New-generation PXF Series

Digital Temperature Controller

! ct ! dly !
n
Fast Compa
User
-frie

PXF9
96 × 96 mm
PXF5 PXF4
48 × 96 mm
48 × 48 mm

Features
Largest bright color LCD in the industry
High speed sampling : 50ms
Fast processing : 100ms
Universal input
The best-in-class compact : 58mm depth
Multidrop master fuction (option)

21B1-E-0062a1
Easy-to-See color LCD! Fast control!
Control output indicator Alarm output (DO) indicator

High contrast, Manual operation indicator


wide viewing
angle
Process value (PV)

Ramp/soak status

Set value (SV)


PID auto tuning indicator

Parameter number
MV Bar graph

User key
Select key Up key
7?-
Digit selector Down key

Tallest PV characters in the industry Universal input


Optimal bright and clear white PV display
Thermocouple
Temperature RTD
1 input
PXF4
Pressure 1 to 5 V DC,
etc.
15.3 mm
Flow rate 4 to 20 mA DC,
etc.
depth:
(PXF5: 18.1 mm 58 mm Easy switchover by parameter
setting
PXF9: 26 mm)

Multidrop master function Bus-powered USB interface equipped


Cooperative operation function Directly connectable to PC via USB port with optional cable.
SV can be transmitted to multi-PXFs through communication. No need of power supply to the PXF.
Synchronous temperature rise control is available in
combination with 2-degrees-of-freedom PID. 3HW[VW7*

L_,_[Y\KLY
69 69 69
56

<:)

0DVWHU 6ODYH 6ODYH 6ODYH AVUL   


=RQH =RQH =RQH =RQH <:)3VHKLY*HISL
Multi-zone control

Parameter copy function


Parameter settings can be copied to multi-PXFs
simultaneously and easily through communication.

Smart Ramp-Soak up to 64 segments/ Position feedback and servo control is available to


15 patterns valve control

Simple power monitoring function/preventive


maintenance alarm

Free loader software - user-friendy key operation 2SHQRXWSXW


and easy to find parameters.
&ORVHRXWSXW

3RWHQWLRPHWHU 7HPS
6HQVRU

7HPS3URFHVV

2
■ Versatile controller for any applications
Type PXF4 PXF5 PXF9
PXF 9
Appearance

Front panel size 48 × 48 mm 48 × 96 mm 96 × 96 mm


Depth 58 mm
Display digits 4-digit (PV and SV)
Character height (PV) 15.3 mm 18.1 mm 26 mm
Indication accuracy RTD input: ±0.2% ±1 digit or ±0.8°C±1 digit, whichever is larger
Thermocouple input: ±0.3%±1 digit or ±1°C±1 digit, whichever is larger
Voltage and current input: ±0.3%FS±1digit
Sampling rate 50 ms
Input signal Process value input Universal input (RTD, thermocouple, voltage/current)
Option Remote SV input Voltage/current
Current transformer (CT) input Dedicated CT (1 to 100 A)
Motorized valve position input - 100Ω to 2.5kΩ (3-wire)
Digital input (DI) Up to 3 points Up to 5 points
Output Control Relay contact ●
signal output
SSR/SSC drive output ●
Current output (linear) ●
Voltage output (linear) ●
Option Motorized valve control output ●
Analog re-transmission output
(voltage) ●
Analog re-transmission output
(current) ●
Heater burnout alarm ●
Operating days alarm ●
Alarm/event contact output (DO) Up to 3 points Up to 5 points
Control method ON/OFF control ●
(*with auto tuning)
PID control* ●
Fuzzy control* ●
2-degrees-of-freedom PID control* ●
Open-loop system supported
(PID2 control) ●
Self tuning ●
Ramp/soak
up to 64 steps
(simple program control)
Option Heating/cooling control* ●
Motorized valve control ●
Function Number of PV/PID patterns Up to 8
SV/PID switchover ●
Soft start ●
Simple power-monitoring ●
Operating days ●
Manual operation ●
User key ●
Communi- Loader interface ●
cation
Option RS-485 (MODBUS) ●
Power sup- 100 to 240 V AC, 50/60 Hz ●
ply voltage
Option 24 V DC/AC ●
Power consumption 10 VA MAX. 13 VA MAX. 13 VA MAX.
Screw terminals for external connection M3
Note: Some functions may be unavailable depending on the model. For more detail, please refer to the specifications.

3
■ Advanced control functions
Parameter setting is available using the front keys or a PC with loader software.

Standard On/Off control Optional Heating/cooling control with auto tuning


functions PID control with auto tuning functions Motorized valve control
Fuzzy control with auto tuning
2-degrees-of-freedom PID control with auto tuning
Open-loop supported PID2 control
Self tuning
Ramp soak function (simple program control)

On/Off control PID control with auto tuning


When process value (PV) is below the set value (SV), output is turned on Typical PID control.
and the heater is energized as shown below. When PV is above SV, output Overshoot may occur due to external disturbance.
is turned off and the heater is de-energized. In this way, output is turned
on/off repeatedly with respect to the SV to keep the temperature constant.
This method of control is called “on/off action (2-position action)”
* When “0” is assigned to parameter P, the on/off action will be selected.
*VU[YVSJOHYHJ[LYPZ[PJVM656--HJ[PVU
/`Z[LYLZPZ

:L[
]HS\L

:L[]HS\L

;PTL
6]LYZOVV[YLZWVUZL
[VKPZ[\YIHUJLZ
65
/LH[LY
6--

Fuzzy control with auto tuning 2-degrees-of-freedom PID control with auto tuning
Fuzzy control is used to suppress overshoot so that the response to This function achieves stable control against external disturbances,
external disturbance is improved. By monitoring PV, overshoot is sup- while suppressing overshoot and undershoot at startup or at SV change.
pressed with startup time remaining unchanged. Also, disturbance ÷GHJUHHVRIIUHHGRP3,'
÷&RQYHQWLRQDO3,'
can be settled quickly.  EHIRUHDGMXVWLQJαDQGβ)
7YVJLZZ]HS\L 7YVJLZZ]HS\L
● Comparison between fuzzy control and conventional control
:= :=

Fuzzy control Conventional control PV 7=

;PTL ;PTL
:L[]HS\L :L[]HS\L ÷GHJUHHVRIIUHHGRP3,'
 ZLWKRSWLPDOαDQGβ)
7YVJLZZ]HS\L
6]LYZOVV[9LZWVUZL[V 6]LYZOVV[9LZWVUZL[V :=
KPZ[\YIHUJLZ KPZ[\YIHUJLZ
7=

;PTL

Open-loop supported PID2 control Self tuning


Reduces overshoot in the processes where the control target is At power up, SV change, or during external disturbance, tuning is
turned off and then on again. made automatically so that the PID parameters are re-optimized.
7YVJLZZ]HS\L
6]LYZOVV[PZJVU[YVSSLK

:=

External
disturbance
7=
Set value change

[
65 Power on
7V^LYZ\WWS`[V
JVU[YVSLX\PWTLU[
6--
Note: For some objects of control, PID values can not be optimized.
*SVZL *SVZL
*VU[YVSSVVW
6WLU

4
Ramp soak function (simple program control) Temperature gradient control of furnace
For control in a heat pattern
Function of automatically changing the set point value with
+PNP[HSPUW\[
the elapsing of time, in accordance with the preset pattern, as 9HTWZVHRHJ[PVUJVTTHUK
shown below. This function is capable of programming 15 pro- 65!:[HY[
6--!9LZL[ ;LTWLYH[\YLPUW\[
gram patterns. Max.64 steps.
:= ,_HTWSLVMZ[LWZ_WH[[LYUZ ;OLYTVJV\WSL
Z[LW Z[LW
:=
4H_Z[LWZ -\YUHJL
:= :=
Z[LW := :=
:= := ::9KYP]L
:= := := V\[W\[
:=
:= :=
::9
:=

