit if there is much snow accumulated
days in snowy days. on the top of the unit.

15. Long Idle Period Maintenance

! CAUTION
If the unit is to be left idle for a long time in winter, completely drain water in the
system through the drain valve, otherwise the water side heat exchanger and
pipes may be damaged due to freezing.

If the unit is to be left idle for a long time, completely drain water in the pipes and the
unit. Otherwise water leakage and damages to the heat exchanger may occur due to freezing.
Especially in winter, water in idle units must be completely drained. You can also fill up the wat-
er system with antifreeze liquid after shutting down the unit. Contact DAIKIN for detailed
informa- tion about the density of the antifreeze liquid.
The power supply must be cut off; otherwise the electric heater in the crankcase is still
powered up and may waste energy.
Before starting the unit that is left idle for a long time, power up the unit 24 hours
beforehand. This ensures that the electric heater in the crankcase is powered up and that the
compressor is heated and conditioned for smooth operation.

©2017 DAIKIN
Appendix 1

Unit Maintenance and Inspection


Interval and running time After After After After After After After After After After After After After After After After After
3 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
months months years years years years years years years years years years years years years years years Replacement standard
Check List Begin-
2500 5000 20000 40000
ning
1.Pressure(Discharge and suction)
2. Oil level(Confirm that oil is present in the up oil sight glass.)
Daily inspection 3. Noise(Is there any abnormal noise?)
4. Check fan breakers(If they trip, find out cause and reset.)
5.Suction superheat and discharge superheat(Suction superheat should be higher than 2℃ and discharge superheat should be higher than 10℃.)
1. The color of refrigerant oil (New oil is clean. If the oil color shows puce or muddy, it is necessary to change the oil. If the oil color shows black, it is necessary to check the oil
filter in compressor.)
2. Check the liquid level and the color of the sight glass near the filter drier (If the test paper turns yellow, it means that water content in refrigerant is over standard. Normally,
Monthly inspection there are no bubbles and it is full liquid in the heating mode and there are few bubbles in cooling mode).The liquid level and the color of the sight glass on the EXV are not as
excessive water content criteria.
3. Check leakage in the refrigerant circle (is there oil around the pipes or any noise of leaking?)
4. Check the oil pressure drop (the difference between discharge pressure and oil pressure should be less than 1.0 bar; otherwise it is necessary to check the compressor.)
Bearing (Screw) ▲ ▲ Replace it if any abnormal operation
(sound, vibration) or debris particle is
Bearing (Gate Rotor) ▲ ▲
found during the inspection.
Casing ○ ○ ○ ○
Replace it if any chip, crack or similar is
Screw rotor ○ ○ ○ ○
found during the inspection.
Gate Rotor ○ ▲ ○ ▲
Replace it if any insulation resistance is
Motor ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲
Compressor abnormal during the inspection.
Solenoid valve ○ ○ ○ ○ ○ ▲ ○ ○ ○ ○ ○ ○ ○ ▲ Replace it if any insulation resistance is
Oil heater ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲ abnormal during the inspection.
Demister(in the oil separator) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Replace it if the differential pressure
Suction strainer ○ ○ ○ ○ ○ ○ ○ ○ ▲ ○ ○ ○ ○ ○ ○ ○ ▲ exceeds 0.5bar during operation.
Replace it if the differential pressure
Oil strainer ○ ○ ○ ○ ○ ▲ ○ ○ ○ ▲ ○ ○ ○ ▲ ○ ○ ○ ▲
exceeds 1.0 bar during operation.
Refrigerant oil ○ ○ ○ ○ ○ ▲ ○ ○ ○ ▲ ○ ○ ○ ▲ ○ ○ ○ ▲
Chemical clean ○ ○ ▲
Replace it if any leakage, heat exchan-
Water side Water reversed clean ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ge pipe broken or the pressure differe-
heat Check the pressure difference nce more than 1.5bar at rated volume
exchanger between inlet and outlet pipe (at ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ of water.
rated flow, less than 1.0 bar)
Fin (Remove surface dust, and
tease fins, then observer the Replace the coil if more than 1/3 of fin
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲
Air side condition of corrosion after or heat exchange pipe are abnormal.
heat removing dust.)
exchanger Heat exchange pipe, header,
distribution pipe ( whether exist ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Braze the broken point.
broken or flat)
Replace motor if any insulation resista-
Motor, fan ( insulation resistant,
Fan ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲ nce is abnormal.
fan blade distortion) Replace fan blade if any distortion.
Appendix 1 (continued)
Interval and running time After After After After After After After After After After After After After After After After After
3 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
months months years years years years years years years years years years years years years years years Replacement standard
Check List Begin-
2500 5000 20000 40000
ning
Replace it if any abnormal operation is
Expansion valve (can not control
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲ observed or can’t control the superheat
the superheat) during the inspection
Solenoid valve (any abnormal Replace it if any abnormal operation is
○ ○ ○ ○ ○ ○ ○ ○ ▲ ○ ○ ○ ○ ○ ○ ○ ▲
operation) observed during the inspection.
Valve
Check whether the safety valve is in
Safety valve ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲ the validation qualified period,
validation must be done if exceeded.
Replace it if any abnormal operation is
Check valve ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲
observed during the inspection.
Digital & analog control board ○ ○ ○ ○ ○ ○ ○ ○ ▲ ○ ○ ○ ○ ○ ○ ○ ▲
Fuse ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Break
Replace it if any contact with the
Contactor ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ serious corrosion or noise when run-
ning.
Control Box
Replace it if remains abnormal after
Sensor & transducer ○ ○ ○ ○ ○ ○ ▲ ○ ○ ○ ○ ○ ○ ○ ▲
corrected
High pressure switch ○ ○ ○ ○ ○ ○ ▲ ○ ○ ○ ○ ○ ○ ○ ▲ Controller alarm abnormally
Replace it if it can’t work correctly
Cooling fan ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲
during the inspection.
Power check(Rated
voltage±10%, Interlinked voltage ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
with unbalanced 2%)
Water Inspection (dirt, impurities) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
The pressure drops in dry filter more
Filter driers filter element(block,
○ ○ ○ ○ ○ ▲ ○ ○ ○ ▲ ○ ○ ○ ▲ ○ ○ ○ ▲ than 0.5bar or the sight glass shows
absorbent)
Others yellow.
Replace it if any insulation resistance is
Water side freeze prevent heater ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ▲
abnormal during the inspection
The fastener of Compressors, fan
and motor whether loosen ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
(re-tight)
Pressure calibration on the
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
controller
Ps: 1.○:According to the contents of the inspection items listed in the inspection, if unusual and included in the replacement standards are met replacement ▲:Replacement
2. For the parts replacement, refer to the operation time and interval, whichever is earlier.
3. The daily and monthly check list are operated and recorded by custom, others should be operated by DAIKIN serviceman.
4. The customer shall bear the maintenance expenses incurred by check and replacement involved in the above table.
5. If a system fault occurs because the customer fails to maintain the unit as required by the above table or maintenance is improper in the warranty period, DAIKIN shall not be responsible for it.