21B1-E-0062e
Superior Versatility and Flexibility
for a Wide Range of Applications
Control output indicator Alarm output (DO) indicator
→P7
Manual operation
Ramp/soak status indicator
→P5
Parameter number
MV Bar graph
User key
Simple
Watt-Hour
Metering
Function
2
RS-485 Communication (option) Universal Input
Bright and clear white PV display for optimal viewing With only 58-mm depth, compact enough to be installed
on small equipment
15.3 mm
58 mm
PXF4
3 different sizes, with a depth of 58 mm Parameter loader software is download free from our
website. Optional USB cable enables PXF to be
connected to and powered from PC.
USB
PXF9 PXF5 PXF4
96 x 96 mm 48 x 96 mm 48 x 48 mm USB cable
3
Advanced Control Functions
Parameter setting is available using the front keys or a PC with Fuji Electric’s loader software.
Standard Functions
1
On/off Control Control characteristic of ON/OFF action
Hysteresis
When process value (PV) is below the set value (SV), PXF turns on the output
to energize the heater, and vice versa. In this way, PXF keeps the temperature
constant by turning the output on and off based on the SV as a threshold. ON
Time
Heater
OFF
2
PID Control with Auto Tuning
Molding Machine
Typical Control Based on PID Theory
Start/stop of auto tuning can be
* Overshoot may occur due to commanded externally.
external disturbance. Setpoint
SV SV
SV -10%
PV (process value)
(Control output)
(Control output)
PV (process value)
ON ON Heater
100% ON ON 100% ON ON
OFF OFF OFF OFF OFF OFF
0% PID control 0% PID control
ON-OFF action ON-OFF action
3 4
Fuzzy Control with Auto Tuning 2-Degree-of-Freedom PID with Auto Tuning
Suppresses Overshoot by Fuzzy Calculation Combined Method for Stable Control
By monitoring PV, PXF suppresses overshoot without Suppresses overshoot and undershoot occurs at
lengthening startup time. At the same time, it can startup or at SV change, or by external disturbances.
quickly deal with external disturbances.
SV SV
Fuzzy control Conventional control
PV PV
• 2-degrees-of-freedom PID
(with optimal α and β)
Overshoot Response to Overshoot Response to Process value
disturbances disturbances
SV
PV
Time
4
5 6
Open-Loop Supported PID2 Control Self Tuning Control
Suppresses Overshoot Auto-Tuned PID for Changing Temperature
Reduces overshoot Process
value
Overshoot is controlled At power up, SV change, or
in the processes SV during external disturbance,
where the controlled PV tuning is made automatically
equipment is power ON
so that the PID parameters External
Set value disturbance
cycled. Power supply to
control equipment
t are re-optimized. change
OFF Close Close *For some objects of control, PID values
Control loop Power on
Open cannot be optimized.
7
Simple Program Control (Ramp Soak Function)
Controlling Temperature Gradient of Furnace
Up to 64 Steps
by heating patterns
PXF automatically changes SV to the preset values at preset times.
Digital input
You can set up to 64 steps and 15 types of operation patterns. For Ramp soak action Temperature input Thermocouple
example, when you bake four kinds of bread, you can divide 64 command
ON: Start Furnace
steps into four patterns to set suitable temperature for each bread. OFF: Reset
SSR drive
SV Example of 16 steps x 4 patterns output
SV-8 Max. SSR
64
step 2 step 3 SV-7 SV-9
step 1 SV-3 SV-13
SV-4 SV-12
steps!! Ramp Soak Function
SV-2 SV-10 SV-14
SV-5 Temperature rise/fall pattern is controlled by
SV-1 SV-11 SV-15 setting a heat pattern having a gradient. You can
SV-16
externally start or reset the pattern.