7=
:= := [Ramp soak function]
;4Y ;4Z ;4Z ;4Y ;PTL ;LTWLYH[\YLYPZLMHSSWH[[LYUPZJVU[YVSSLKI`ZL[[PUNHOLH[WH[[LYUOH]PUN
;4Y ;4Z HNYHKPLU[(J[PVUZ[HY[YLZL[PUNJHUILJVTTHUKLKL_[LYUHSS`
Z[LW[V!WH[[LYU Z[LW[V!WH[[LYU Z[LW [V!WH[[LYU Z[LW[V!WH[[LYU
:=
:=
■Basic functions ■Number of steps ■Operation :=

:L[]HS\L
① [h · min] or [min · s] and patterns Start/stop/suspension :=
② Guarantee soak Steps Patterns can be performed by :=
various ways (a user :=
③ Repeat action 64 1
:=
④ PV start 32 2 key, parameter set- :=
⑤ Delay start 16 4 ting, digital input, or
⑥ Power failure recovery 8 8 communication) ;PTL

PID auto tuning Temperature control of plastic molding machine


Start/stop of auto tuning can be commanded externally.
PID parameters are automatically set by the controller's measurement and
+PNP[HSPUW\[
computation function. This instrument provides 2 types of auto-tuning func- (\[V[\UPUNJVTTHUK
65!Y\U
tions; the standard type (auto-tuning with SV used as reference) and the low 6--!Z[VW

SV type (auto-tuning with the value 10% below SV used as reference).


;LTWLYH[\YLHSHYT
(a) Standard type (b) Low-PV type 7= ;\UPUN
(;Z[HY[ (;LUK70+ZL[\W (;Z[HY[ (;LUK70+ZL[\W ;LTWLYH[\YLPUW\[
(;JVTW\[H[PVU (;JVTW\[H[PVU :=
4VSKPUNTHJOPUL
::9 ::9 9H^TH[LYPHSZ
:L[]HS\L
:L[]HS\L
65 65
:= ;LTWLYH[\YL
:= :=
PUW\[
7=WYVJLZZ]HS\L

7=WYVJLZZ]HS\L
*VU[YVSV\[W\[
*VU[YVSV\[W\[

65 65
65 65 65 65

6-- 6-- 6-- 6-- 6-- Heater


6--
70+JVU[YVS 70+JVU[YVS
656--HJ[PVU 656--HJ[PVU

Heating/cooling control (option) Energy saving in livestock barns


● Both heating and cooling are controlled with only one temperature
controller utilizing its 2 control outputs.
By a single controller, both heating and cooling control output are obtained. ● Power consumption can be curbed by controlling a cooling fan
motor with inverter.
Output Output
Heating side Cooling side Heating side Cooling side
;LTWLYH[\YLPUW\[ZPNUHS
Coefficient 0.5
Coefficient 1.0 4V[VYVMJVVSPUNMHU *\YYLU[
9VVT V\[W\[
Coefficient 2.0 M
[LTWLYH[\YL
Deviation Set value (SV) Deviation Deviation Deviation
(-) Overlap
(-) Heating side Cooling side (+) band Dead band (+)
proportional band proportional band Inverter *\YYLU[
V\[W\[
Proportional band (P) Set value (SV)

PUZOLK
Note: For the cooling side proportional band, set a coefficient with /LH[LYWV^LY
;VOLH[LY Z\WWS`
respect to the heating side proportional band. *H[[SLZOLK
(ON-OFF control if coefficient is 0.) (79

Motorized valve control (option) Heating/cooling control of air conditioner


*VTTHUKZ^P[JO

· Position feedback control based on motorized valve :\TTLY>PU[LY


*SVZLPUZ\TTLYVWLUPU^PU[LY
position signal :^P[JOPUN
6WLUPUZ\TTLYJSVZLPU^PU[LY :\TTLY!5VYTHSHJ[PVU
· Servo control without valve position signal >PU[LY!9L]LYZLHJ[PVU
=HS]LJVU[YVS
JVTTHUKV\[W\[

/V[^H[LY
:VSLUVPK]HS]L =HS]LWVZP[PVU
ZPNUHS
YLZPZ[HUJL ;LTWLYH[\YLZLUZVY
M

*VSK^H[LY (PY
JVUKP[PVULY
:VSLUVPK]HS]L 4V[VYPaLK]HS]L

5
■ Even more functions which extend the possibilities of temperature controller
Standard SV and PID selection Optional Re-transmission output
functions Soft start functions Remote SV input
Simple power-monitoring Heater burnout alarm
Operating days alarm Alarm output
Digital input
RS-485 Communication

SV and PID selection Soft start


Allows you to register up to 8 sets of SV setting and PID set- This function controls the maximum output produced when
ting, and to switch among them, enabling optimum PID set- turning on the equipment (including the temperature controller).
ting for changing process, materials, or PV. You can perform This function is useful for effects such as suppressing the heat-
SV selection only, or PID selection only. er output during equipment startup, or lightening the load.

*VU[YVSV\[W\[4= 4=^P[OV\[ZVM[Z[HY[

:=Z^P[JOPUN
::9KYP]L
70+Z^P[JOPUN V\[W\[ :VM[Z[HY[V\[W\[
::9 ZL[]HS\L
73*
MV with soft start
SPTP[LK
69 69 69 69
:=Z^P[JOPUN

 [
70+Z^P[JOPUN :VM[Z[HY[ZL[[PTL
7HSL[[L 7HSL[[L 7V^LY65VY
7HSL[[L +PNP[HSPUW\[65

Simple power-monitoring Operating days alarm


Calculates the energy consumption by connecting an op- ① Operating days This function is useful for preven-
tional current transformer. (See page 10.) indication tive maintenance because it let
>P[O*; >P[OV\[*; ② Operating days you know the appropriate time for
/LH[LYSVHK ,Z[PTH[LK]VS[HNL /LH[LYSVHK ,Z[PTH[LK]VS[HNL alarm output maintenance work.
7?- 7?-
7HYHTL[LYZL[[PUN 7HYHTL[LYZL[[PUN
 3VHK]VS[HNL=  3VHK]VS[HNL=
,ULYN` ,ULYN`
× JVUZ\TW[PVU × JVUZ\TW[PVU
(* (* 65[PTL R>O
R>O
7HYHTL[LYZL[[PUN
3VHK 0.2
*VU[YVSV\[W\[ J\YYLU[ *VU[YVSV\[W\[ 3VHK
*; J\YYLU[ (SHYT
4LHZ\YLZ
HJ[\HSJ\YYLU[ *;PUW\[
(SHYTPZ[YPNNLYLK^OLU[OLVWLYH[LKKH`Z
,Z[PTH[LKJ\YYLU[ YLHJO[OL]HS\L`V\ZL[
=VS[HNL!LZ[PTH[LK]HS\LZL[I` =VS[HNL!LZ[PTH[LK]HS\LZL[I`
\ZLY=  \ZLY=
*\YYLU[!]HS\LTLHZ\YLKI`*; *\YYLU[!LZ[PTH[LK]HS\LZL[I`
 \ZLY(

Re-transmission output (option) Remote SV input (option)


A cost corresponding to one temperature sensor can be re- SV can be configured externally.
duced just by connecting a PV transfer signal to a recorder. • Input signal (any one of the followings):
• Output signal (any one of the followings): 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC, 0 to 20 mA DC,
0 to 20 mA DC, 4 to 20 mA DC, 0 to 5 V DC, 1 to 5 V DC,
0 to 10 V DC, 4 to 10 V DC 4 to 20 mA DC
• Output type: • Input impedance: About 1 MΩ
process value (PV), set value (SV), control output (MV),
or PV-SV (DV)
:LX\LUJLY

