Item Description Unit BOQ Qty


( EGP ) ( EGP )
16 Electrical System
General Notes
Contactor shall obtain authorities approvals during
construction stage, preparing all official submissions

Drawings, bill of quantities and specifications should


be taken into consideration when implementing the
required work

Bill of quantities listed in this estimate is for guidance


only and the contractor should review all quantities
as per drawings and site conditions

The contractor is required to supply all materials and


equipment necessary to finalize the work whether
mentioned or not mentioned in the bill of quantities

The contractor is required to complete the


implementation of all actions in accordance with the
World International Codes as well as in accordance
with Local Codes.

The contractor is required to check the existing


works at site with the new design drawings and
submit a coordinated shop drawing for the engineer
approval

The contractor is required to check existing tie in


points at site
The price must include any coordination cost to
implement the MEP activities in case of modification
that will might occurred by the ID designer for a part
or entire of the project furniture layout and or
reflected ceiling.

Provide spare parts as recommended by the


manufacturer for the number of years maintenance
as expected under local conditions and to allow for
emergency replacement due to accidental breakage
or failure as per specification.

The Contractor is required to prepare for the training


programs and factory inspections programs as per
the specifications requirements

1 MEDIUM VOLTAGE RING MAIN UNIT:


‫لوحات الجهد المتوسط الحلقية الرئيسية‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supplying, installing, connecting and testing 11 KV as
per electrical utility requirments 4 Cells R.M.U unit
including (SF6) load break switches 630A for the two
incomers with spare cell & (SF6) C.B 1250A for
outgoing cell, earthing, switches, earth fault
indicators, M.V Cables terminations, Measurement
Cell, interface with BMS and all accessories and
ancillary works and materials required for complete
1-1 Nr 2
installation as specified and as indicated on the
drawings and specifications with all protection and

2 MEDIUM VOLTAGE SWITCH GEAR


‫موزع الجهد المتوسط‬
Supply, install, test and operate (11 KV switch gear)
distributer 8 cells as shown on drawings and specs.
complete with all required as per electrical utility
requirments and all accessories, Metering cell and
ancillary works and materials required for complete
installation as specified and as indicated on the
drawings and specifications including:-
2 main incoming (SF6) C.B 1250 A - 11KV
1 Bus Coupler (SF6) C.B 1250A - 11KV
1 Bus Riser 1250A - 11K V
2.1 4 outgoing (SF6) C.B 630 A - 11KV Nr 1
With all protection and measuring devices, interface
with BMS, according to electrical power supply
authority requirments

3 MEDIUM VOLTAGE CABLES


‫كابالت الجهد المتوسط‬
Supply, install, connect, test & put into operation
Multicore AL cable XLPE insulated as per electrical
utility requirments, steel tape armoured and PVC
sheathed, the item shall include all excavation back
filling work road crossing, cable trenches and all
3.1 requirement for establishing work as specified in
drawing and specifications. ML 400
(3Cx240) Sqmm AL / XLPE / STA / PVC 11KV

4 DISTRIBUTION TRANSFORMER
‫محوالت التوزيع‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Furnishing, Supplying, installing, connecting and
testing of the Dry type distribution transformer,
11/0.4KV, 50 Hz [ + 2 x 2.5% & [ - 4 x 2.5% ] KV as per
electrical utility requirments complete with rails,
rycham, enclosure, fittings cable end box,
temperature monitoring, cable terminals for both
incoming cables, bus duct, components, accessories,
interface with BMS, electricity authority
requirements all necessary accessories and ancillary
works and materials required for complete
installation as specified and as
indicated on the drawings for the following:

4-1 Dry type, 1600KVA, (11/0.4) KV Nr 4


5 PRIME DIESEL GENERATOR SET
‫مولد الديزل‬
Supplying, installing, connecting and testing of
genset unit (at 50°C ambient) 0.8 p.f., 380 / 220V
Prime diesel Generator set complete all necessary
accessories and ancillary works and materials
required for complete noise level should not exceed
70db @ 7m from the center of the genset. and as
indicated on the drawings such as, but not limited to
the following:
Air circuit breaker inside enclosure with enough
space for cables termination, Sound proofing of
room / acoustic treatment, inlet and outlet
attenuators, Control panel, critical silencer, flexible
joints, exhaust pipes, daily fuel tanks, fuel lines from
Monthly tank, automatic and manual pumps with
control panel, accessories, canvas, duct, air outlet
louvers, vibration absorbtion, monitoring and
protection equipment, interface with BMS, Also
including a set of complete erection material and
special tools.for the following units:

5-2 1000 KVA PRIME RATING genset Nr 2


6 AUTOMATIC TRANSFER BYPASS SWITCH ( ATS )
‫مفاتيح الفصل االتوماتيكى‬
Supplying, installing, connecting and testing
(Automatic Transfer Switch) single selonoid double
throw type complete with all components including
control cables, interface with BMS and all necessary
accessories and ancillary works and materials
required for complete installation as specified and as
indicated on the drawings.

