New-Generation PXF Series

Digital Temperature Controller

Exceeding Your Expectations...


High Speed and High Accuracy
Multi-Drop Master Function
Universal Input

21B1-E-0062e
Superior Versatility and Flexibility
for a Wide Range of Applications
Control output indicator Alarm output (DO) indicator
→P7

Manual operation
Ramp/soak status indicator

→P5

Process value (PV)


PID auto tuning indicator

Set value (SV)

Parameter number

MV Bar graph
User key

Select key Up key


PXF9

Digit selector Down key

Multi-Functional to Suit Your Needs


Fast Control
In addition to 9 types of temperature control functions Accuracy 100ms
including on-off control, heating/cooling control, and
2-degrees-of-freedom PID, useful functions such as
±0.2%
(depends on input type
multi-drop control using RS-485 network and simple and range)
Operating
watt-hour monitoring are available. All these features Days Alarm
make PXF practical for any applications.
Sampling Rate
50 ms
*For details of each functions, see pages 4–7.

Simple
Watt-Hour
Metering
Function

2
RS-485 Communication (option) Universal Input

SV can be transmitted to multi-PXFs through


communication. Synchronous temperature-rise control is
available in combination with 2-degrees-of-freedom PID.
Thermocouple
Temperature RTD
Synchronized heating function
Example: injection
1 input
SV SV SV molding machine
RS485
Pressure 1–5 V DC,
etc.

Flow rate 4–20 mA DC,


Master Slave Slave Slave Zone 1 2 3 4 etc.
Zone 1 Zone 2 Zone 3 Zone 4
Multi-zone control (synchronized heating)
Easy switchover by parameter setting

Tallest PV Characters in the Industry Compact Design

Bright and clear white PV display for optimal viewing With only 58-mm depth, compact enough to be installed
on small equipment

15.3 mm

58 mm

PXF4

Size Selection Parameter Setting Available on PC

3 different sizes, with a depth of 58 mm Parameter loader software is download free from our
website. Optional USB cable enables PXF to be
connected to and powered from PC.

USB
PXF9 PXF5 PXF4
96 x 96 mm 48 x 96 mm 48 x 48 mm USB cable

3
Advanced Control Functions
Parameter setting is available using the front keys or a PC with Fuji Electric’s loader software.

Standard Functions

1
On/off Control Control characteristic of ON/OFF action
Hysteresis

Simple and Basic Control Setpoint

When process value (PV) is below the set value (SV), PXF turns on the output
to energize the heater, and vice versa. In this way, PXF keeps the temperature
constant by turning the output on and off based on the SV as a threshold. ON
Time

Heater
OFF

2
PID Control with Auto Tuning
Molding Machine
Typical Control Based on PID Theory
Start/stop of auto tuning can be
* Overshoot may occur due to commanded externally.
external disturbance. Setpoint

Overshoot Response to PV Tuning


disturbances
Digital input SV
Auto tuning
command
ON ON
ON: Start
OFF: stop

PID Auto Tuning


The controller calculates optimal PID parameters. PXF has 2 types of auto-tuning
Temp.
functions; the standard type (auto-tuning with SV used as reference) and the low SV alarm
type (auto-tuning with the value 10% below SV used as reference).
Temperature Temperature input
input
(a) Standard type (b) Low-PV type Molding machine
AT end AT end SSR SSR
AT start (PID setup) (PID setup) Raw materials
AT start
AT computation AT computation

SV SV
SV -10%
PV (process value)
(Control output)

(Control output)

PV (process value)
ON ON Heater
100% ON ON 100% ON ON
OFF OFF OFF OFF OFF OFF
0% PID control 0% PID control
ON-OFF action ON-OFF action

3 4
Fuzzy Control with Auto Tuning 2-Degree-of-Freedom PID with Auto Tuning
Suppresses Overshoot by Fuzzy Calculation Combined Method for Stable Control
By monitoring PV, PXF suppresses overshoot without Suppresses overshoot and undershoot occurs at
lengthening startup time. At the same time, it can startup or at SV change, or by external disturbances.
quickly deal with external disturbances.

• Conventional PID • 2-degrees-of-freedom PID


(before adjusting α and β)
Process value Process value

SV SV
Fuzzy control Conventional control

PV PV

Setpoint Setpoint Time Time

• 2-degrees-of-freedom PID
(with optimal α and β)
Overshoot Response to Overshoot Response to Process value
disturbances disturbances
SV

PV

Time

4
5 6
Open-Loop Supported PID2 Control Self Tuning Control
Suppresses Overshoot Auto-Tuned PID for Changing Temperature
Reduces overshoot Process
value
Overshoot is controlled At power up, SV change, or
in the processes SV during external disturbance,
where the controlled PV tuning is made automatically
equipment is power ON
so that the PID parameters External
Set value disturbance
cycled. Power supply to
control equipment
t are re-optimized. change
OFF Close Close *For some objects of control, PID values
Control loop Power on
Open cannot be optimized.

7
Simple Program Control (Ramp Soak Function)
Controlling Temperature Gradient of Furnace
Up to 64 Steps
by heating patterns
PXF automatically changes SV to the preset values at preset times.
Digital input
You can set up to 64 steps and 15 types of operation patterns. For Ramp soak action Temperature input Thermocouple
example, when you bake four kinds of bread, you can divide 64 command
ON: Start Furnace
steps into four patterns to set suitable temperature for each bread. OFF: Reset
SSR drive
SV Example of 16 steps x 4 patterns output
SV-8 Max. SSR