PV transfer :L[[LTWLYH[\YL:=
output [V=+*
;LTWLYH[\YLPUW\[

=VS[HNLJ\YYLU[ -Y`LY
*\YYLU[
JVU[YVSZPNUHS *VU[YVS ;LTWLYH[\YL
Recorder PHR V\[W\[ PUW\[
6PS
(*WV^LYYLN\SH[VY
(79 /LH[LY *LSS( *LSS) *LSS* *LSS+ *LSS,
;OL[LTWLYH[\YLVMLHJOJLSSPZZL[I`[OLZLX\LUJLY

6
Heater burnout alarm (option) Alarm output (option)
• A current transformer (CT) is required. (See page 10, optional items). Up to 3 points 
• The power supply voltage and the alarm action point need
to be configured beforehand. (SHYT[`WL (J[PVUKPHNYHT
• Available only for single-phase heater
• Not available when using thyristor phase angle control <WWLYSPTP[HIZVS\[L]HS\L 7=

(IZVS\[L]HS\LHSHYTZ
[Example of PXF5/PXF9] (3U
7V^LYZ\WWS`[V=(*/a

3V^LYSPTP[HIZVS\[L]HS\L 7=
 (3U
7V^LYZ\WWS`

*VU[YVSV\[W\[ <WWLYSPTP[HIZVS\[L]HS\L
 
^P[OOVSK 7=
(3U
 
/LH[LYI\YUV\[
+ -
HSHYTV\[W\[ 3V^LYSPTP[HIZVS\[L]HS\L
0*    
^P[OOVSK 7=
6: (3U
*\YYLU[ ,SLJ[YVTHNUL[PJZ^P[JO (3U
[YHUZMVYTLY <WWLYSPTP[KL]PH[PVU 7=
*; :=
;OLYTVJV\WSL (3U
3V^LYSPTP[KL]PH[PVU 7=
:=

Deviation alarms
>PYLK[V7?-
/LH[LY
^P[OUVWVSHYP[`
<WWLYHUKSV^LYSPTP[Z (3U (3U
,SLJ[YPJM\YUHJL
KL]PH[PVU 7=
:=

<WWLYSPTP[KL]PH[PVU (3U
^P[OOVSK 7=
>PYLK[VOLH[LY[OYV\NOOVSLPU*; :=

3V^LYSPTP[KL]PH[PVU (3U
^P[OOVSK 7=
:=

Digital input (option) <WWLYHUKSV^LYSPTP[Z (3U (3U


7=
KL]PH[PVU^P[OOVSK :=
For SV changeover, AT startup, timer startup, program se- 9HUNL\WWLYHUKSV^LYSPTP[Z (3U (3U
lection, start/stop/reset, PID changeover, etc. KL]PH[PVU
7=
(34PUKLWLUKLU[VWLYH[PVU :=
+PNP[HSPUW\[ 9HUNL\WWLYHUKSV^LY 7=
:=JOHUNLJVTTHUK
SPTP[ZHIZVS\[L]HS\L (3 (3
Range alarms

Changeover of 4 set
::9KYP]L ::9KYP]L
values (front SV, SV1 to 9HUNL\WWLYHUKSV^LY (3 (3
V\[W\[ V\[W\[
SV3) can be commanded
::9 ::9 externally. SPTP[ZKL]PH[PVU 7=
:=
6]LU
(3
9HUNL\WWLYSPTP[HIZVS\[L
;LTWLYH[\YL ]HS\LHUKSV^LYSPTP[KL]PH[PVU 7=
PUW\[
:= (3
(3
9HUNL\WWLYSPTP[KL]PH[PVU
HUKSV^LYSPTP[HIZVS\[L]HS\L 7=
;LTWLYH[\YLPUW\[ (3 :=

RS-485 Communication (option) • Programless communication


PXF can be connected with PLC without a program.
• High-speed communication (user address mapping function)
7YVNYHTSLZZOVZ[JVTT\UPJH[PVU
You can make a list of your most necessary parameters
(max. 32 words) to quickly acquire those data at a time.
Communication speed: max. 115.2 kbps

Address Parameter ;LTWLYH[\YL PXF4


30001 PV Max.32 words JVU[YVS
PXF9
30002 SV(Read) Address Parameter 9LMSV^ZVSKLYPUNKL]PJL PXF5
30003 DV 30001 PV

30004 MV1 30002 SV(Read)

. . 40003 SV(Write) • PXFs can be connected with PC, programmable operation


. .
. . 30004 MV1 display, or PLC.
40006 P
40003 SV(Write) 7YVNYHTTHISLVWLYH[PVUKPZWSH`
40007 I
40004 STBY
40008 D
40005 AT
40006 P . .
. .
. .
40007 I
– –
40008 D 9:*
. . – –
. .
:PNUHSJVU]LY[LY
. . – – 9:46+)<: 4H_JVU[YVSSLYZ
JVUULJ[HISL

7?- 7?- 7?- 7?-

7
■ Specifications
■ General specifications ■ Control output
Power supply voltage 100 (-15%) V to 240 (+10%) V AC, 50/60Hz Number of point Up to 2 (2 points: Heating/cooling control)
24 V DC/AC (±10%) Type ① Relay contact output (SPST)
Power consumption Type 100 to 240 V AC 24 V DC/AC Select among  • Proportional cycle: 1 to 150 s
PXF4 10 VA MAX. 3 VA MAX. ① to ⑥ below  • Contact structure: 1 SPST contact *SPST:
single pole single throw
PXF5 & 9 13 VA MAX. 8 VA MAX.
 • Contact capacity: 250 V AC/30 V DC, 3 A (resistive load)
Insulation resistance 20 MΩ or more (at 500 V DC)  • Minimum ON/OFF current: 10 mA (5 V DC)
Withstand voltage Power source ⇔ all terminals: 1500 V AC for 1 min  • Mechanical life: 20 million operations MIN. (100 operations/min)
Relay contact output ⇔ all terminals: 1500 V AC for 1 min  • Electrical life: 100,000 operations MIN. (rated load)
Between others: 500 V AC for 1 min ② Relay contact output (SPDT)
 • Proportional cycle: 1 to 150 s
■ Process value input  • Contact structure: 1 SPDT contact
Number of input 1 *SPDT: single pole double throw
 • Contact capacity: 250 V AC/30 V DC, 5A (resistive load)
Input setting Programmable scale
 • Mechanical life: 50 million operations MIN. (100 operations/min)
Input signal See Table 1  • Electrical life: 100,000 operations MIN. (rated load)
(Universal input: thermocouple/RTD/voltage/current) ③ SSR/SSC drive output
Standard measurement See Table 1  • Proportional cycle: 1 to 150 s
range and input type  • ON voltage: 12 V DC (between 10.7 and 13.2 V DC)
 • OFF voltage: 0.5 V DC or lower
Indication accuracy • Thermocouple input: either ±1°C ±1 digit or  • Maximum current: 20 mA DC
(at Ta = 23°C) ±0.3% ±1 digit of indicated value, whichever is larger  • Load resistance: 600 Ω MIN.
*except: ④ Current output (0 to 20 mA DC/4 to 20 mA DC)
Thermocouple B: 0 to 400°C: no accuracy assurance  • Accuracy: ±5%FS
Thermocouple R: 0 to 500°C: ±3°C ±1 digit  • Load resistance: 500 Ω MAX.
All thermocouples: -200 to -100°C: ±2°C ±1 digit ⑤ Voltage output (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC)
• RTD input: ±0.8°C ±1 digit or  • Accuracy: ±5%FS
±0.2% ±1 digit of indicated value, whichever is larger  • Load resistance: 10 kΩ MIN.
• mV input, voltage input, current input: ±0.3%FS ±1 digit ⑥ Motorized valve control output
Temperature effect on ±0.3%FS/10°C  • Contact structure: 2 SPST contacts without interlock circuit
sensitivity *SPST: Single Pole Single Throw
 • Contact capacity: 250 V AC/30 V DC, 3 A (resistive load)
Indication resolution See Table 1
  Minimum ON/OFF current: 100 mA (24 V DC)
Sampling rate 50 ms  • Mechanical life: 20 million operations MIN. (100 operations/min)
Input impedance • Thermocouple, mV input: 1 MΩ or more  • Electrical life: 100,000 operations MIN. (rated load)
• Current input: 150 Ω or less (built-in diode)
• Voltage input: About 1 MΩ ■ Alarm output (DO) (option)
Variation by signal source • Thermocouple, mV input: ±0.3%FS ±1 digit per 100 Ω Number of outputs Relay contact output: up to 5 (shared common) PXF4: up to 3
resistance • Voltage input: ±0.3%FS ±1 digit per 500 Ω          up to 3 (independent common) PXF4: up to 2
Allowable wiring resis- • RTD: 10 Ω MAX. (per wire) Output specifications Relay contact output
tance Contact structure: 1 SPST contact *SPST: single pole single throw
Allowable input voltage: • DC voltage input: within ±35 V Contact capacity: 250 V AC/30 V DC, 1A (resistive load)
• Current input: within ±25 mA Minimum ON/OFF current: 10 mA (5 V DC)
• Thermocouple, RTD, mV input: within ±5 V Mechanical life: 20 million operations MIN. (100 operations/min)
Noise reduction ratio • Normal mode: 40 dB (50/60 Hz) Electrical life: 100,000 operations MIN. (rated load)
• Common mode: 120 dB (50/60 Hz) Output functions Alarm output (see "Alarm function"), main unit control mode output,
• Between input and power supply: ±1°C at 220 V AC, 50/60 Hz program status output, control output 1 and 2, etc.
Input correction: (a) User adjustment: ±50%FS for each of zero and span point Output cycle 100 ms
(b) Process value shift: ±10%FS
(c) Input filter: 0.0 to 120.0 s ■ Re-transmission output (option)
(filter OFF if set at 0.0)
Number of point 1
(d) Square root extraction: -0.1 to 105% (OFF if set to -0.1%)
Overrange · Out of the range between -5 to 105% of FS Type Current/voltage output (0 to 20 mA DC/4 to 20 mA DC/0 to 5 V DC/
underrange (accuracy not guaranteed between -5 and 0, and between 100 and 1 to 5 V DC/0 to 10 V DC/ 2 to 10 V DC)
105%FS) • Guaranteed output range: 0 to 21mA DC/0 to 10.5 V DC
*except: • Accuracy: ±0.2%FS (±5%FS at 1 mA or smaller)
 • JPt (-199.9°C to 600.0°C) input: • Resolution: 10,000 MIN.
Out of the range between • Load resistance: 500 Ω MAX. (current), 10 kΩ MIN. (voltage)
 • Pt (-200°C to 850°C) input:
-2% to 105% of FS
 • 0 to 10 V DC input: Output cycle 100 ms
 • Thermocouple E: Out of the range between -5 to 102% of FS Output contents PV, SV, DV, MV
■ Remote SV input (option) Additional function Scaling function