6-1 ATS -- 1250A FOR CHILLERS Nr 3


6-2 ATS -- 800A Nr 2
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
6-3 ATS-FP -- 1200A UL/FM Approved Type Nr 1
7 LOW VOLTAGE BUS DUCT SYSTEM:
‫بارات الجهد المنخفض‬
Supplying, installing, connecting and testing feeder
type, 3L+N with 50% integral earthing, Bimetal
busduct, indoor type complete with all necessary
accessories (elbows, transformer end box,
suspension elements,
expansion joints ….etc) as specified & down on
drawings.

7-1 Bus Duct 3200A, 380V, 50hz, 3L+N , 50 oC ML 200


7-2 Bus Duct 1600A, 380V, 50hz, 3L+N , 50 oC ML 60
8 MAIN DISTRIBUTION BOARDS
‫بارات الجهد المنخفض الرئيسية‬
Supply, install, connect, test and put into operation
the main low voltage distribution boards, complete
with Power factor correction, all protective devices,
measuring instruments, SIM (Smart Interface
Modules), interface with BMS, Communicating
digital power meters, terminal blocks, busbars,
Termination of incoming and outgoing bus duct /
Cables including cable glands, labels, tags,
terminations, components, accessories and all
related ancillary works as shown on drawings and
specified in specifications.

8-1 LVP-01 Nr 1
8-2 LVP-02 Nr 1
8-3 LVP-03 Nr 1
8-4 LVP-04 Nr 1
8-5 ELVP-01 Nr 1
8-6 ELVP-02 Nr 1
8-7 EMDB - Synchronization Panel Nr 1
8-8 Automatic / Manual Coupler Cell 3200A Nr 2
9 SUBMAIN DISTRIBUTION BOARDS
‫لوحات التوزيع الشبة عمومية‬
Supply, install, connect, test and put into operation
the submain low voltage distribution boards,
complete with all protective devices, measuring
instruments, SIM (Smart Interface Modules),
interface with BMS, Communicating digital power
meters, terminal blocks, busbars, Termination of
incoming and outgoing Cables including cable glands,
labels, tags, terminations, components, accessories
and all related

9-1 USMDB-OP-TH1 Nr 1
9-2 USMDB-OP-TH2 Nr 1
9-3 USMDB-M Nr 1
9-4 SMDB-G Nr 1
9-5 SMDB-F Nr 1
9-6 SMDB-S Nr 1
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
9-7 SMDB-TH Nr 1
9-8 SMDB-AC-R Nr 1
9-9 SMDB-AC-UR Nr 1
9-10 SMDB-ELEV Nr 1
9-11 ESMDB-G Nr 1
9-12 ESMDB-F Nr 1
9-13 ESMDB-S Nr 1
9-14 ESMDB-TH Nr 1
9-15 ESMDB-ELEV Nr 1
9-16 ESMDB-PR Nr 1
9-17 ESMDB-AC-R Nr 1
9-18 ESMDB-AC-UR Nr 1
9-19 CBSMDB-M Nr 1
9-20 CBSMDB-G Nr 1
DISTRIBUTION, LIGHTING AND POWER PANEL
10 BOARDS
‫لوحات التوزيع الفرعية‬
Supply, install, connect, test and put into operation
the distribution lighting and power panel boards,
complete with all protective devices, measuring
instruments, terminal blocks, busbars, termination of
incoming and outgoing cables including controlling
cable, bush bottons, cable glands, labels, tags,
components, accessories and all related ancillary
works as shown on drawings and specified in
specifications