SV-6
PV
TM1s TM5s TM16r Time
TM1r TM5r SV-8
TM16s
Setpoint SV-7
step 1 to 4: pattern 1 step 5 to 8: pattern 2 step 9 to 12: pattern 3 step 13 to 16: pattern 4 SV-3
SV-4
SV-2
■ Basic functions ■ Operation ■ Number of steps and SV-5
1. [h · min] or [min · s] You can start/stop/suspend patterns SV-1 SV-6
2. Guarantee soak the operation using a user Steps Patterns
3. Repeat action key, parameter setting, digital 64 1
4. PV start input, or communication. 32 2
5. Delay start Time
16 4
6. Power restoring function
8 8
Optional Functions
1
Heating and Cooling Control
Energy Savings in Livestock Barns
with Dual Output
Both heating and cooling are controlled with one
temperature controller using its two control outputs.
Output
Heating side Cooling side Heating side Output Cooling side Power consumption can be curbed by controlling a cooling fan
Coefficient 0.5 motor with inverter.
Coefficient 1.0 Temperature input signal
Coefficient 2.0
Cooling fan motor
Current output
Deviation Set value (SV) Deviation Deviation Deviation (+) Room M
(-) (+) (-) Overlap band temperature
Heating side Cooling side Dead band
Proportional Proportional
band band Inverter
Proportional band (P) Set value (SV)
Current output
in shed
Heater power supply
To heater
Cattle shed AC power regulator (APR)
* For the cooling side proportional band, set a coefficient with respect to the heating side
proportional band. (Works as on-off control if coefficient is zero.)
2
Motorized Valve Control
Heating/Cooling Control of Air Conditioner
Valve Opening/Closing is Available
Command switch
Summer Winter
· Position feedback control based on motorized valve Close in summer, open in winter Switching
5
Variety of Functions
Expanding the Uses of Temperature Controllers and Improve the User Experience
Standard Functions
PID switching
Palette 1 Palette 2 Soft start
Palette 7
output set
value
MV with
soft start (limited)
SV switching
SSR
PID switching SSR drive 0% t
output
Soft start
PLC set time
Power ON or
Digital input ON
Voltage: estimated value set by user (220 V) Voltage: estimated value set by user (220 V)
Current: value measured by CT Current: estimated value set by user (0.2 A)
Optional Functions
1 2
Re-transmission Output
Temperature Signals to External Heater Burnout Alarm
Devices Quickly Informs You a Failure
Cost savings achieved by eliminating the need for an extra • A current transformer (CT) is required.
temperature sensor • The alarm action point must be configured beforehand.
• Output signal : 0–20 mA DC, 4–20 mA DC, 0–5 V DC, 1–5 V
DC, 0–10 V DC, or 2–10 V DC [Example of PXF5/PXF9]
*Available only for single-
Power supply 100–240 V DC, 50/60 Hz
• Process value (PV), set value (SV), control output (MV), or phase heater
PV-SV (DV) 11 Power supply *Not available when using
thyristor phase angle control
12 Control output 1
1 6
PV transfer
output Temperature input
2
+ -
7
31 33 35 36
Heater burnout
MG alarm output
Voltage/ Fryer SW
current Electromagnetic switch
Current
Current transformer Wired to PXF
control (CT) (with no polarity)
signal Thermocouple
Recorder PHR Oil
Heater Wired to heater
AC power regulator (through hole in CT)
(APR) Heater Electric furnace
6
3 4
Alarm Output Digital Input
Up to 5 Alarms (PXF4: up to 3) SV Can be Switched Externally
Alarm type Action diagram SV change, AT start, timer startup, program selection, start/
stop/reset, PID changeover, etc.