Number of input 1
■ Display unit
Input signal Voltage: 0 to 5 V DC/1 to 5 V DC/0 to 10 V DC
Current: 0 to 20 mA DC/4 to 20 mA DC Type LCD (with backlight)
(an external 250-ohm resistor is required for current input) Indication contents Process value indication: 11-segment, 4-digit [white]
Input impedance Approx. 1 MΩ Setpoint indication: 11-segment, 4-digit [green]
Screen No. indication: 7-segment, 4-digit [orange]
Sampling rate 50 ms
Indication status: 42 indicator lamps
■ Current transformer (CT) input (option) Luminance setting possible (4 steps)

Input type Single phase CT, 1 point ■ Setting section


For 1 A to 30 A: CTL-6-S-H
For 20 A to 100 A: CTL-12-S36-8 Type and number of keys Sheet type keys (with emboss), 5 keys
Range of detected current 1 A to 100A
Detected current accuracy Setpoint ±5%FS
■ Control functions
Detected current resolu- 0.1 A ON/OFF control Refer to page 4.
tion PID control • Dual control (heating/cooling)
ON time necessary for 300 ms MIN. • PID parameters determination: Auto tuning
detection Fuzzy PID control • Dual control (heating/cooling)
• PID parameters determination: Auto tuning
■ Digital input (DI) (option) Self tuning control Refer to page 4.
Number of point up to 5 (PXF4: up to 3)
PID2 control • Dual control (heating/cooling)
Specification No-voltage contact or transistor input • PID parameters determination: Auto tuning
Contact capacity: 5 V DC, about 2 mA (per point) 2-degrees-of-freedom PID • PID parameters determination: Auto tuning
Input judgment: ON voltage: 2 V DC or lower
Position proportional • Full stroke time: 30 seconds MIN.
OFF voltage: 3 V DC or higher
PID (servo) with position (not available for PXF4)
Sampling pulse width 50 ms MIN. feedback
Function Remote mode selection, SV changeover, control standby, AT startup,
timer startup, alarm unlatch, program selection, start/stop/reset, PID ■ Control parameters
switching (normal/reverse), etc.
Proportional band (P) 0.1% to 999.9%
■ Valve position feedback signal (Potentiometer) input (option) Integration time (I) 0 to 3200 s (invalidated when I = 0)
Model PXF5 and PXF9 (not available for PXF4) Differential time (D) 0.0 to 999.9 s (invalidated when D = 0)
Resistance range 100 Ω to 2.5 kΩ (three-wire) Control cycle 100 to 900 ms (in 100 ms), 1 to 99 s (in seconds)
Resolution 0.5%FS Anti-reset windup 0 to 100% of measurement range
Accuracy ±1.0%FS
Hysteresis band 50% of measurement range (at 2-position control only)
Temperature effect on ±0.5%FS/10°C
sensitivity Number of SV and PID 8: Changed by any of parameter setting, digital input, communica-
patterns tion, user function keying, zone change.
Burnout function Not provided

8
■ Control mode ■ Structure
Mode Auto/Manual/Remote Mounting method Panel mount
*During 2-position control in Manual mode,
External terminals Screw terminals, M3
2-position manual operation with MV = 100% or 0% is operated.
  Case • Material: ABS, PPO
Mode changeover: • Auto <=> Manual: Balanceless・bumpless • Non-combustibility grade: UL94V-0 equivalent
• Auto/Manual→Remote: Balance・bumpless • Color: Black
• Auto/Manual→Remote: Balance・bumpless Protection structure • Panel front side: IP66, NEMA-4X equivalent
(When the panel is mounted using our genuine packing.
■ Alarm function Not water-proof if mounted closely together.)
• Body: IP20 equivalent (slits on top and bottom)
Number of alarm setting Up to 5 (depends on the number of DO)
• Terminals: IP00 equivalent. Terminal cover can be provided
points
optionally.
Alarm type Process value (upper limit/lower limit, absolute/deviation,
Dimensions Refer to page 14.
range), main unit error, etc.
(non-excitation, delay, latch, timer function option provided) Weight PXF4: approx. 100 g, PXF5: approx. 170 g,
Heater current alarm *Current detector(CT) is to be prepared separately PXF9: approx. 220 g
function (optional) (see page 10.)
■ User customize function and Program (ramp/soak) function
Detectable range 1 A to 100 A Number of program 64 steps x 1 patterns,
steps 32 steps x 2 pattern,
16 steps x 4 pattern, or
Detected current reso- 0.1 A
8 steps x 8 patterns
lution
(1 step = 2 segments)
Setting resolution 0.1 A
Control option: Control by digital input
Hysteresis 0.0 to 100.0 A Status output by digital output
Basic functions [1] Segment time can be set in "Hour, Minutes" or "Minutes,
■ RS-485 communication (option) Seconds"
No. of points 1 ② Guarantee soak
③ Repeat action
Physical specifications EIA-485 ④ PV start
Protocol Modbus-RTU ⑤ Delay start
Communication method Half-duplex bit serial, asynchronous communication ⑥ Power restoring function
Memory backup EEPROM
Code type Data length: 8 data bits. Parity: Odd, even, none.
Baud rate 9600 bps, 19200 bps, 38.4 kbps, 115.2 kbps ■ User functions
Connection Up to 32 units connectable including multidrop master func- User key assignment Auto/Manual change, Standby ON/OFF change, remote SV
tion change.
Communication Up to 500 m (total connection length)
distance ■ Password function
Additional functions • Cooperative operation 3-level password
The function in which slave devices can be operated via
master device by connecting several temperature control- ■ Simple power-monitoring function and operating days alarm
lers.
• Programless communication Simple power- • By connecting a current transformer (to be prepared sepa-
The function in which a temperature controller can be con- monitoring function rately), electric power consumption of the heater can be
nected to a PLC without program. displayed. (Electric power is calculated based on the fixed
Supported PLCs: Mitsubishi PLC Q series voltage value you set.)
        Siemens PLC S7 series • Current detector(CT) is to be prepared separately
(see page 10.)
■ Operation and storage conditions • Current detection range: 1 A to 100 A
Operating temperature -10°C to 50°C Operating days alarm • Indicates the number of days the controller has been oper-
ated and activates alarm output (optional) when it exceeds
Storage temperature -20°C to 60°C the setpoint.
Operating/storage 90%RH or less (Non condensation) • Useful for preventive maintenance because it let you know
humidity the appropriate time for maintenance work.
Warm-up time 30 min MIN. ■ Processing at power failure
Vibration during transportation: 9.8 m/s2 (1 G) or less
2
Memory protection Protect by non-volatile memory
Impact during transportation: 294m/s (30 G) or less
■ Self-diagnosis
Method: Program error supervision by watchdog timer