10.1 DB-AC-R Nr 1
10.2 DB-P1-R Nr 1
10.3 DB-P2-R Nr 1
10.4 DB-L-R Nr 1
10.5 DB-L-TH3 Nr 1
10.6 DB-P-TH3 Nr 1
10.7 DB-L-TH1 Nr 1
10.8 DB-P-TH1 Nr 1
10.9 DB-AC-TH1 Nr 1
10.10 DB-P-TH2 Nr 1
10.11 DB-L-TH2 Nr 1
10.12 DB-L-S3 Nr 1
10.13 DB-P-S3 Nr 1
10.14 DB-AC-S3 Nr 1
10.15 DB-L-S1 Nr 1
10.16 DB-P-S1 Nr 1
10.17 DB-AC-S1 Nr 1
10.18 DB-AC-S2 Nr 1
10.19 DB-P-S2 Nr 1
10.20 DB-L-S2 Nr 1
10.21 DB-L-F1 Nr 1
10.22 DB-P-F1 Nr 1
10.23 DB-AC-F1 Nr 1
10.24 DB-L-F3 Nr 1
10.25 DB-AC-F3 Nr 1
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
10.26 DB-P-F3 Nr 1
10.27 DB-AC-F2 Nr 1
10.28 DB-P-F2 Nr 1
10.29 DB-L-F2 Nr 1
10.30 DB-L-G1 Nr 1
10.31 DB-P-G1 Nr 1
10.32 DB-AC-G1 Nr 1
10.33 DB-G-KIT Nr 1
10.34 DB-AC-G2 Nr 1
10.35 DB-P-G2 Nr 1
10.36 DB-L-G2 Nr 1
10.37 DB-M1 Nr 1
10.38 DB-AC-M1 Nr 1
10.39 DB-M2 Nr 1
10.40 EDB-R Nr 1
10.41 EDB-L-TH1 Nr 1
10.42 EDB-P-TH1 Nr 1
10.43 EDB-L-ICU.1 Nr 1
10.44 EDB-L-ICU.2 Nr 1
10.45 EDB-AC-ICU.2 Nr 1
10.46 EDB-L-TH1 Nr 1
10.47 EDB-P-TH1 Nr 1
10.48 EDB-P-NICU Nr 1
10.49 EDB-L-NICU Nr 1
10.50 EDB-L-S1 Nr 1
10.51 EDB-P-S1 Nr 1
10.52 EDB-L-S2 Nr 1
10.53 EDB-P-S2 Nr 1
10.54 EDB-P-F1 Nr 1
10.55 EDB-L-F1 Nr 1
10.56 EDB-P-F3 Nr 1
10.57 EDB-L-F3 Nr 1
10.58 EDB-AC-F3 Nr 1
10.59 EDB-L-F2 Nr 1
10.60 EDB-P-F2 Nr 1
10.61 EDB-PH2 Nr 1
10.62 EDB-G1 Nr 1
10.63 EDB-BO Nr 1
10.64 EDB-PH Nr 1
10.65 EDB-G-KIT Nr 1
10.66 EDB-G2 Nr 1
10.67 EDB-SEC1 Nr 1
10.68 EDB-SEC2 Nr 1
10.69 EDB-M1 Nr 1
10.70 EDB-M2 Nr 1
10.71 EDB-PR Nr 1
10.72 EDB-SUB Nr 1
10.73 UDB-R Nr 1
10.74 UDB-TH1 Nr 1
10.75 UDB-TH2 Nr 1
10.76 UDB-S1 Nr 1
10.77 UDB-S2 Nr 1
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
10.78 UDB-F3 Nr 1
10.79 UDB-F2 Nr 1
10.80 UDB-G1 Nr 1
10.81 UDB-G2 Nr 1
10.82 UDB-M1 Nr 1
10.83 UDB-M2 Nr 1
10.84 UDB-IT Nr 1
10.85 EDB-L-G2 Nr 1
10.86 EDB-P-G2 Nr 1
10.87 EDB-PH1 Nr 1
10.88 EDB-CH Nr 1
10.89 UDB-F1 Nr 1
10.90 EDB-F1 Nr 1
10.91 EDB-F2 Nr 1
10.92 UDB-S3 Nr 1
10.93 DB-H-S3 Nr 1
10.94 EDB-P-S3 Nr 1
10.95 EDB-L-S3 Nr 1
10.96 DB-AC-TH2 Nr 1
10.97 DB-H-TH3 Nr 1
10.98 EDB-L-TH2 Nr 1
10.99 EDB-P-TH2 Nr 1
10.100 UDB-NICU-TH Nr 1
10.101 DB-L-FO2 Nr 1
10.102 DB-L-FO1 Nr 1
10.103 DB-L-FO3 Nr 1
10.104 DB-P-FO2 Nr 1
10.105 DB-P-FO1 Nr 1
10.106 DB-AC-FO1 Nr 1
10.107 DB-P-FO3 Nr 1
10.108 UDB-FO1 Nr 1
10.109 EDB-L-FO1 Nr 1
10.110 EDB-P-FO1 Nr 1
10.111 UDB-ICU2-FO2 Nr 1
10.112 UDB-ICU2-FO3 Nr 1
10.113 UDB-ICU1-FO2 Nr 1
10.114 UDB-ICU1-FO3 Nr 1
10.115 CB-G Nr 1
10.116 CB-F Nr 1
10.117 CB-S Nr 1
10.118 CB-TH Nr 1
10.119 CB-FO Nr 1
10.120 CB-R Nr 1
11 LANDSCAPE LIGHTING PANEL BOARD
‫لوحة االضاءة الخارجية‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, connect, test and put into operation
the distribution landscape lighting panel boards,
complete with Contactors, photocell relay, timer,
push buttons, BMS interface, control circuits, and all
protective devices, measuring instruments, terminal
blocks, busbars, termination of incoming and
outgoing cables including controlling cable, bush
bottons, cable glands, labels, tags, components,
accessories and all related ancillary works as shown
on drawings and specified in specifications