64
step 2 step 3 SV-7 SV-9
step 1 SV-3 SV-13
SV-4 SV-12
steps!! Ramp Soak Function
SV-2 SV-10 SV-14
SV-5 Temperature rise/fall pattern is controlled by
SV-1 SV-11 SV-15 setting a heat pattern having a gradient. You can
SV-16
externally start or reset the pattern.
SV-6
PV
TM1s TM5s TM16r Time
TM1r TM5r SV-8
TM16s
Setpoint SV-7
step 1 to 4: pattern 1 step 5 to 8: pattern 2 step 9 to 12: pattern 3 step 13 to 16: pattern 4 SV-3
SV-4
SV-2
■ Basic functions ■ Operation ■ ‌Number of steps and SV-5
1. [h · min] or [min · s] You can start/stop/suspend patterns SV-1 SV-6
2. Guarantee soak the operation using a user Steps Patterns
3. Repeat action key, parameter setting, digital 64 1
4. PV start input, or communication. 32 2
5. Delay start Time
16 4
6. Power restoring function
8 8

Optional Functions

1
Heating and Cooling Control
Energy Savings in Livestock Barns
with Dual Output
Both heating and cooling are controlled with one
temperature controller using its two control outputs.
Output
Heating side Cooling side Heating side Output Cooling side Power consumption can be curbed by controlling a cooling fan
Coefficient 0.5 motor with inverter.
Coefficient 1.0 Temperature input signal
Coefficient 2.0
Cooling fan motor
Current output
Deviation Set value (SV) Deviation Deviation Deviation (+) Room M
(-) (+) (-) Overlap band temperature
Heating side Cooling side Dead band
Proportional Proportional
band band Inverter
Proportional band (P) Set value (SV)
Current output
in shed
Heater power supply
To heater
Cattle shed AC power regulator (APR)
* ‌For the cooling side proportional band, set a coefficient with respect to the heating side
proportional band. (Works as on-off control if coefficient is zero.)

2
Motorized Valve Control
Heating/Cooling Control of Air Conditioner
Valve Opening/Closing is Available
Command switch
Summer Winter
· ‌Position feedback control based on motorized valve Close in summer, open in winter Switching

position signal Open in summer, close in winter Summer: Normal action


Winter: Reverse action
· Servo control without valve position signal Valve control command output

Hot water Valve position


Solenoid valve signal (resistance)
M Temperature sensor
Cold water Air conditioner
Solenoid valve Motorized valve

5
Variety of Functions
Expanding the Uses of Temperature Controllers and Improve the User Experience

Standard Functions

1 SV and PID selection


Easy Switching Among 8 Presets
This enables optimum PID setting for changing process,
2 Soft Start
Saves Energy at Startup
Prevents the output being maximum when turning on the
materials, or PV. You can perform SV selection only, PID equipment (including the temperature controller). This is
selection only, or PID selection according to PV. useful for suppressing the load at equipment startup.
SV SV SV Control output (MV) MV without soft start
SV
SV switching

PID switching
Palette 1 Palette 2 Soft start
Palette 7
output set
value
MV with
soft start (limited)
SV switching
SSR
PID switching SSR drive 0% t
output
Soft start
PLC set time
Power ON or
Digital input ON

3 Simple Watt-Hour Metering Function


Tells You the Energy Consumption
If you use an optional current transformer (See page 10).
4 Operating Days Alarm
For Well-Timed Maintenance
Indicator or alarm output alert you when the number of days
Approximate monitoring is also available without CT. operated has reached the limit you set.

With CT Estimated voltage Without CT Estimated voltage


PXF PXF
Heater load Heater load
Parameter setting Parameter setting
220 Load voltage 220 Load voltage
(V) (V)
Energy Energy
× consumption ON time × consumption
AC kWh AC kWh
Load Parameter
Control output current setting
Control output
CT 0.2
Measures CT input Load Alarm
actual current
current
Estimated current

Voltage: estimated value set by user (220 V) Voltage: estimated value set by user (220 V)
Current: value measured by CT Current: estimated value set by user (0.2 A)

Optional Functions

1 2
Re-transmission Output
Temperature Signals to External Heater Burnout Alarm
Devices Quickly Informs You a Failure
Cost savings achieved by eliminating the need for an extra • A current transformer (CT) is required.
temperature sensor • The alarm action point must be configured beforehand.
• Output signal : 0–20 mA DC, 4–20 mA DC, 0–5 V DC, 1–5 V
DC, 0–10 V DC, or 2–10 V DC [Example of PXF5/PXF9]
*Available only for single-
Power supply 100–240 V DC, 50/60 Hz
• Process value (PV), set value (SV), control output (MV), or phase heater
PV-SV (DV) 11 Power supply *Not available when using
thyristor phase angle control
12 Control output 1
1 6
PV transfer
output Temperature input
2
+ -
7
31 33 35 36
Heater burnout
MG alarm output
Voltage/ Fryer SW
current Electromagnetic switch
Current
Current transformer Wired to PXF
control (CT) (with no polarity)
signal Thermocouple
Recorder PHR Oil
Heater Wired to heater
AC power regulator (through hole in CT)
(APR) Heater Electric furnace

6
3 4
Alarm Output Digital Input
Up to 5 Alarms (PXF4: up to 3) SV Can be Switched Externally
Alarm type Action diagram SV change, AT start, timer startup, program selection, start/
stop/reset, PID changeover, etc.
Changeover of 4 set values
Absolute value alarm

Upper limit absolute value ALn


PV
(front SV, SV1, SV2, SV3) can
be commanded externally.
Lower limit absolute value ALn
PV
Digital input SV
Upper limit absolute value PV
change command
(with hold) ALn
SSR drive SSR drive
output output
Lower limit absolute value Oven
PV SSR SSR
(with hold) ALn
ALn
Upper limit deviation PV Temperature
SV input
ALn
Lower limit deviation PV
SV Temperature input
Deviation alarm

Upper and lower limits ALn ALn


PV
deviation SV
Upper limit deviation (with ALn
PV

5
hold) SV
Lower limit deviation (with ALn
PV
Remote SV Input
hold) SV
Upper and lower limits ALn ALn SV Can be Configured Externally
PV
deviation (with hold) SV
ALn ALn
• Input signal: 0–5 V DC, 1–5 V DC, 0–10 V DC,
Range upper and lower limits deviation 0-20 mA DC, or 4–20 mA DC
(ALM1/2 independent operation) PV
SV • Input impedance: About 1 MΩ
Range upper and lower PV
limits absolute value AL2 AL1
Range alarm

PLC
AL2 AL1
Range upper and lower Set temperature (SV)
limits deviation SV
PV 1 to 5 V DC
AL2
Range upper limit absolute
value and lower limit deviation SV AL1
PV

AL1
Range upper limit deviation and
lower limit absolute value AL2 SV
PV Control Temper-
output ature input

Cell A Cell B Cell C Cell D Cell E

The temperature of each cell is set by the PLC.