Table 1 input type and range


Measurement range Minimum input Measurement range Minimum input
Input type Code (PvT) Input type Code (PvT)
[°C] increment [°C] [°C] increment [°C]
Pt 100 PT1 0.0 to 150.0 0.1 Thermocouple J J1 0.0 to 400.0 0.1
PT2 0.0 to 300.0 0.1 J2 -20.0 to 400.0 0.1
PT3 0.0 to 500.0 0.1 J3 0.0 to 800.0 0.1
PT4 0.0 to 600.0 0.1 J4 -100 to 1000 1
PT5 -50.0 to 100.0 0.1 K K1 0 to 400 0.1
PT6 -100.0 to 200.0 0.1 K2 -20.0 to 500.0 0.1
PT7 -199.9 to 600.0 0.1 K3 0.0 to 800.0 0.1
PT8 -200 to 850 1 K4 -200 to 1300 1
DC voltage 0 to 5 V DC 0-5V R R 0 to 1700 1
1 to 5 V DC 1-5V B B 0 to 1800 1
0 to 10V DC 0-10 -1999 to 9999 (Range S S 0 to 1700 1
2 to 10V DC 2-10 where scaling is - T T1 -199.9 to 200.0 0.1
0 to 100mV DC MV allowed) T2 -199.9 to 400.0 0.1
DC current 0 to 20mA DC 0-20 E E1 0.0 to 800.0 0.1
4 to 20mA DC 4-20 E2 -150.0 to 800.0 0.1
E3 -200 to 800 1
L L -100 to 850 1
U U1 -199.9 to 400.0 0.1
U2 -200 to 400 1
N N -200 to 1300 1
W W 0 to 2300 1
PL-II PL-2 0 to 1300 1

9
■ ORDERING CODE
#_TTZPaL% #_TTZPaL%
4V[VYPaLK]HS]LJVU[YVS[`WLIHZLTVKLS!7?- 4V[VYPaLK]HS]LJVU[YVS[`WLIHZLTVKLS!7?-
+PNP[ :WLJPMPJH[PVUZ *VKL +PNP[ :WLJPMPJH[PVUZ *VKL
 #-YVU[WHULSZPaL>_/%  #-YVU[WHULSZPaL>_/%
×TT 7?- ×TT 7?-
   (    (
 #*VU[YVSV\[W\[%  #*VU[YVSV\[W\[%
9LSH`JVU[HJ[:7:;5V[L ( 4V[VYPaLK]HS]LJVU[YVSV\[W\[^P[O7-)PUW\[ ;
9LSH`JVU[HJ[:7+;5V[L )  #*VU[YVSV\[W\[%
::9KYP]LV\[W\[ * 5VUL @
*\YYLU[V\[W\[ ,  #9L]PZPVUJVKL% 
=VS[HNLV\[W\[ 7 #(SHYTV\[W\[%
 #*VU[YVSV\[W\[% 5VUL 
5VUL @ WVPU[ 
9LSH`JVU[HJ[:7:; ( WVPU[Z -
::9KYP]LV\[W\[ * WVPU[ZPUKLWLUKLU[JVTTVU 1
*\YYLU[V\[W\[ ,  #7V^LYZ\WWS`]VS[HNLPUZ[Y\J[PVUTHU\HS%
=VS[HNLV\[W\[ 7 [V=(*1HWHULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS @
9L[YHUZTPZZPVUV\[W\[J\YYLU[ 9 [V=(*,UNSPZOPUZ[Y\J[PVUTHU\HS =
9L[YHUZTPZZPVUV\[W\[]VS[HNL : [V=(**OPULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS >
 #9L]PZPVUJVKL%  =(*+*1HWHULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS (
#(SHYTV\[W\[% =(*+*,UNSPZOPUZ[Y\J[PVUTHU\HS )
5VUL  =(*+**OPULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS +
WVPU[   #6W[PVU%
WVPU[Z - 5VUL @
WVPU[Z 4 +PNP[HSPUW\[+0 +
WVPU[ZPUKLWLUKLU[JVTTVU 1 9:JVTT\UPJH[PVU+PNP[HSPUW\[+0 =
 #7V^LYZ\WWS`]VS[HNLPUZ[Y\J[PVUTHU\HS%   
[V=(*1HWHULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS @ 
[V=(*,UNSPZOPUZ[Y\J[PVUTHU\HS =
[V=(**OPULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS >
=(*+*1HWHULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS (
=(*+*,UNSPZOPUZ[Y\J[PVUTHU\HS ) Optional Items
=(*+**OPULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS + Name Model
 #6W[PVU% Current detector (CT) 1 A to 30 A ZOZ*CCTL-6-S-H
5VUL @ 20 A to 100A ZOZ*CCTL-12-S36-8
9:*VTT\UPJH[PVU 4
Terminal cover ZZPPXR1-A230
+PNP[HSPUW\[+0 :
Parameter loader interface cable ZZP*TQ501923C3
9:JVTT\UPJH[PVU+PNP[HSPUW\[+0 =
9:JVTT\UPJH[PVU9LTV[L:=PUW\[5V[L 2 Shunt resistor (250 Ω±0.1%) ZZPPXR1-A190
9:*VTT\UPJH[PVU*;PUW\[5V[L 1 Panel mounting adapter for replacement from
   PXR7 to PXF4 ZZP*TQ502732C1

5V[L!5V[H]HPSHISLMVY[OL[OJVKL¸*¹¸,¹¸7¹¸9¹¸:¹
5V[L!>OLU\ZPUNJ\YYLU[MVY[OLYLTV[L:=PUW\[HKKHVOTYLZPZ[VY[V[OLPUW\[[LYTPUHS
5V[L!>OLU\ZPUN[OL*;PUW\[MVYOLH[LYI\YUV\[HSHYTHKKVULHSHYTV\[W\[MVYP[PU[OL [OJVKL

Outline diagram of optional items


Panel mounting adapter for replacement from PXR7 to PXF4 (ZZP*TQ502732C1)

Panel mounting adapter >OLU[OLWHULS[OPJRULZZPZTT How to install PXF4 with the adapter
7HULS[VTT

