8 MV SWITCHGEAR RELAY SETTING AVAILABLE IN REALY


Over Current Protection Earth Fault Protection Over Voltage Protection Under Voltage Protection
IEp
SNO FEEDER CT RATIO VT RATIO Ip Drop - REMARKS
Ip TEp IEC curve I> TI> I>> TI>> IEp TIEp Drop - IEC curve IE> TEI> IE>> TIE>> U> TU> U>> TU>> U< TU< U<< TU<<
out
out
13.8 KV MV1 SWITCHGEAR
1 MV1.1 PROTECTION REALY AT INCOMER FROM MRMU-1
2 MV1.2 PROTECTION RELAY AT GENERATOR INCOMER FROM G1.3
3 MV1.3 600/1A 13800/110V 0.35 0.12 INST VI 3.5 0.08 3.5 0.08 0.08 0.1 INST VI 0.6 0.08 0.6 0.08 121 5 121 5 94 5 94 5
4 MV1.4 600/1A 13800/110V 0.35 0.12 INST VI 3.5 0.08 3.5 0.08 0.08 0.1 INST VI 0.6 0.08 0.6 0.08 121 5 121 5 94 5 94 5
5 MV1.5 600/1A 13800/110V 0.35 0.12 INST VI 3.5 0.08 3.5 0.08 0.08 0.1 INST VI 0.6 0.08 0.6 0.08 121 5 121 5 94 5 94 5
13.8 KV MV2 SWITCHGEAR
6 MV2.1 PROTECTION RELAY AT INCOMER FROM MRMU-2
7 MV2.2 PROTECTION RELAY AT GENERATOR INCOMER FROM G1.7
8 MV2.3 600/1A 13800/110V 0.35 0.12 INST VI 3.5 0.08 3.5 0.08 0.08 0.1 INST VI 0.6 0.08 0.6 0.08 121 5 121 5 94 5 94 5
9 MV2.4 600/1A 13800/110V 0.35 0.12 INST VI 3.5 0.08 3.5 0.08 0.08 0.1 INST VI 0.6 0.08 0.6 0.08 121 5 121 5 94 5 94 5
10 MV2.5 600/1A 13800/110V 0.35 0.12 INST VI 3.5 0.08 3.5 0.08 0.08 0.1 INST VI 0.6 0.08 0.6 0.08 121 5 121 5 94 5 94 5 UV OFF
13.8 KV GENERATOR SWITCHGEAR
11 G1.1 600/1A 13800/110V 0.2 0.35 INST VI 2 0.5 2 0.5 0.06 0.3 INST VI 0.35 0.5 0.35 0.5
12 G1.2 600/1A 13800/110V 0.2 0.35 INST VI 2 0.5 2 0.5 0.06 0.3 INST VI 0.35 0.5 0.35 0.5
13 G1.3 600/1A 13800/110V 0.35 0.25 INST VI 3.5 0.3 3.5 0.3 0.08 0.2 INST VI 0.6 0.3 0.6 0.3
14 G1.4 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03 NOT AVAILABLE
15 G1.5 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
16 G1.6 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
17 G1.7 600/1A 13800/110V 0.35 0.25 INST VI 3.5 0.3 3.5 0.3 0.08 0.2 INST VI 0.6 0.3 0.6 0.3
13.8 KV MV3 SWITCHGEAR
18 MV3.1 PROTECTION RELAY AT INCOMER FROM MV1.5
19 MV3.2 PROTECTION RELAY AT INCOMER FROMMV2.5
20 MV3.3 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
21 MV3.4 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
NOT AVAILABLE
22 MV3.5 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
23 MV3.6 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
13.8 KV MV4 SWITCHGEAR
24 MV4.1 PROTECTION RELAY AT INCOMER FROM MV1.4
25 MV4.2 PROTECTION RELAY AT INCOMER FROMMV2.4
26 MV4.3 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
27 MV4.4 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
NOT AVAILABLE
28 MV4.5 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
29 MV4.6 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
13.8 KV MV5 SWITCHGEAR
30 MV5.1 PROTECTION RELAY AT INCOMER FROM MV1.3
31 MV5.2 PROTECTION RELAY AT INCOMER FROMMV2.3
32 MV5.3 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
33 MV5.4 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
NOT AVAILABLE
34 MV5.5 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03
35 MV5.6 600/1A 13800/110V 0.12 0.1 INST VI 2 0.03 2 0.03 0.05 0.05 INST VI 0.25 0.03 0.25 0.03