6
• Multidrop master function
RS-485 Communication Synchronous temperature-rise control is available in
combination with 2-degrees-of-freedom PID.
Synchronized heating function
• User address mapping function Example: injection molding
Users can create a list of necessary parameters (max. 32 RS485
SV SV SV machine
words) for quick data acquisition on that data set.
Communication speed: max. 115.2 kbps

Master Slave Slave Slave Zone 1 2 3 4


Zone 1 Zone 2 Zone 3 Zone 4
Address Parameter Multi-zone control (synchronized heating)
30001 PV Max.32 words
30002 SV(Read) Address Parameter • Parameter copy function
30003 DV 30001 PV
Parameter values can be copied to multiple PXFs
30004 MV1 30002 SV(Read)
simultaneously.
40003 SV(Write)
.
.
.
. • Communication with PC, programmable operation display,
. . 30004 MV1
or PLC
40006 P
40003 SV(Write)
40007 I PLC Programmable operating display
40004 STBY
40008 D
40005 AT
40006 P . .
. .
. .
40007 I
40008 D – –
RS-232C
– – Programless
. . Signal converter communication
. .
. . – –
RS-485 (Modbus)
Up to 32
controllers

PXF4 PXF5 PXF5 PXF9

7
Product Lineup
Model PXF4 PXF5 PXF9

Appearance

Front panel size (W x H) 48 × 48 mm 48 × 96 mm 96 × 96 mm


Depth 58 mm
Display digits 4-digit (PV and SV)
Character height (PV) 15.3 mm 18.1 mm 26 mm
RTD input: ±0.2% of indication value ±1 digit or ±0.8°C±1 digit, whichever is larger
Indication accuracy Thermocouple input: ±0.3%±1 digit of indicated value or ±1°C±1 digit, whichever is larger
Voltage input and current input: ±0.3%FS ±1 digit
Sampling rate 50 ms
Process value input Universal input (RTD, thermocouple, voltage/current)
Remote SV input Voltage/current
Current transformer (CT) input Dedicated CT (1 to 100 A)
Input signal
Option Motorized valve position input - 100Ω to 2.5kΩ (3-wire)
1 (Motorized valve control ver-
Digital input (DI) Up to 3
sion: up to 3)
Relay contact ●

Control out- SSR drive output ●


put Current output (linear) ●
Voltage output (linear) ●

Output Motorized valve control output ●


signal Analog re-transmission output (voltage) ●
Analog re-transmission output (current) ●
Option
Heater burnout alarm output ●
Operating days alarm ●
Alarm/event contact output (DO) Up to 3 Up to 5
ON/OFF control ●
PID control* ●
Fuzzy control* ●
2-degrees-of-freedom PID control* ●
Control method
(*with auto tuning) Open-loop supported PID2 con-

trol
Self tuning ●
Ramp soak function (simple pro-
Up to 64 steps
gram control)
Heating/cooling control* ●
Option
Motorized valve control ●
Number of PV/PID patterns Up to 8
SV/PID switchover ●
Soft start ●
Functions Simple watt-hour metering ●
Operating days ●
Manual operation ●
User key ●

Communi- Loader interface ●


cation Option RS-485 (Modbus) ●

Power sup- 100–240 V AC, 50/60 Hz ●


ply voltage Option 24 V DC/AC ●
Power consumption 10 VA MAX. 13 VA MAX. 13 VA MAX.
Screw terminals M3
*Some functions are unavailable depending on the model. For more detail, please refer to the specifications on Page 14.

8
Outline Diagram
PXF4
Outer dimensions Panel cutout

73.2 (if with terminal cover)


7.7 58
1
Mounting fixture For close mounting in horizontal direction
48 Panel cutout ("n" units)
(Waterproof property is lost in this case)
+0.5
45 0 For mounting "n" units +0.5

48 (terminal cover)
(48 × n-3) 0

+0.5
45 0

73 MIN.

+0.5
44.8
48

57

0
45
In horizontal close mounting where the
63 MIN. packing cannot be used, PXF front panel
does not meet NEMA 4X nor IP66.

Water-proof t (panel thickness) 1 ≤ t ≤ 8


packing Terminal cover
(option)
Panel * Dimensions include coating thickness.

PXF5
Outer dimensions Panel cutout

72.2 (terminal cover included)


8.7 57
For close mounting in horizontal direction
2 Mounting ("n" units)
48 fixture (Waterproof property is lost in this case)
+0.6
45 0 For mounting "n" units
93.7 (terminal cover)

+0.8
+0.8 (48 × n-3) 0
92 0

+0.8
116 MIN.
110.4

0
91.4

92
96

In horizontal close mounting where the


packing cannot be used, PXF front panel
does not meet NEMA 4X nor IP66.
Water-proof
packing 50 MIN.

t (panel thickness) 1 ≤ t ≤ 8
Terminal cover
Panel (option)
* Dimensions include coating thickness.

PXF9
Outer dimensions Panel cutout

72.2 (terminal cover included)


8.7 57
2 Mounting
fixture 92 +0.8
0
96
92 +0.8
0
93.7 (terminal cover)

116 MIN.
110.4
91.4
96

100 MIN.

Water-proof t (panel thickness) 1 ≤ t ≤ 8 Terminal cover


packing
(option)
Panel
* Dimensions include coating thickness.