7?-
4V\U[PUNIYHJRL[

7?-
WHULSJ\[V\[

4V\U[PUNZJYL^Z
WJZ

4V\U[PUNMYHTL
WYV]PKLK^P[O7?-
>H[LY[PNO[WHJRPUN
Current detector (CT)
‹:WLJPMPJH[PVU!([V( ‹:WLJPMPJH[PVU!([V(
‹;`WL!*;3:/ ‹;`WL!*;3:
21 30 ø2.36

15 2.8
9
7

ø5.8
25

40
10.5

2.5

ø12
10

30
‹+L[LJ[PVUPZH]HPSHISLVUS`MVYZPUNSLWOHZL
15

40
ø3.5
M3, depth 4 OLH[LY
7.5

30 ‹*HUUV[IL\ZLK^OLU[OLOLH[LYPZJVU[YVSSLK
40 \ZPUN[O`YPZ[VYWOHZLHUNSLJVU[YVS

10
#_ TTZPaL%# _ TTZPaL%
4V[VYPaLK]HS]LJVU[YVS[`WLIHZLTVKLS!7?-VY7?-  4V[VYPaLK]HS]LJVU[YVS[`WL
+PNP[ :WLJPMPJH[PVUZ *VKL +PNP[ :WLJPMPJH[PVUZ *VKL
 #-YVU[WHULSZPaL>_/%  #-YVU[WHULSZPaL>_/%
× TT 7?- × TT 7?-
× TT 7?- × TT 7?-
   (    (
 #*VU[YVSV\[W\[%  #*VU[YVSV\[W\[%
9LSH`JVU[HJ[:7:; ( 4V[VYPaLK]HS]LJVU[YVSV\[W\[^P[O7-)PUW\[ :
9LSH`JVU[HJ[:7+; ) 4V[VYPaLK]HS]LJVU[YVSV\[W\[^P[OV\[7-)PUW\[ =
::9KYP]LV\[W\[ *  #*VU[YVSV\[W\[%
*\YYLU[V\[W\[ , 5VUL @
=VS[HNLV\[W\[ 7  #9L]PZPVUJVKL% 
 #*VU[YVSV\[W\[% #(SHYTV\[W\[%
5VUL @ 5VUL 
9LSH`JVU[HJ[:7:; ( WVPU[ 
::9KYP]LV\[W\[ * WVPU[Z -
*\YYLU[V\[W\[ , WVPU[Z 4
=VS[HNLV\[W\[ 7 WVPU[ZPUKLWLUKLU[JVTTVU 1
9L[YHUZTPZZPVUV\[W\[J\YYLU[ 9  #7V^LYZ\WWS`]VS[HNLPUZ[Y\J[PVUTHU\HS%
9L[YHUZTPZZPVUV\[W\[]VS[HNL : [V=(*1HWHULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS @
 #9L]PZPVUJVKL%  [V=(*,UNSPZOPUZ[Y\J[PVUTHU\HS =
#(SHYTV\[W\[% [V=(**OPULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS >
5VUL  =(*+*1HWHULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS (
WVPU[  =(*+*,UNSPZOPUZ[Y\J[PVUTHU\HS )
WVPU[Z - =(*+**OPULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS +
WVPU[Z 4  #6W[PVU%
WVPU[ZPUKLWLUKLU[JVTTVU 1 5VUL @
 #7V^LYZ\WWS`]VS[HNLPUZ[Y\J[PVUTHU\HS% 9:JVTT\UPJH[PVU+PNP[HSPUW\[+0+0+0 <
[V=(*1HWHULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS @   
[V=(*,UNSPZOPUZ[Y\J[PVUTHU\HS = 
[V=(**OPULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS >
=(*+*1HWHULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS ( Optional Items
=(*+*,UNSPZOPUZ[Y\J[PVUTHU\HS )
=(*+**OPULZL ,UNSPZOPUZ[Y\J[PVUTHU\HS + Name Model
 #6W[PVU% Current detector (CT) 1 A to 30 A ZOZ*CCTL-6-S-H
5VUL @   20 to 100A ZOZ*CCTL-12-S36-8
9:*VTT\UPJH[PVU 4 Terminal cover (note) ZZPPXF1-B100
+PNP[HSPUW\[+0+0 ; Parameter loader interface cable ZZP*TQ501923C3
9LTV[L:=PUW\[+PNP[HSPUW\[+05V[L / Shunt resistor (250 Ω±0.1%) ZZPPXR1-A190
*;PUW\[+PNP[HSPUW\[+05V[L .
Note: For PXF9, two covers are necessary for one unit.
9:JVTT\UPJH[PVU+PNP[HSPUW\[+0 =
9:JVTT\UPJH[PVU+PNP[HSPUW\[+0+0+0(\_PSPHY`HSHYTV\[W\[(3(3 *
  

5V[L!>OLU\ZPUNJ\YYLU[MVY[OLYLTV[L:=PUW\[HKKHVOTYLZPZ[VY[V[OLPUW\[[LYTPUHS
5V[L!>OLU\ZPUN[OL*;PUW\[MVYOLH[LYI\YUV\[HSHYTHKKVULHSHYTV\[W\[MVYP[PU[OL [OJVKL
Scope of delivery
● Controller x1 ● Panel mounting adapter x 2
● Instruction manual x 1 ● Water-proof packing x 1

■ INSULATION BLOCK DIAGRAM

● PXF4 ● PXF5, PXF9

7V^LYZ\WWS` Internal circuit 7V^LYZ\WWS` 0U[LYUHSJPYJ\P[

7YVJLZZ]HS\LPUW\[ 7YVJLZZ]HS\LPUW\[
*VU[YVSV\[W\[YLSH`JVU[HJ[VY *VU[YVSV\[W\[YLSH`JVU[HJ[VY
9LTV[L:=PUW\[ 4V[VYPaLK]HS]L67,5V\[W\[ 9LTV[L:=PUW\[
4V[VYPaLK]HS]L67,5V\[W\[
*;PUW\[ *\YYLU[[YHUZMVYTLY*;PUW\[
*VU[YVSV\[W\[ =HS]LWVZP[PVUMLLKIHJR7-)PUW\[
*VU[YVSV\[W\[YLSH`JVU[HJ[VY ::9KYP]LJ\YYLU[]VS[HNL *VU[YVSV\[W\[YLSH`JVU[HJ[VY
4V[VYPaLK]HS]L*36:,V\[W\[ 4V[VYPaLK]HS]L*36:,V\[W\[ *VU[YVSV\[W\[
*VU[YVSV\[W\[
::9KYP]LJ\YYLU[]VS[HNL ::9KYP]LJ\YYLU[]VS[HNL

(SHYTV\[W\[ *VU[YVSV\[W\[::9KYP]LJ\YYLU[]VS[HNLVY
+PNP[HSPUW\[[V (SHYTV\[W\[HUKYLSH`JVU[HJ[
YLSH`JVU[HJ[ (SHYTV\[W\[[V YL[YHUZTPZZPVUV\[W\[

(SHYTV\[W\[ YLSH`JVU[HJ[ (SHYTV\[W\[


*VTT\UPJH[PVU9: +PNP[HSPUW\[[V
YLSH`JVU[HJ[ YLSH`JVU[HJ[ (SHYTV\[W\[[V
(SHYTV\[W\[ 9LSH`JVU[HJ[
*VTT\UPJH[PVU9:
!IHZPJPUZ\SH[PVU YLSH`JVU[HJ[
>OLU[OL [OJVKLPZ¸1¹(3HUK(3!PUKLWLUKLU[JVTTVU
!M\UJ[PVUHSPUZ\SH[PVU
>OLU[OL [OJVKLPZV[OLY[OHU¸1¹(3[V(3!ZOHYLKJVTTVU !IHZPJPUZ\SH[PVU
!UVPUZ\SH[PVU Ç>OLU[OL [OJVKLPZ¸1¹(3HUK(3!PUKLWLUKLU[JVTTVU
!M\UJ[PVUHSPUZ\SH[PVU
Ç>OLU[OL [OJVKLPZV[OLY[OHU¸1¹(3[V(3!ZOHYLKJVTTVU
!UVPUZ\SH[PVU