Changeover of 4 set values
Absolute value alarm
5
hold) SV
Lower limit deviation (with ALn
PV
Remote SV Input
hold) SV
Upper and lower limits ALn ALn SV Can be Configured Externally
PV
deviation (with hold) SV
ALn ALn
• Input signal: 0–5 V DC, 1–5 V DC, 0–10 V DC,
Range upper and lower limits deviation 0-20 mA DC, or 4–20 mA DC
(ALM1/2 independent operation) PV
SV • Input impedance: About 1 MΩ
Range upper and lower PV
limits absolute value AL2 AL1
Range alarm
PLC
AL2 AL1
Range upper and lower Set temperature (SV)
limits deviation SV
PV 1 to 5 V DC
AL2
Range upper limit absolute
value and lower limit deviation SV AL1
PV
AL1
Range upper limit deviation and
lower limit absolute value AL2 SV
PV Control Temper-
output ature input
6
• Multidrop master function
RS-485 Communication Synchronous temperature-rise control is available in
combination with 2-degrees-of-freedom PID.
Synchronized heating function
• User address mapping function Example: injection molding
Users can create a list of necessary parameters (max. 32 RS485
SV SV SV machine
words) for quick data acquisition on that data set.
Communication speed: max. 115.2 kbps
7
Product Lineup
Model PXF4 PXF5 PXF9
Appearance
8
Outline Diagram
PXF4
Outer dimensions Panel cutout
48 (terminal cover)
(48 × n-3) 0
+0.5
45 0
73 MIN.
+0.5
44.8
48
57
0
45
In horizontal close mounting where the
63 MIN. packing cannot be used, PXF front panel
does not meet NEMA 4X nor IP66.
PXF5
Outer dimensions Panel cutout
+0.8
+0.8 (48 × n-3) 0
92 0
+0.8
116 MIN.
110.4
0
91.4
92
96
t (panel thickness) 1 ≤ t ≤ 8
Terminal cover
Panel (option)
* Dimensions include coating thickness.
PXF9
Outer dimensions Panel cutout
116 MIN.
110.4
91.4
96
100 MIN.
Rear view
PXF4 PXF5 PXF9
Terminal M3
Terminal M3 Terminal M3
9
4 5 6 7 8 9 10 11 12 13
Ordering Code PX F A 2 - 0 0
PXF4 Standard Type PXF4 Motorized Valve Control Type
Digit Specifications Code Digit Specifications Code
Front panel size W x H Front panel size W x H
1-4 1-4
48 × 48mm PXF4 48 × 48mm PXF4
5 - A 5 - A
Control output 1 Control output 1
6
Relay contact (SPST) *1 A Motorized valve control output (without PFB input) T
Relay contact (SPDT) *1 B Control output 2
6 7
SSR drive output C None Y
Current output E 8 Revision code 2
Voltage output P Alarm output
Control output 2 None 0
None Y 9 1 point 1
Relay contact (SPST) A 2 points F
SSR drive output C 2 points (independent common) J
7 Power supply voltage/instruction manual
Current output E
Voltage output P 100 to 240 V AC, Japanese & English Y
Re-transmission output (current) R 100 to 240 V AC, English V
Re-transmission output (voltage) S 10 100 to 240 V AC, Chinese & English W
8 Revision code 2 24 V AC/DC, Japanese & English A
Alarm output 24 V AC/DC, English B
None 0 24 V AC/DC, Chinese & English D
1 point 1 Option
9 None 1
2 points F 11
3 points M Digital input (DI 1, 2, 3) D
2 points (independent common) J RS-485 communication + Digital input (DI1) V
Power supply voltage/instruction manual 12
- 00
100 to 240 V AC, Japanese & English Y 13
100 to 240 V AC, English V
10 100 to 240 V AC, Chinese & English W
24 V AC/DC, Japanese & English A
24 V AC/DC, English B
24 V AC/DC, Chinese & English D
Option
None 1 Optional items
RS-485 Communication M Name Model
11 Digital input (DI1) S 1 A to 30A ZOZCCTL-6-S-H
Current transformer
RS-485 communication + Digital input (DI1) V 20 to 100A ZOZCCTL-12-S36-8
RS-485 communication + Remote SV input *2 K Terminal cover ZZPPXR1-A230
RS-485 Communication + CT input *3 J Parameter loader interface cable ZZPTQ501923C3
12 Shunt resistor (250 Ω±0.1%) ZZPPXR1-A190
- 00
13 Panel mounting adapter for replacement from PXR7 to PXF4 ZZPTQ502732C1
*1: Not available for the 7th code “C”, “E”, “P”, “R”, “S”. However, if you want to order the 6th
code “A” (SPST relay contact for the control output 1) and the 7th code “R” or “S” (current/
voltage re-transmission output for the control output 2), specify the model as follows:
R
PXF4AA 2- 02
S
*2: When using current for the remote SV input, add a 250-ohm resistor to the input terminal.