Rear view
PXF4 PXF5 PXF9

1-12 13-24 25-36 1-12 13-24 25-36

1-6 7-12 13-18


6.2
6.2
6.2

Terminal M3

Terminal M3 Terminal M3

9
4 5 6 7 8 9 10 11 12 13

Ordering Code PX F A 2 - 0 0
PXF4 Standard Type PXF4 Motorized Valve Control Type
Digit Specifications Code Digit Specifications Code
Front panel size W x H Front panel size W x H
1-4 1-4
48 × 48mm PXF4 48 × 48mm PXF4
5 - A 5 - A
Control output 1 Control output 1
6
Relay contact (SPST) *1 A Motorized valve control output (without PFB input) T
Relay contact (SPDT) *1 B Control output 2
6 7
SSR drive output C None Y
Current output E 8 Revision code 2
Voltage output P Alarm output
Control output 2 None 0
None Y 9 1 point 1
Relay contact (SPST) A 2 points F
SSR drive output C 2 points (independent common) J
7 Power supply voltage/instruction manual
Current output E
Voltage output P 100 to 240 V AC, Japanese & English Y
Re-transmission output (current) R 100 to 240 V AC, English V
Re-transmission output (voltage) S 10 100 to 240 V AC, Chinese & English W
8 Revision code 2 24 V AC/DC, Japanese & English A
Alarm output 24 V AC/DC, English B
None 0 24 V AC/DC, Chinese & English D
1 point 1 Option
9 None 1
2 points F 11
3 points M Digital input (DI 1, 2, 3) D
2 points (independent common) J RS-485 communication + Digital input (DI1) V
Power supply voltage/instruction manual 12
- 00
100 to 240 V AC, Japanese & English Y 13
100 to 240 V AC, English V
10 100 to 240 V AC, Chinese & English W
24 V AC/DC, Japanese & English A
24 V AC/DC, English B
24 V AC/DC, Chinese & English D
Option
None 1 Optional items
RS-485 Communication M Name Model
11 Digital input (DI1) S 1 A to 30A ZOZCCTL-6-S-H
Current transformer
RS-485 communication + Digital input (DI1) V 20 to 100A ZOZCCTL-12-S36-8
RS-485 communication + Remote SV input *2 K Terminal cover ZZPPXR1-A230
RS-485 Communication + CT input *3 J Parameter loader interface cable ZZPTQ501923C3
12 Shunt resistor (250 Ω±0.1%) ZZPPXR1-A190
- 00
13 Panel mounting adapter for replacement from PXR7 to PXF4 ZZPTQ502732C1
*1: ‌Not available for the 7th code “C”, “E”, “P”, “R”, “S”. However, if you want to order the 6th
code “A” (SPST relay contact for the control output 1) and the 7th code “R” or “S” (current/
voltage re-transmission output for the control output 2), specify the model as follows:
R
PXF4AA 2- 02
S

*2: When using current for the remote SV input, add a 250-ohm resistor to the input terminal.
*3: ‌When using the CT input for heater burnout alarm, add one alarm output for it in the 9th
code.

PXF5 & PXF9 Standard Type PXF5 & PXF9 Motorized Valve Control Type
Digit Specification Code Digit Specifications Code
Front panel size W x H Front panel size W x H
1-4 48 × 96 mm PXF5 1-4 48 × 96 mm PXF5
96 × 96 mm PXF9 96 × 96 mm PXF9
5 - A 5 - A
Control output 1 Control output 1
Relay contact (SPST) A 6 Motorized valve control output (without PFB input) S
Relay contact (SPDT) B Motorized valve control output (with PFB input) V
6
SSR drive output C Control output 2
7
Current output E None Y
Voltage output P 8 Revision code 2
Control output 2 Alarm output
None Y None 0
Relay contact (SPST) A 1 point 1
9
SSR drive output C 2 points F
7
Current output E 3 points M
Voltage output P 2 points (independent common) J
Re-transmission output (current) R Power supply voltage/instruction manual
Re-transmission output (voltage) S 100 to 240 V AC, Japanese & English Y
8 Revision code 2 100 to 240 V AC, English V
Alarm output 10 100 to 240 V AC, Chinese & English W
None 0 24 V AC/DC, Japanese & English A
1 point 1 24 V AC/DC, English B
9
2 points F 24 V AC/DC, Chinese & English D
3 points M Option
2 points (independent common) J 11 None 1
Power supply voltage/instruction manual RS-485 communication + Digital input (DI1, DI2, DI3) U
100 to 240 V AC, Japanese & English Y 12
- 00
100 to 240 V AC, English V 13
10 100 to 240 V AC, Chinese & English W
24 V AC/DC, Japanese & English A
24 V AC/DC, English B
24 V AC/DC, Chinese & English D Optional items
Option
Name Model
None 1
1 A to 30A ZOZCCTL-6-S-H
RS-485 Communication M Current transformer
20 to 100A ZOZCCTL-12-S36-8
Digital input (DI 1 and DI2) T
11 Terminal cover *1 ZZPPXF1-B100
Remote SV input + Digital input (DI3) *1 H
Parameter loader interface cable ZZPTQ501923C3
CT input + Digital input (DI1) *2 G
Shunt resistor (250 Ω±0.1%) ZZPPXR1-A190
RS-485 communication + Digital input (DI1) V
RS-485 + Digital input (DI3, DI4, DI5) + Auxiliary alarm output (AL4, AL5) C *1: For PXF9, two covers are necessary for one unit.
12
- 00
13 Scope of delivery
*1: When using current for the remote SV input, add a 250-ohm resistor to the input terminal. ∙ Controller × 1 ∙ Instruction manual × 1
*2: ‌When using the CT input for heater burnout alarm, add one alarm output for it in the 9th ∙ Panel mounting adapter × 1 set ∙ Water-proof packing × 1
code.