11
■ CONNECTION DIAGRAM

Standard type 48 x 48 mm <PXF4>

*VU[YVS 9LSH`V\[W\[ 9LSH`V\[W\[ 9LSH`V\[W\[ 9LSH`V\[W\[


::9 *\YYLU[ =VS[HNL MVYT(JVU[HJ[ ::9 *\YYLU[ =VS[HNL
V\[W\[ MVYT(JVU[HJ[ :7+; :7+;
*VU[YVS 9LSH`V\[W\[ 9LSH`V\[W\[ 9LSH`V\[W\[ 9LSH`V\[W\[ 9LSH`V\[W\[
V\[W\[ 5VUL 5VUL 5VUL 5VUL 5VUL :7:; :7:; :7:; :7:; :7:;
OUT1 + + + OUT1 + + +
13 13 NC 13 OUT1 13 OUT1 13 OUT1 13 13 NC 13 OUT1 13 OUT1 13 OUT1
OUT1 – OUT1 –
14 14 COM 14 – COM 14 COM 14 – COM 14 14 COM 14 – COM 14 COM 14 – COM
15 No. 15 No.

11 11 11 11 11
OUT2 OUT2 OUT2 OUT2 OUT2
12 12 12 12 12

*VU[YVS
V\[W\[ ::9 *\YYLU[ =VS[HNL ::9 *\YYLU[ =VS[HNL ::9 *\YYLU[ =VS[HNL
*VU[YVS *\YYLU[VYYL[YHUZTPZZPVU *\YYLU[VYYL[YHUZTPZZPVU *\YYLU[VYYL[YHUZTPZZPVU =VS[HNLVYYL[YHUZTPZZPVU =VS[HNLVYYL[YHUZTPZZPVU =VS[HNLVYYL[YHUZTPZZPVU
::9 ::9 ::9 V\[W\[J\YYLU[ V\[W\[]VS[HNL
V\[W\[ V\[W\[J\YYLU[ V\[W\[J\YYLU[ V\[W\[]VS[HNL V\[W\[]VS[HNL
+ + + + + + + + +
13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1
– – – – – – – – –
14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM
15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2
VYYL[YHUZTPZZPVU VYYL[YHUZTPZZPVU VYYL[YHUZTPZZPVU VYYL[YHUZTPZZPVU VYYL[YHUZTPZZPVU VYYL[YHUZTPZZPVU

7YVJLZZ]HS\LPUW\[
<UP]LYZHSPUW\[
(SHYTV\[W\[
WVPU[Z 4[LYTPUHSZ
A
+
PUKLWLUKLU[JVTTVU WVPU[Z VYWVPU[Z 16 16
B
+ +
1 7 13 17 17 17 17
AL1 1 AL1 1 AL1 1
2 8 14 18 – 18
B 18 – 18 –
AL1 COM 2 AL2 2 Non-C 2
3 9 15
AL2 3 AL3 3 AL2 3 ;OLYTVJV\WSL 9;+ *\YYLU[PUW\[ =VS[HNLPUW\[
4 10 16
AL2 COM 4 COM 4 COM 4
1RWH 5 11 17 6W[PVU
5V[L!7V^LYZ\WWSPLZMVY(3HUK(3T\Z[ILVM[OLZHTL[`WL 6 12 18 9:
LP[OLY(*VY+* +
7
7V^LYZ\WWS` 9:
8 –
=(*=+* =(*
+PNP[HSPUW\[ 9LTV[L:=PUW\[ *;PUW\[
5 5 +
9 +0 9 9
6 6 9:= CT1
10 10 – 10
+0*64
/a /a

Motorized valve control type

6W[PVU
=HS]LJVU[YVS
+PNP[HSPUW\[ 9:
*SVZL
11 +
12 7 7
*64 9:
+0 8
8

=HS]L
JVU[YVS +0
V\[W\[ 9
=HS]LJVU[YVS +0
10
+0*64
6WLU +PNP[HSPUW\[
13
14
*64
9 +0
10 +0*64

(SHYTV\[W\[
WVPU[Z
PUKLWLUKLU[JVTTVU5V[L VYWVPU[Z

(3 1 (3 1
(3*64 2 5VU* 2 4
(3
[LYTPUHSZ
3 (3 3
(34*64 4 *64 4 1 7 13
5V[L
2 8 14
5V[L!7V^LYZ\WWSPLZMVY(3HUK(3T\Z[ILVM[OL
 ZHTL[`WLLP[OLY(*VY+* 3 9 15
7YVJLZZ]HS\LPUW\[
4 10 16
7V^LYZ\WWS` <UP]LYZHSPUW\[
5 11 17

=(*=+* =(* 6 12 18
16 $
+
16
17 %
+ +
17 17 17
5 5
18 – 18 % 18 – 18 –
6 6
;OLYTVJV\WSL 9;+ *\YYLU[PUW\[ =VS[HNLPUW\[
/a /a

12
Standard type
48 x 96 mm <PXF5> 96 x 96 mm <PXF9>
9LSH`V\[W\[ 9LSH`V\[W\[
::9 *\YYLU[ =VS[HNL
:7:; :7+;
6<; + + +
*VU[YVS 1 1 5V 1 6<; 1 6<; 1 6<;
V\[W\[ 6<;
2 2 *64 2 - *64 2 - *64 2 - *64
3 5*

9LSH`V\[W\[ 9L[YHUZTPZZPVU 9L[YHUZTPZZPVU


::9 *\YYLU[ =VS[HNL
MVYT(JVU[HJ[ V\[W\[J\YYLU[ V\[W\[]VS[HNL

*VU[YVS + + + + +
V\[W\[ 4 4 OUT2 4 OUT2 4 OUT2 4 OUT2 4 OUT2
OUT2
5 5 – COM 5 – COM 5 – COM 5 – COM 5 – COM

4[LYTPUHSZ
1 13 25
6W[PVU
2 14 26
9: +PNP[HSPUW\[ *;PUW\[
3 15 27
4 16 28
(SHYTV\[W\[ 5 17 29
+ 27 +0 31
WVPU[Z 25
PUKLWLUKLU[JVTTVU WVPU[Z VYWVPU[Z 6 18 30 9: 28 +0*64 32 *;
26 –
7 19 31 29 +0 33
(3 6 (3 6 (3 6
8 20 32
(3*64 7 (3 7 5VU* 7
9 21 33
(3 8 (3 8 (3 8
10 22 34
(3*64 9 *64 9 *64 9
5V[L 11 23 35
5V[L!7V^LYZ\WWSPLZMVY(3HUK(3T\Z[ILVM[OLZHTL[`WL 12 24 36
LP[OLY(*VY+*

6W[PVU
7YVJLZZ]HS\LPUW\[
+PNP[HSV\[W\[ +PNP[HSPUW\[ 9LTV[L:=PUW\[
7V^LYZ\WWS` <UP]LYZHSPUW\[
=(*=+* =(* 17 +0 (
+
34 34
13 (3 +
)
+ +
18 +0*64 23
35 35 35 35
11 11 14 *64 9:=
19 +0 24 –
36 36
) 36 36
15 (3
– – –
12 12
20 +0
;OLYTVJV\WSL 9;+ *\YYLU[PUW\[ =VS[HNLPUW\[
/a /a

Motorized valve control type

4V[VYPaLK]HS]LJVU[YVS[`WL
=HS]LJVU[YVS
6WLU
1
2
*64
=HS]L
JVU[YVS
V\[W\[ =HS]LJVU[YVS

*SVZL
4
5
*64 4[LYTPUHSZ

1 13 25
6W[PVU
2 14 26
9: +PNP[HSPUW\[ 7-)PUW\[
3 15 27
4 16 28 30 0
5 17 29
+ 27 +0
25 31 7-)
(SHYTV\[W\[ 9: 28 +0*64
6 18 30 26 32
WVPU[Z WVPU[Z VYWVPU[Z