11-1 EDB-LS Nr 1
12 MEDICAL EQ. DISTRIBUTION PANEL BOARDS
‫لوحات التوزيع االجهزة الطبية‬
Supply, install, connect, test and put into operation
the distribution medical equipments panel boards
with isolated power system complete with isolating
transformer 3PH/1PH for Operation theaters or
3PH/3PH for otherwise spaces, 50HZ medical type,
Isolating screen, Remote control, sarien and
indication lamps at nursing counters and leakage
indication monitor unit LIM, all special requirements
for operation and medical rooms distribution boards,
interface with BMS, complete with all protective
devices, measuring instruments, isolating
transformers, terminal blocks, busbars, termination
of incoming and outgoing cables including cable
glands, labels, tags, components, accessories and all
related ancillary works as shown on drawings and
specified in specifications

12-1 UDB-OP1 Nr 1
12-2 UDB-OP2 Nr 1
12-3 UDB-OP3 Nr 1
12-4 UDB-OP4 Nr 1
12-5 UDB-OP-S Nr 1
12-6 UDB-ICU-TH1 Nr 1
12-7 UDB-ICU1-TH2 Nr 1
12-8 UDB-ICU2-TH2 Nr 1
12-9 UDB-ICU1-TH3 Nr 1
12-10 UDB-ICU2-TH3 Nr 1
12-11 UDB-NICU-S Nr 1
12-12 UDB-DIALYSIS 1 Nr 1
12-13 UDB-DIALYSIS 2 Nr 1
13 LIGHTING CONTROL PANELS:
‫لوحات التحكم فى االضاءة‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, connect, test and put into operation
lighting control panels for layout and all floors to
control all corridors and public areas, complete with
push buttons, indication lamps, conduits, control
cables, termination of cables, including cable glands,
labels, tags, components, accessories and all related
ancillary works as shown on drawings and specified
in specifications.

13-1 LCP-M1 Nr 1
13-2 LCP-M2 Nr 1
13-3 LCP-G1 Nr 1
13-4 LCP-G2 Nr 1
13-5 LCP-F1 Nr 1
13-6 LCP-F2 Nr 1
13-7 LCP-F3 Nr 1
13-8 LCP-S1 Nr 1
13-9 LCP-S2 Nr 1
13-10 LCP-S3 Nr 1
13-11 LCP-TH1 Nr 1
13-12 LCP-TH2 Nr 1
13-13 LCP-TH3 Nr 1
13-14 LCP-R Nr 1
14 UNINTERRUPTABLE POWER SUPPLY (UPS)
‫وحدات التغذية الغير متقطعة‬
Supply, install, connect, test and into operation
Complete Conventional UPS units transformerless
type including Protection, Processors, Batteries,
Inverters, Rectifiers, Static Bypass, Maintenance
Bypass, Filters “if needed” with Maximum 3% THD,
interface with BMS, DC Circuit Breakers and all
related accessories required for fixation as specified
and shown on drawings

14-1 UPS -- (60KVA), 30 min. Nr 1


14-2 UPS -- (30KVA), 30 min. Nr 5
14-3 UPS -- (25KVA), 30 min. Nr 1
14-4 UPS -- (15KVA), 30 min. Nr 6
14-5 UPS -- (30KVA), 10 min. Nr
14-6 UPS -- (40KVA), 10 min. Nr 1
14-7 UPS -- (200KVA), 10 min. Nr 1
15 (UPS) PROTECTION CIRCUIT BREAKERS
‫مفاتيح وحدات التغذية الغير متقطعة‬
Supply, install, connect, test and put into operation
UPS protection circuit breakers with enclosure,
complete with moulded case circuit breakers,
termination of incoming and outgoing cables
including cable glands, labels, tags, components.
accessories and all related ancillary works as shown
on drawings and specified in specifications.