10
Outline Diagram of Optional Items
Panel mounting adapter for replacement from PXR7 to PXF4 (ZZPTQ502732C1)
Panel mounting adapter How to install PXF4 with the adapter

When the panel thickness


is 8 mm
Panel (1 to 8 mm)
30 72
72 4 18

PXF4
Mounting
bracket

72

48
PXF4
72

74
mounting hole
Mounting
screws (4 pcs)

Mounting frame
0.7 (provided with PXF4)
Watertight packing 4 61

Current transformer (CT)


For 1–30A (CTL-6-S-H) For 20–100A (CTL-12-S36-8)

30
ø2.36
21
15 2.8
9
7

ø5.8
40
25
10.5

2.5

ø12
10

15 • Detection is available only for single-phase


30 heater
M3, depth 4
7.5

40 30 • Cannot be used when the heater is


ø3.5
controlled using thyristor phase angle control.
40

Insulation Block Diagram


PXF4 PXF5 and PXF9

Power supply Internal circuit Power supply Internal circuit

Control output 1 (relay contact) Process value input Control output 1 (relay contact) Process value input
or Remote SV input or Remote SV input
Motorized valve OPEN output Motorized valve OPEN output
CT input Current transformer (CT) input
Control output 1
Control output 2 (relay contact) (SSR drive, current, voltage) Control output 2 (relay contact) Valve position feedback (PFB) input
or or
Motorized valve CLOSE output Control output 2 Motorized valve CLOSE output Control output 1
(SSR drive, current, voltage) (SSR drive, current, voltage)
Alarm output 1 Digital input 1 to 3 Alarm output 4 and 5 (relay contact) Control output 2 (SSR drive, current,
(Relay contact) Alarm output 1 to 3 voltage) or re-transmission output
Alarm output 2 (Relay contact)
Communication (RS-485) Alarm output 1 Digital input 1 to 3
(Relay contact) (Relay contact) Alarm output 1 to 3
Basic insulation Alarm output 2 (Relay contact)
When the 9th code is "J" When the 9th code Communication (RS-485)
(Relay contact)
(AL1 and AL2: is other than "J" Functional insulation
(AL1, AL2, and AL3: No insulation Basic insulation
independent common) When the 9th code is "J" When the 9th code
shared common)
(AL1 and AL2: is other than "J" Functional insulation
independent common) (AL1, AL2, and AL3: No insulation
shared common)

11
Connection Diagram
Standard type (base model: PXF4)
Control Relay output Relay output SSR Relay output Relay output SSR
output 1 Current Voltage Current Voltage
(SPST) (SPDT) (SPST) (SPDT)
Control Relay output Relay output Relay output Relay output Relay output
output 2 None None None None None (SPST) (SPST) (SPST) (SPST) (SPST)
OUT1 + + + OUT1 + + +
13 13 NC 13 OUT1 13 OUT1 13 OUT1 13 13 NC 13 OUT1 13 OUT1 13 OUT1
OUT1 - OUT1 -
14 14 COM 14 - COM 14 COM 14 - COM 14 14 COM 14 - COM 14 COM 14 - COM
15 NO 15 NO

11 11 11 11 11
OUT2 OUT2 OUT2 OUT2 OUT2
12 12 12 12 12

Control SSR Voltage SSR Current


output 1 Current SSR Current Voltage Voltage
Control Current or Current or Current or Voltage or Voltage or Voltage or
output 2 SSR SSR SSR re-transmission re-transmission re-transmission re-transmission re-transmission re-transmission
output (current) output (current) output (current) output (voltage) output (voltage) output (voltage)
+ + + + + + + + +
13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1 13 OUT1
- - - - - - - - -
14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM 14
+ COM
15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2 15 OUT2
or re-transmission or re-transmission or re-transmission or re-transmission or re-transmission or re-transmission

Process value input


Alarm output Universal input
2 points
3 points 1 or 2 points
M3 terminals A
+
(independent common) 16 16
B
+ +
1 7 13 17 17 17 17
AL1 1 AL1 1 AL1 1
2 8 14
B
AL1 COM 2 AL2 2 Non-C 2 18 - 18 18 - 18 -

AL2 3 AL3 3 AL2 3 3 9 15 Thermocouple RTD Current Voltage


4 10 16
input input
AL2 COM 4 COM 4 COM 4
Note 1) 5 11 17 Option
Note 1: Power supplies for AL1 and AL2 must be of the same type, 6 12 18 RS485
either AC or DC. +
7
Power supply RS485
8 -
24 V AC/24 V DC 100-240 V AC
Digital input Remote SV input CT input
5 5 +
9 DI1 9 9
6 6 RSV1 CT1
10 DI-COM 10 - 10
50/60Hz 50/60Hz

Motorized valve control type (base model: PXF4)

Option
Valve control
Digital input RS485
Close
11 +
12 7 7
COM DI3 RS485
8 8 -
Valve DI2
control 9
output 1 Valve control DI1
10
DI-COM
Open Digital input
13
14
COM
9 DI1
10 DI-COM

Alarm output
2 points
(independent common) 1 or 2 points

AL1 1 AL1 1
AL1 COM 2 Non-C 2 M3
AL2 3 AL2 3
terminals
ALM2 COM 4 COM 4 1 7 13
Note 1)
2 8 14
Note 1: Power supplies for AL1 and AL2 must be of
the same type, either AC or DC. 3 9 15
Process value input
Power supply 4 10 16 Universal input
5 11 17
24 V AC/24 V DC 100-240 V AC A
+
16 16
6 12 18
B
+ +
17 17 17 17
5 5
B
18 - 18 18 - 18 -
6 6
Thermocouple RTD Current Voltage
50/60Hz 50/60Hz input input

12
Standard type (base model: PXF5, PXF9)
Relay output Relay output SSR Current
(SPDT) Voltage
(SPST)
OUT1 + + +
Control
1 1 NO 1 OUT1 1 OUT1 1 OUT1
OUT1
output 1 2 2 COM 2 - COM 2 - COM 2 - COM
3 NC

Relay output Re-transmission Re-transmission


SSR Current Voltage output (current) output (voltage)
(SPST)

+ + + + +
Control 4 4 OUT2 4 OUT2 4 OUT2 4 OUT2 4 OUT2
output 2 OUT2
5 5 - COM 5 - COM 5 - COM 5 - COM 5 - COM