*3: When using the CT input for heater burnout alarm, add one alarm output for it in the 9th
code.
PXF5 & PXF9 Standard Type PXF5 & PXF9 Motorized Valve Control Type
Digit Specification Code Digit Specifications Code
Front panel size W x H Front panel size W x H
1-4 48 × 96 mm PXF5 1-4 48 × 96 mm PXF5
96 × 96 mm PXF9 96 × 96 mm PXF9
5 - A 5 - A
Control output 1 Control output 1
Relay contact (SPST) A 6 Motorized valve control output (without PFB input) S
Relay contact (SPDT) B Motorized valve control output (with PFB input) V
6
SSR drive output C Control output 2
7
Current output E None Y
Voltage output P 8 Revision code 2
Control output 2 Alarm output
None Y None 0
Relay contact (SPST) A 1 point 1
9
SSR drive output C 2 points F
7
Current output E 3 points M
Voltage output P 2 points (independent common) J
Re-transmission output (current) R Power supply voltage/instruction manual
Re-transmission output (voltage) S 100 to 240 V AC, Japanese & English Y
8 Revision code 2 100 to 240 V AC, English V
Alarm output 10 100 to 240 V AC, Chinese & English W
None 0 24 V AC/DC, Japanese & English A
1 point 1 24 V AC/DC, English B
9
2 points F 24 V AC/DC, Chinese & English D
3 points M Option
2 points (independent common) J 11 None 1
Power supply voltage/instruction manual RS-485 communication + Digital input (DI1, DI2, DI3) U
100 to 240 V AC, Japanese & English Y 12
- 00
100 to 240 V AC, English V 13
10 100 to 240 V AC, Chinese & English W
24 V AC/DC, Japanese & English A
24 V AC/DC, English B
24 V AC/DC, Chinese & English D Optional items
Option
Name Model
None 1
1 A to 30A ZOZCCTL-6-S-H
RS-485 Communication M Current transformer
20 to 100A ZOZCCTL-12-S36-8
Digital input (DI 1 and DI2) T
11 Terminal cover *1 ZZPPXF1-B100
Remote SV input + Digital input (DI3) *1 H
Parameter loader interface cable ZZPTQ501923C3
CT input + Digital input (DI1) *2 G
Shunt resistor (250 Ω±0.1%) ZZPPXR1-A190
RS-485 communication + Digital input (DI1) V
RS-485 + Digital input (DI3, DI4, DI5) + Auxiliary alarm output (AL4, AL5) C *1: For PXF9, two covers are necessary for one unit.
12
- 00
13 Scope of delivery
*1: When using current for the remote SV input, add a 250-ohm resistor to the input terminal. ∙ Controller × 1 ∙ Instruction manual × 1
*2: When using the CT input for heater burnout alarm, add one alarm output for it in the 9th ∙ Panel mounting adapter × 1 set ∙ Water-proof packing × 1
code.