15-1 C.B (50A) 18KA SC BC. Nr 0


UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
15-2 C.B (63A) 18KA SC BC. Nr 8
15-3 C.B (80A) 18KA SC BC. Nr 6
15-4 C.B (125A) 18KA SC BC. Nr 2
15-5 C.B (400A) 18KA SC BC. Nr 2
15-6 C.B (40A) 18KA SC BC. Nr 12
16 LOW VOLTAGE CABLES AND FEEDERS
‫كابالت الجهد المنخفض‬
MULTI CORE PVC/PVC INSULATED (0.6/1KV)
Supply, install, connect, test and put into operation
Multi core copper conductors 0.6 / 1 KV, XLPE
insulated and PVC sheathed low voltage cables,
complete with all terminations, cable supports, duct
bank, UPVC conduits, laying over cable ladders /
trays, saddles, cable glands, labels, tags, fittings,
16-1 accessories and all related ancillary works as shown
on drawings and specified in specifications.

16-1-1 (4Cx240) mm2 ML 170


16-1-2 (3Cx240+120) mm2 ML 244
16-1-3 (4Cx185) mm2 ML 150
16-1-4 (3Cx185+95) mm2 ML 230
16-1-5 (3Cx150+70) mm2 ML 160
16-1-6 (3Cx120+70) mm2 ML 750
16-1-7 (3Cx95+50) mm2 ML 670
16-1-8 (3Cx70+35) mm2 Fire Resistance Cables ML 35
16-1-9 (4Cx70) mm2 ML
16-1-10 (3Cx70+35) mm2 ML 331
16-1-11 (3Cx50+25) mm2 ML 385
16-1-12 (3Cx50+25) mm2 Fire Resistance Cables ML 30
16-1-13 (3Cx35+16) mm2 ML 469
16-1-14 (4Cx25) mm2 ML 1182
16-1-15 (4Cx25) mm2 Fire Resistance Cables ML
16-1-16 (4Cx16)) mm2 ML 1639
16-1-17 (4Cx16) mm2 Fire Resistance Cables ML 899
16-1-18 (4Cx10) mm2 ML 2657
16-1-19 (4Cx10) mm2 Fire Resistance Cables ML 505
16-1-20 (4Cx6) mm2 ML 299
16-1-21 (1Cx630) mm2 ML
16-1-22 (1Cx120) mm2 ML 414
16-1-23 (1Cx95) mm2 ML 380
16-1-24 (1Cx70) mm2 ML 1210
16-1-25 (1Cx50) mm2 ML 670
16-1-27 (1Cx35) mm2 ML 366
16-1-28 (1Cx25) mm2 ML 415
16-1-30 (1Cx16) mm2 ML 4364
16-1-32 (1Cx10) mm2 ML 2762
16-1-34 (1Cx6) mm2 ML 869
16-1-35 (4Cx6) mm2 Fire Resistance Cables ML 570
16-1-36 (4Cx4) mm2 ML 25
16-1-37 (4Cx4) mm2 Fire Resistance Cables ML 120
16-1-39 (1Cx4) mm2 ML 145
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
MULTI CORE XLPE/STA/PVC INSULATED (0.6/1KV)
16-2 for landscape

Supply, install, connect, test and put into operation


multi core aluminium conductors 0.6 / 1 KV, XLPE
insulated and STA sheathed low voltage cables,
direct buried in ground complete with all excavation
back filling work road crossing, cable trenches and all
requirement for establishing work as shown on
drawings and specified in specifications.

16-2-1 (4Cx16) mm2 AL/XLPE/STA/PVC ML 180


17 CABLE LADDERS
‫ساللم كابالت‬

Supply, install, test and put into operation heavy


duty hot dip galvanized cable ladders, complete with
all elbows, tees, reducers, suspension elements,
supports, connectors, earthing connector, fasteners,
studs, fire stopping material, warning signs, bolts,
nuts, washers, covers, accessories and all related
ancillary works as shown on drawings and specified
in specifications.