M3 terminals
1 13 25
Option
2 14 26
RS-485 Digital input CT input
3 15 27
4 16 28
Alarm output 5 17 29
+ 27 DI1 31
25
2 points 3 points 1 or 2 points RS485 28 DI-COM 32 CT1
6 18 30
(independent common) 26 -
7 19 31 29 DI2 33
AL1 6 AL1 6 AL1 6
8 20 32
AL1 COM 7 AL2 7 Non-C 7
9 21 33
AL2 8 AL3 8 AL2 8
10 22 34
AL2 COM 9 COM 9 COM 9
Note 1) 11 23 35

Note 1: Power supplies for AL1 and AL2 must be of the same type, 12 24 36
either AC or DC.
Option Process value input
Digital output Digital input Remote SV input Universal input
Power supply
A
+
24 V AC/24 V DC 100-240 V AC 17 DI3 34 34
13 AL4 + +
B
+
18 DI-COM 23 35 35 35 35
11 11 14 COM RSV1 B
19 DI4 24 - 36 - 36 36 - 36 -
12 12 15 AL5
20 DI5 Thermocouple RTD Current Voltage
input input
50/60Hz 50/60Hz

Motorized valve control type (base model: PXF5, PXF9)

Valve control
Open
1
2
COM
Valve
control
output 1 Valve control

Close
4
5
COM M3 terminals

1 13 25
Option
2 14 26
RS-485 Digital input PFB input
3 15 27
4 16 28 30 I+
+ 27 DI1
Alarm output 5 17 29 25 31 PFB
RS485 28 DI-COM
2 points 6 18 30 26 32
(independent common) 3 points 1 or 2 points -
29 DI2
7 19 31 33 I–
AL1 6 AL1 6 AL1 6 8 20 32
AL1 COM 7 AL2 7 Non-C 7 9 21 33
AL2 8 AL3 8 AL2 8 10 22 34
AL2 COM 9 COM 9 COM 9 11 23 35
Note 1)
12 24 36
Note 1: Power supplies for AL1 and AL2 must be of the same type,
either AC or DC.

Process value input


Power supply Option Universal input
24 V AC/24 V DC 100-240 V AC Digital input A
+
34 34
B
+ +
35 35 35 35
11 11 17 DI3 B
36 - 36 36 - 36 -
12 12 18 DI-COM
Thermocouple RTD Current Voltage
50/60Hz 50/60Hz input input

13
Specifications
General specifications Valve position feedback signal (potentiometer) input (option)
Power supply volt- Model PXF5 and PXF9 (not available for PXF4)
100 V (-15%) to 240 V (+10%) AC, 50/60 Hz, 24 V AC/DC (±10%)
age Resistance range 100Ω to 2.5kΩ, three-wire
Model 100 to 240 V AC 24 V DC/AC Resolution 0.5% FS
Power consumption PXF4 10 VA MAX. 5 VA MAX. Accuracy ±1.0%FS
PXF5 & PXF9 13 VA MAX. 8 VA MAX. Temperature effect on sensitivity ±0.5%FS/10°C
Insulation resistance 20 MΩ or more (at 500 V DC) Burnout function None
Power source ↔ all terminals: 1500 V AC for 1 min
Withstand voltage Relay contact output ↔ all terminals: 1500 V AC for 1 min Control output
Between others: 500 V AC for 1 min
No. of points Up to 2 (2 points: Heating/cooling control)

Process value input 1. Relay contact output (SPST)