10
Outline Diagram of Optional Items
Panel mounting adapter for replacement from PXR7 to PXF4 (ZZPTQ502732C1)
Panel mounting adapter How to install PXF4 with the adapter
PXF4
Mounting
bracket
72
48
PXF4
72
74
mounting hole
Mounting
screws (4 pcs)
Mounting frame
0.7 (provided with PXF4)
Watertight packing 4 61
30
ø2.36
21
15 2.8
9
7
ø5.8
40
25
10.5
2.5
ø12
10
Control output 1 (relay contact) Process value input Control output 1 (relay contact) Process value input
or Remote SV input or Remote SV input
Motorized valve OPEN output Motorized valve OPEN output
CT input Current transformer (CT) input
Control output 1
Control output 2 (relay contact) (SSR drive, current, voltage) Control output 2 (relay contact) Valve position feedback (PFB) input
or or
Motorized valve CLOSE output Control output 2 Motorized valve CLOSE output Control output 1
(SSR drive, current, voltage) (SSR drive, current, voltage)
Alarm output 1 Digital input 1 to 3 Alarm output 4 and 5 (relay contact) Control output 2 (SSR drive, current,
(Relay contact) Alarm output 1 to 3 voltage) or re-transmission output
Alarm output 2 (Relay contact)
Communication (RS-485) Alarm output 1 Digital input 1 to 3
(Relay contact) (Relay contact) Alarm output 1 to 3
Basic insulation Alarm output 2 (Relay contact)
When the 9th code is "J" When the 9th code Communication (RS-485)
(Relay contact)
(AL1 and AL2: is other than "J" Functional insulation
(AL1, AL2, and AL3: No insulation Basic insulation
independent common) When the 9th code is "J" When the 9th code
shared common)
(AL1 and AL2: is other than "J" Functional insulation
independent common) (AL1, AL2, and AL3: No insulation
shared common)
11
Connection Diagram
Standard type (base model: PXF4)
Control Relay output Relay output SSR Relay output Relay output SSR
output 1 Current Voltage Current Voltage
(SPST) (SPDT) (SPST) (SPDT)
Control Relay output Relay output Relay output Relay output Relay output
output 2 None None None None None (SPST) (SPST) (SPST) (SPST) (SPST)
OUT1 + + + OUT1 + + +
13 13 NC 13 OUT1 13 OUT1 13 OUT1 13 13 NC 13 OUT1 13 OUT1 13 OUT1
OUT1 - OUT1 -
14 14 COM 14 - COM 14 COM 14 - COM 14 14 COM 14 - COM 14 COM 14 - COM
15 NO 15 NO
11 11 11 11 11
OUT2 OUT2 OUT2 OUT2 OUT2
12 12 12 12 12
Option
Valve control
Digital input RS485
Close
11 +
12 7 7
COM DI3 RS485
8 8 -
Valve DI2
control 9
output 1 Valve control DI1
10
DI-COM
Open Digital input
13
14
COM
9 DI1
10 DI-COM
Alarm output
2 points
(independent common) 1 or 2 points
AL1 1 AL1 1
AL1 COM 2 Non-C 2 M3
AL2 3 AL2 3
terminals
ALM2 COM 4 COM 4 1 7 13
Note 1)
2 8 14
Note 1: Power supplies for AL1 and AL2 must be of
the same type, either AC or DC. 3 9 15
Process value input
Power supply 4 10 16 Universal input
5 11 17
24 V AC/24 V DC 100-240 V AC A
+
16 16
6 12 18
B
+ +
17 17 17 17
5 5
B
18 - 18 18 - 18 -
6 6
Thermocouple RTD Current Voltage
50/60Hz 50/60Hz input input
12
Standard type (base model: PXF5, PXF9)
Relay output Relay output SSR Current
(SPDT) Voltage
(SPST)
OUT1 + + +
Control
1 1 NO 1 OUT1 1 OUT1 1 OUT1
OUT1
output 1 2 2 COM 2 - COM 2 - COM 2 - COM
3 NC
+ + + + +
Control 4 4 OUT2 4 OUT2 4 OUT2 4 OUT2 4 OUT2
output 2 OUT2
5 5 - COM 5 - COM 5 - COM 5 - COM 5 - COM
M3 terminals
1 13 25
Option
2 14 26
RS-485 Digital input CT input
3 15 27
4 16 28
Alarm output 5 17 29
+ 27 DI1 31
25
2 points 3 points 1 or 2 points RS485 28 DI-COM 32 CT1
6 18 30
(independent common) 26 -
7 19 31 29 DI2 33
AL1 6 AL1 6 AL1 6
8 20 32
AL1 COM 7 AL2 7 Non-C 7
9 21 33
AL2 8 AL3 8 AL2 8
10 22 34
AL2 COM 9 COM 9 COM 9
Note 1) 11 23 35
Note 1: Power supplies for AL1 and AL2 must be of the same type, 12 24 36
either AC or DC.