PUKLWLUKLU[JVTTVU 29 +0
7 19 31 33 0¶
(3 6 (3 6 (3 6 8 20 32

(3*64 7 (3 7 5VU* 7 9 21 33

(3 8 (3 8 (3 8 10 22 34

(3*64 9 *64 9 *64 9 11 23 35


1RWH
12 24 36
5V[L!7V^LYZ\WWSPLZMVY(3HUK(3T\Z[ILVM[OLZHTL[`WL
    LP[OLY(*VY+*

7YVJLZZ]HS\LPUW\[
7V^LYZ\WWS` 6W[PVU <UP]LYZHSPUW\[
=(*=+* =(* +PNP[HSPUW\[ A
+
34 34
B
+ +
35 35 35 35
11 11 17 +0
36 – 36
B 36 – 36 –
12 12 18 +0*64
;OLYTVJV\WSL 9;+ *\YYLU[PUW\[ =VS[HNLPUW\[
/a /a

13
■ OUTLINE DIAGRAM
PXF4
Outer dimensions Panel cutout

PM^P[O[LYTPUHSJV]LY
  Panel cutout For close mounting in horizontal direction
 (“n” units)
4V\U[PUNMP_[\YL
 45 +0.5 (Waterproof property is lost in this case)
0 For mounting
“n” units
+0.5
(48×n-3)0

+0.5
0
[LYTPUHSJV]LY

73 MIN.
45

+0.5
0
45




This mounting does not meet NEMA-4X/IP66
63 MIN.
(front waterproof specification). (Because the packing
cannot be used in horizontal close mounting.)

>H[LYWYVVM [WHULS[OPJRULZZ
WHJRPUN ˜[˜ ;LYTPUHSJV]LYVW[PVU
7HULS

* Dimensions include coating thickness.

PXF5
Outer dimensions Panel cutout

[LYTPUHSJV]LYPUJS\KLK
 
For close mounting in horizontal direction
 (“n” units)
 4V\U[PUNMP_[\YL
(Waterproof property is lost in this case)
45 +0.6
0 For mounting
“n” units
+0.8
(48×n-3)
92 +0.8

0
[LYTPUHSJV]LY

+0.8


0
116 MIN.


92


This mounting does not meet NEMA-4X/IP66 (front


waterproof specification). (Because the packing
cannot be used in horizontal close mounting.)
>H[LYWYVVM
WHJRPUN
50 MIN.
[WHULS[OPJRULZZ
˜[˜ ;LYTPUHSJV]LY
7HULS VW[PVU
* Dimensions include coating thickness.

PXF9
Outer dimensions Panel cutout

[LYTPUHSJV]LYPUJS\KLK
 
 4V\U[PUNMP_[\YL 92 +0.8
0

92 +0.8
0
[LYTPUHSJV]LY

116 MIN.





100 MIN.

>H[LYWYVVM [WHULS[OPJRULZZ
˜[˜ ;LYTPUHSJV]LY
WHJRPUN
VW[PVU
7HULS * Dimensions include coating thickness.

■ Rear view <PXF5> <PXF9>


<PXF4>   
  


  





;LYTPUHS ;LYTPUHS
;LYTPUHS

14
■ Related products

Module type temperature controllers (PUM) 24 x 48 mm sized Temperature Controller (PXR3)

(IILFLHQWVROXWLRQWKDWPHHWV
\RXUH[SHFWDWLRQV Various functions in compact body
■ Up to 64 control loops ■ Detachable terminal ■ High-speed data Front dimension 24×48 mm
■ Fr
■ Heater break alarm ■ Bilingual loader communication Multiple input:
■ Mu
CT (8 points) per module ■ Simple loader (RS485/230.4 kbps) RTD,
RT thermocouple,
operation ■ High-speed data vo
voltage/current
sampling (200 m/s) ■ He
Heating/cooling control
Optional functions:
■ Op
Wide selection of modules
Alarm output, 8-step ramp
Al
◦ Control Module do
doak, re-transmission output,
◦ Event input/output RS
RS-485 communication,
◦ Analog input/output digital input
di
◦ Analog input DIN rail mounting
◦ Analog output
◦ CC-LINK communication Optional DIN rail mounting
◦ Mitsubishi PLC adapter allows you to mount
communication PXR3 to DIN rail or wall.
◦ PROFIBUS
◦ Ethernet
(WWSPJH[PVUL_HTWSLZ 5HWUDQVPLVVLRQRXWSXWLQWRP$'&
Programmable
Programmable operating display PV transfer output 3;5
operating display 7HPSHUDWXUHLQSXW
Mitsubishi PLC
Serial connection
Communication '&aP$ )U\HU
Module Optimal control
Programless Control Module simulator &XUUHQWFRQWUROVLJQDO
Oven
communication 5HFRUGHU3+)
Optimal
control 2LO
$&SRZHUUHJXODWRU
Temperature control  $35  +HDWHU
Control module, Multistage
Air fan control Event I/O Module
Reflow soldering device baking furnace

Socket type Temperature Controller PXR4 Digital Temperature Controller (PXE4)

Easy maintenance Slim! Easy operation! Compact

Just fitting into a socket

(Size:48×48mm)

Easy wiring and Input signal 1point


Detachable structure of
installation! Capable of changing over temperature
socket and controller enables
type (resistance-bulb, 9 types of
you to:
thermocouples) with front key.
• Perform wiring on new
socket previously
Control output 1point
• Replace controllers without
wiring work Relay contact output, SSR/SSC drive
output, ON/OFF control and Fuzzy
control (with auto-tuning)

• 48 x 48 mm sized front panel with large display • Designed for simplicity and ease-of-use
• DIN rail mounting available • Thin panel: 1.6 mm
• PID auto tuning, self tuning, fuzzy control provided as standard • Short depth: 62 mm
• Three type of control output: relay contact, SSR/SSC, current • Alarm output up to 2 points
• Two alarm outputs (optional), 8-step ramp soak (optinal) • Standby and soft-start functions
• Front water proof structure (IP66)

15
SPECIAL ATTENTION NEEDED for all Digital Temperature Controllers
(Please read carefully the following instructions.)

7!2.).' Over-temperature Protection


Any control system design should take into account that any part of the system has the potential to fail.

For temperature control systems, continued heating should be considered the most dangerous condition, and the machine should
be designed to automatically stop heating if unregulated due to the failure of the control unit or for any other reason.

The following are the most likely causes of unwanted continued heating:

1) Controller failure with heating output constantly on


2) Disengagement of the temperature sensor from the system
3) A short circuit in the thermocouple wiring
4) A valve or switch contact point outside the system is locked to keep the heat switched on.

In any application where physical injury or destruction of equipment might occur, we recommend the installation of independent
safety equipment, with a separate temperature sensor, to disable the heating circuit in case of overheating.

The controller alarm signal is not designed to function as a protective measure in case of controller failure.

  &DXWLRQRQ6DIHW\
%HIRUHXVLQJSURGXFWVLQWKLVFDWDORJEHVXUHWRUHDGWKHLULQVWUXFWLRQPDQXDOVLQDGYDQFH

*UREDO6DOHV6HFWLRQ
,QVWUXPHQWDWLRQ 6HQVRUV3ODQQLQJ'HSW
)XMLPDFKL+LQRFLW\7RN\R-DSDQ
KWWSZZZIXMLHOHFWULFFRP
3KRQH)D[
KWWSZZZIXMLHOHFWULFFRPSURGXFWVLQVWUXPHQWV

,QIRUPDWLRQLQWKLVFDWDORJLVVXEMHFWWRFKDQJHZLWKRXWQRWLFH 3ULQWHGLQ-DSDQ)2/6

You might also like