• Proportional cycle: 1 to 150 s
Number of inputs 1 • Contact structure: 1 SPST contact *SPST: single pole single throw
Input setting Programmable scale • Contact capacity: 250 V AC/30 V DC, 3A (resistive load)
See Table 1 on Page 15. • Minimum ON/OFF current: 10 mA (5 V DC)
Input signal • Mechanical life: 20 million operations MIN. (100 operations/min)
(Universal input: thermocouple/RTD/voltage/current)
• Electrical life: 100,000 operations MIN. (rated load)
Standard measurement 2. Relay contact output (SPDT)
See Table 1 on Page 15.
range and input type • Proportional cycle: 1 to 150 s
• ‌Thermocouple input: either ±1°C ±1 digit or ±0.3% of indicated • Contact structure: 1 SPDT contact *SPDT: single pole double t row
value ±1 digit, whichever is larger • Contact capacity: 250 V AC/30 V DC, 5A (resistive load)
*except: • Mechanical life: 50 million operations MIN. (100 operations/min)
Thermocouple B: 0 to 400°C: no accuracy assurance • Electrical life: 100,000 operations MIN. (rated load)
Indication accuracy Thermocouple R: 0 to 500°C: ±3°C ±1 digit 3. SSR drive output
(at Ta = 23°C) Thermocouples of which measuring range is between -200°C and • Proportional cycle: 1 to 150 s
-100°C: ±2°C ±1 digit Type • ON voltage: 12 V DC (between 10.7 and 13.2 V DC)
• ‌RTD input: ±0.8°C ±1 digit or ±0.2% of indication value ±1 digit, Select among 1 to 6 • OFF voltage: 0.5 V DC or lower
whichever is larger • Maximum current: 20 mA DC
• mV input, voltage input, current input: ±0.3%FS ±1 digit • Load resistance: 600 Ω MIN.
Temperature effect 4. Current output (0 to 20 mA DC/4 to 20 mA DC)
±0.3%FS/10°C • Accuracy: ±5%FS
on sensitivity
Indication resolution See Table 1 on Page 15. • Load resistance: 500 Ω MAX.
5. Voltage output (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC)
Sampling rate 50 ms
• Accuracy: ±5%FS
• Thermocouple, mV input: 1 MΩ or more Load resistance: 10 kΩ MIN.
Input impedance • Current input: 150 Ω or less (built-in diode) 6. Motorized valve control output
• Voltage input: About 1 MΩ • C ontact structure: 2 SPST contacts without interlock circuit
Variation by signal • Thermocouple, mV input: ±0.3%FS ±1 digit per 100 Ω *SPST: Single Pole Single Throw
source resistance • Voltage input: ±0.3%FS ±1 digit per 500 Ω • Contact capacity: 250 V AC/30 V DC, 3A (resistive load)
Allowable wiring • Minimum ON/OFF current: 100 mA (24 V DC)
• RTD: 10 Ω MAX. (per wire) • Mechanical life: 20 million operations MIN. (100 operations/min)
resistance
• Electrical life: 100,000 operations MIN. (rated load)
• DC voltage input: within ±35 V
Allowable input volt-
• Current input: within ±25 mA
age:
• Thermocouple, RTD, mV input: within ±5 V Alarm output (DO) (option)
Normal mode: 40 dB (50/60 Hz) Relay contact
Noise reduction ratio Common mode: 120 dB (50/60 Hz) Number of outputs Shared COM: PXF5 & PXF9: ≤5, PXF4: ≤3
Between input and power supply: ±1°C at 220 V AC, 50/60 Hz Independent COM: PXF5 & PXF9: ≤3, PXF4: ≤2
(a) User adjustment: ±50%FS for each of zero and span point Relay contact output
(b) Process value shift: ±10%FS • Contact structure: SPST *SPST: single pole single throw
Input correction
(c) Input filter: 0.0 to 120.0 s (filter is off when set to 0.0) • Contact capacity: 250 V AC/30 V DC, 1A (resistive load)
Output specifications
(d) Square root extraction: -0.1 to 105% (OFF if set to -0.1%) Minimum ON/OFF current: 10 mA (5 V DC)
Out of the range between -5% and 105% FS (accuracy is not as- • Mechanical life: 20 million operations MIN. (100 operations/min)
sured between -5 and 0, and between 100 and 105%FS) Electrical life: 100,000 operations MIN. (rated load)
Overrange · *except: Alarm output (see "Alarm function"), main unit control mode output,
Output functions
underrange • Pt (-200°C to 850°C) input: Out of the range between program status output, control output 1 and 2, etc.
• 0 to 10 V DC input: -2% to 105% of FS Output cycle 100 ms
• Thermocouple E: Out of the range between -5 to 102% of FS
Re-transmission output (option)
Remote SV input (option)
No. of points 1
Number of inputs 1 Current/voltage output (0 to 20 mA DC/4 to 20 mA DC/0 to 5 V DC/1
Voltage: 0 to 5 V DC/1 to 5 V DC/0 to 10 V DC to 5 V DC/ 0 to 10 V DC/2 to 10 V DC)
Input signal Current: 0 to 20 mA DC/4 to 20 mA DC (an external resistance of • Guaranteed output range: 0 to 21 mA DC/0 to 10.5 V DC
250 Ω is required for current input) Type
• Accuracy: ±0.2%FS (±5%FS at 1 mA or smaller)
Input impedance Approx. 1 MΩ • Resolution: 10,000 MIN.
Sampling rate 50 ms • Load resistance: 500 Ω MAX. (current), 10 kΩ MIN. (voltage)
Output cycle 100 ms
Current transformer (CT) input (option) Output contents PV, SV, DV, MV
Single phase CT, 1 point Additional function Scaling function
Input type For 1 A to 30 A: CTL-6-S-H
For 20 A to 100 A: CTL-12-S36-8 Display and keys
Range of detected Type LCD (with backlight)
1 A to 100A
current Process value indication: 11-segment, 4-digit [white]
Detected current Setpoint indication: 11-segment, 4-digit [green]
Setpoint ±5%FS Indication contents
accuracy Screen No. indication: 7-segment, 4-digit [orange]
Detected current Status indication: 42 indicator lamps
0.1A
resolution Luminance setting possible (4 steps)
ON time necessary Keys Sheet type keys (with emboss), 5 keys
300 ms MIN.
for detection
Control functions
Digital input (DI) (option) ON/OFF control Refer to page 4.
• Dual control (heating/cooling)
PXF5 and PXF9: up to 3 PID control
• PID parameters determination: Auto tuning
No. of points PXF4 standard version: 1
PXF4 motorized valve control version: 3 • Dual control (heating/cooling)
Fuzzy PID control
Specifications No-voltage contact or transistor input • PID parameters determination: Auto tuning
Contact capacity: 5 V DC, about 2 mA (per point) Self tuning control Refer to page 5.
ON voltage: 2 V DC or lower • Dual control (heating/cooling)
Input judgment: PID2 control
OFF voltage: 3 V DC or higher • PID parameters determination: Auto tuning
Sampling pulse width 50 ms MIN. 2-degrees-of-freedom PID • PID parameters determination: Auto tuning
Remote mode selection, SV changeover, control standby, AT startup, Position proportional PID
• Full stroke time: 30 seconds MIN. (not available for PXF4)
Functions timer startup, alarm unlatch, program selection, start/stop/reset, PID (servo) with position feedback
switching (normal/reverse), etc.

14
Control parameters Operation and storage conditions
Proportional band (P) 0.1% to 999.9% Operating temperature -10°C to 50°C
Integration time (I) ‌‌0 to 3200 s (invalidated when I = 0) Storage temperature -20°C to 60°C
Differential time (D) ‌0.0 to 999.9 s (invalidated when D = 0) Operating/storage humidity 90%RH or less (Non condensation)
Control cycle 100 to 900 ms (in 100 ms), 1 to 99 s (in seconds) Warm-up time 30 min MIN.
Vibration during transportation: 9.8 m/s2 (1 G) or less
Anti-reset windup 0 to 100% of measurement range
Impact during transportation: 294m/s2 (30 G) or less
Hysteresis band 50% of measurement range (at 2-position control only)
Number of SV and 8: Changed by any of parameter setting, digital input, communica- Enclosure
PID patterns tion, user function keying, zone change. Installation Panel mount
External terminals Screw terminals, M3
Control mode • Material: ABS, PPO
Auto/Manual/Remote Case • Non-combustibility grade: UL94V-0 equivalent
Mode *During 2-position control in Manual mode, 2-position manual opera- • Color: Black
tion with MV = 100% or 0% is operated. • ‌Panel front side: IP66, NEMA-4X equivalent (When the panel is
• Auto ↔ Manual: Balanceless ∙ bumpless mounted using our genuine packing. Not water-proof if mounted
Mode changeover: • Auto/Manual→Remote: Balance ∙ bumpless Protection structure closely together.)
• Auto/Manual Remote: Balance ∙ bumpless • Body: IP20 equivalent (slits on top and bottom)