Option Process value input
Digital output Digital input Remote SV input Universal input
Power supply
A
+
24 V AC/24 V DC 100-240 V AC 17 DI3 34 34
13 AL4 + +
B
+
18 DI-COM 23 35 35 35 35
11 11 14 COM RSV1 B
19 DI4 24 - 36 - 36 36 - 36 -
12 12 15 AL5
20 DI5 Thermocouple RTD Current Voltage
input input
50/60Hz 50/60Hz
Valve control
Open
1
2
COM
Valve
control
output 1 Valve control
Close
4
5
COM M3 terminals
1 13 25
Option
2 14 26
RS-485 Digital input PFB input
3 15 27
4 16 28 30 I+
+ 27 DI1
Alarm output 5 17 29 25 31 PFB
RS485 28 DI-COM
2 points 6 18 30 26 32
(independent common) 3 points 1 or 2 points -
29 DI2
7 19 31 33 I–
AL1 6 AL1 6 AL1 6 8 20 32
AL1 COM 7 AL2 7 Non-C 7 9 21 33
AL2 8 AL3 8 AL2 8 10 22 34
AL2 COM 9 COM 9 COM 9 11 23 35
Note 1)
12 24 36
Note 1: Power supplies for AL1 and AL2 must be of the same type,
either AC or DC.
13
Specifications
General specifications Valve position feedback signal (potentiometer) input (option)
Power supply volt- Model PXF5 and PXF9 (not available for PXF4)
100 V (-15%) to 240 V (+10%) AC, 50/60 Hz, 24 V AC/DC (±10%)
age Resistance range 100Ω to 2.5kΩ, three-wire
Model 100 to 240 V AC 24 V DC/AC Resolution 0.5% FS
Power consumption PXF4 10 VA MAX. 5 VA MAX. Accuracy ±1.0%FS
PXF5 & PXF9 13 VA MAX. 8 VA MAX. Temperature effect on sensitivity ±0.5%FS/10°C
Insulation resistance 20 MΩ or more (at 500 V DC) Burnout function None
Power source ↔ all terminals: 1500 V AC for 1 min
Withstand voltage Relay contact output ↔ all terminals: 1500 V AC for 1 min Control output
Between others: 500 V AC for 1 min
No. of points Up to 2 (2 points: Heating/cooling control)
14
Control parameters Operation and storage conditions
Proportional band (P) 0.1% to 999.9% Operating temperature -10°C to 50°C
Integration time (I) 0 to 3200 s (invalidated when I = 0) Storage temperature -20°C to 60°C
Differential time (D) 0.0 to 999.9 s (invalidated when D = 0) Operating/storage humidity 90%RH or less (Non condensation)
Control cycle 100 to 900 ms (in 100 ms), 1 to 99 s (in seconds) Warm-up time 30 min MIN.