• Terminals: IP00 equivalent. Terminal cover can be mounted optionally.
Alarm Dimensions Refer to page 9.
Number of alarm Up to 5 (depends on the number of DO) Weight PXF4: approx. 100 g, PXF5: approx. 170 g, PXF9: approx. 220 g
Process value (upper limit/lower limit, absolute/deviation, range),
Alarm type main unit error, etc.(non-excitation, delay, latch, timer function option
Customizable function and Program (ramp/soak) function
provided) Number of program 64 steps × 1 pattern, 32 steps × 2 patterns, 16 steps × 4 patterns,
Heater current alarm steps: or 8 steps × 8 patterns (1 step = 2 segments)
Current transformer (CT) is to be prepared separately (see page 10.)
function (option) Control by digital input
Control option
Status output by digital output
Detectable range 1 A to 100 A
1. Segment time can be set in "Hour, Minutes" or "Minutes, Seconds"
Detected current resolution 0.1A 2. Guarantee soak
Setting resolution 0.1A 3. Repeat action
Basic functions
4. PV start
Hysteresis 0.0 to 100.0 A
5. Delay start
6. Power restoring function
RS-485 communication (option) Memory backup EEPROM
No. of points 1 point
Physical specifications EIA-485
Protocol Modbus-RTU
User key
Communication method Half-duplex bit serial, asynchronous communication Auto/Manual change, Standby ON/OFF change, remote SV change,
Assignable functions
Code type Data length: 8 data bits. Parity: Odd, even, none. ramp/soak change, etc.
Baud rate 9600 bps, 19200 bps, 38.4 kbps, 115.2 kbps
Connection Up to 32 units
Password function
Communication distance Up to 500 m (total connection length) 3-level password
• Multidrop master function
The function in which slave devices can be operated by a master Simple watt-hour metering function and operating days alarm
device by connecting several temperature controllers. • By connecting a current transformer (to be prepared separately),
• Programless communication electric power consumption of the heater can be displayed. (Elec-
Additional function Simple watt-hour
The function in which a temperature controller can be connected tric power is calculated based on the fixed voltage value you set.)
to a PLC without program. metering function
• Current transformer (CT) is to be prepared separately (see page 10.)
Supported PLCs: Mitsubishi
‌ PLC Q series • Current detection range: 1 A to 100 A
Siemens PLC S7 series • ‌Indicates the number of days the controller has been operated
Operating days and activates alarm output (optional) when it exceeds the setpoint.
alarm • ‌Useful for preventive maintenance because it let you know the ap-
propriate time for maintenance work.

Data backup at power outage


on non-volatile memory

Self-diagnosis
Program error supervision by watchdog timer

Table 1 input type and range


Input type Code (PvT) Measurement range [°C] Minimum input increment [°C] Input type Code (PvT) Measurement range [°C] Minimum input increment [°C]
PT1 0.0 to 150.0 0.1 J1 0.0 to 400.0 0.1
PT2 0.0 to 300.0 0.1 J2 -20.0 to 400.0 0.1
J
PT3 0.0 to 500.0 0.1 J3 0.0 to 800.0 0.1
PT4 0.0 to 600.0 0.1 J4 -100 to 1000 1
RTD Pt 100
PT5 -50.0 to 100.0 0.1 K1 0 to 400 0.1
PT6 -100.0 to 200.0 0.1 K2 -20.0 to 500.0 0.1
K
PT7 -199.9 to 600.0 0.1 K3 0.0 to 800.0 0.1
PT8 -200 to 850 1 K4 -200 to 1300 1
0 to 5 V DC 0-5V R R 0 to 1700 1
1 to 5 V DC 1-5V B B 0 to 1800 1
DC voltage 0 to 10V DC 0-10 -1999 to 9999 (Range Thermocou- S S 0 to 1700 1
2 to 10V DC 2-10 where scaling is al- - ple T1 -199.9 to 200.0 0.1
lowed) T
0 to 100mV DC MV T2 -199.9 to 400.0 0.1
0 to 20 mA DC 0-20 E1 0.0 to 800.0 0.1
DC current
4 to 20 mA DC 4-20 E E2 -150.0 to 800.0 0.1
E3 -200 to 800 1
L L -100 to 850 1
U1 -199.9 to 400.0 0.1
U
U2 -200 to 400 1
N N -200 to 1300 1
W W 0 to 2300 1
PL-II PL-2 0 to 1300 1

15
Please read the following instructions carefully before operating the Digital Temperature Controller

WARNING Over-Temperature Protection


Any control system design should take into account that any part of the system has the potential to fail.

For temperature control systems, continued heating should be considered the most dangerous condition, and the machine should be
designed to automatically stop heating if unregulated due to the failure of the control unit or for any other reason.

The following are the most likely causes of unwanted continued heating:

1) Controller failure with heating output constantly on


2) Disengagement of the temperature sensor from the system
3) A short circuit in the thermocouple wiring
4) A valve or switch contact point outside the system is locked to keep the heat switched on.

In any application where physical injury or destruction of equipment might occur, we recommend the installation of independent safety
equipment, with a separate temperature sensor, to disable the heating circuit in case of overheating.

The controller alarm signal is not designed to function as a protective measure in case of controller failure.

Information in this catalog is subject to change without notice.


Read the instruction manuals thoroughly before using the products.

www.fujielectric.com

Instrumentation & Sensors Planning Dept.


Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
Phone: +81-3-5435-7021 Fax: +81-3-5435-7475
www.fujielectric.com/products/instruments/

Printed in Japan 2018-9/3 FOLS