Vibration during transportation: 9.8 m/s2 (1 G) or less
Anti-reset windup 0 to 100% of measurement range
Impact during transportation: 294m/s2 (30 G) or less
Hysteresis band 50% of measurement range (at 2-position control only)
Number of SV and 8: Changed by any of parameter setting, digital input, communica- Enclosure
PID patterns tion, user function keying, zone change. Installation Panel mount
External terminals Screw terminals, M3
Control mode • Material: ABS, PPO
Auto/Manual/Remote Case • Non-combustibility grade: UL94V-0 equivalent
Mode *During 2-position control in Manual mode, 2-position manual opera- • Color: Black
tion with MV = 100% or 0% is operated. • Panel front side: IP66, NEMA-4X equivalent (When the panel is
• Auto ↔ Manual: Balanceless ∙ bumpless mounted using our genuine packing. Not water-proof if mounted
Mode changeover: • Auto/Manual→Remote: Balance ∙ bumpless Protection structure closely together.)
• Auto/Manual Remote: Balance ∙ bumpless • Body: IP20 equivalent (slits on top and bottom)
→
• Terminals: IP00 equivalent. Terminal cover can be mounted optionally.
Alarm Dimensions Refer to page 9.
Number of alarm Up to 5 (depends on the number of DO) Weight PXF4: approx. 100 g, PXF5: approx. 170 g, PXF9: approx. 220 g
Process value (upper limit/lower limit, absolute/deviation, range),
Alarm type main unit error, etc.(non-excitation, delay, latch, timer function option
Customizable function and Program (ramp/soak) function
provided) Number of program 64 steps × 1 pattern, 32 steps × 2 patterns, 16 steps × 4 patterns,
Heater current alarm steps: or 8 steps × 8 patterns (1 step = 2 segments)
Current transformer (CT) is to be prepared separately (see page 10.)
function (option) Control by digital input
Control option
Status output by digital output
Detectable range 1 A to 100 A
1. Segment time can be set in "Hour, Minutes" or "Minutes, Seconds"
Detected current resolution 0.1A 2. Guarantee soak
Setting resolution 0.1A 3. Repeat action
Basic functions
4. PV start
Hysteresis 0.0 to 100.0 A
5. Delay start
6. Power restoring function
RS-485 communication (option) Memory backup EEPROM
No. of points 1 point
Physical specifications EIA-485
Protocol Modbus-RTU
User key
Communication method Half-duplex bit serial, asynchronous communication Auto/Manual change, Standby ON/OFF change, remote SV change,
Assignable functions
Code type Data length: 8 data bits. Parity: Odd, even, none. ramp/soak change, etc.
Baud rate 9600 bps, 19200 bps, 38.4 kbps, 115.2 kbps
Connection Up to 32 units
Password function
Communication distance Up to 500 m (total connection length) 3-level password
• Multidrop master function
The function in which slave devices can be operated by a master Simple watt-hour metering function and operating days alarm
device by connecting several temperature controllers. • By connecting a current transformer (to be prepared separately),
• Programless communication electric power consumption of the heater can be displayed. (Elec-
Additional function Simple watt-hour
The function in which a temperature controller can be connected tric power is calculated based on the fixed voltage value you set.)
to a PLC without program. metering function
• Current transformer (CT) is to be prepared separately (see page 10.)
Supported PLCs: Mitsubishi
PLC Q series • Current detection range: 1 A to 100 A
Siemens PLC S7 series • Indicates the number of days the controller has been operated
Operating days and activates alarm output (optional) when it exceeds the setpoint.
alarm • Useful for preventive maintenance because it let you know the ap-
propriate time for maintenance work.
Self-diagnosis
Program error supervision by watchdog timer
15
Please read the following instructions carefully before operating the Digital Temperature Controller
For temperature control systems, continued heating should be considered the most dangerous condition, and the machine should be
designed to automatically stop heating if unregulated due to the failure of the control unit or for any other reason.
The following are the most likely causes of unwanted continued heating:
In any application where physical injury or destruction of equipment might occur, we recommend the installation of independent safety
equipment, with a separate temperature sensor, to disable the heating circuit in case of overheating.
The controller alarm signal is not designed to function as a protective measure in case of controller failure.
www.fujielectric.com