17.1 1000 x 150 mm ML 348


17.2 800 x 150 mm ML 500
17.3 600x150 ML 9
18 CABLE TRAYS
‫حوامل كابالت‬

Supply, install, test and put into operation


perforated heavy duty Electrostatic Painted after hot
dip galvanization Covered cable trays, complete with
all elbows, tees, reducers, suspension elements,
supports, connectors, earthing connector, fasteners,
studs, fire stopping material, warning signs, bolts,
nuts, washers, covers, accessories and all related
ancillary works as shown on drawings and specified
in specifications

18-1 1000 x 100 mm ML 286


18-2 800 x 100 mm ML 105
18-3 600 x 100 mm ML 31
18-4 400 x 100 mm ML 289
18-5 300 x 100 mm ML 183
18-6 200 x 100 mm ML 336
18-7 100 x 100 mm ML 568
19 CABLE TRUNKING
‫حوامل كابالت التيار الخفيف‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )

Supply, install, test and put into operation non


perforated heavy duty Electrostatic Painted after
hot dip galvanization Covered cable trunking multi -
compartment for low current systems, complete
with all elbows, tees, reducers, suspension elements,
supports, connectors, earthing connector, fasteners,
studs, fire stopping material, warning signs, bolts,
nuts, washers, covers, accessories and all related
ancillary works as shown on drawings and specified
in specifications.

19-1 150 x 100 mm ML 450


19-2 200 x 100 mm ML 1688
19-3 300 x 100 mm ML 69
19-4 400 x 100 mm ML 46
20 LIGHTING INSTALLATION
20-1 LIGHTING OUTLETS
‫مخرج االنارة‬

Supply, install, connect, test and put into operation


lighting outlets complete with all conduits, conduit
fittings, terminations, fittings, thermoplastic cables
to other outlets, to control modules, to lighting
switches or back to the panelboard, junction boxes,
pull boxes, cap connectors, components, accessories
and all related ancillary works as shown on drawings
and specified in specifications.

Lighting outlets by copper wire 3(1x3) sqmm in 20


20-1-1 Nr 4708
mm medium gauge pvc conduit

Lighting outlets by copper wire 3(1x3) sqmm in 20


20-1-2 Nr 35
mm medium gauge pvc conduit for EXH. FAN

Lighting outlets by copper wire 3(1x3) sqmm in 20


20-1-3 mm medium gauge pvc conduit for CEILING FAN Nr 0

Single Phase Lighting outlets by copper wire 3(1x3)


20-1-4 sqmm in 20 mm medium gauge pvc conduit for Nr 0
Operation Theater Pendant
20-2 LIGHTING FIXTURES
‫وحدات االنارة‬

Supply, install, connect, test and put into operation


indoor/outdoor lighting fixtures, complete with all
lamps,LED, drives, relays, terminations, components,
accessories and all related ancillary works as shown
on drawings and specified in specifications.(for type
description, refer to the lighting fixtures details)

20-2-1 F21 Nr 279


20-2-2 F13 Nr 461
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
20-2-3 D8 Nr 430
20-2-4 LF10 Nr 250
20-2-5 LF34 Nr 50
20-2-6 F11 Nr 477
20-2-7 LF45 Nr 12
20-2-8 F15 Nr 76
20-2-9 F76 Nr 324
20-2-10 D2 Nr 132
20-2-11 WII Nr 64
20-2-12 W5 Nr 243
20-2-13 F40 Nr 130
20-2-14 GI Nr 66
20-2-15 D11 Nr 71
20-2-16 F17 Nr 314
20-2-17 FCO Nr 6
20-2-18 LF02 Nr 178
20-2-19 WW4 Nr 0
20-2-20 F22 Nr 269
20-2-21 LF322 Nr 95
20-2-22 F14 Nr 92
20-2-23 F04 Nr 33
20-2-24 LF16 Nr 57
20-2-25 W6 Nr 4
20-2-26 F16 Nr 476
20-3 EXTERNAL LIGHTING FIXTURES
‫وحدات االنارة الخارجية‬

Supply, install, connect, test and put into operation


indoor/outdoor lighting fixtures, complete with all
lamps, capacitors, electronic ballasts, power factor
correction, earthing system, pit, base, terminations,
components, accessories and all related ancillary
works as shown on drawings and specified in
specifications.(for type description, refer to the
lighting fixtures details)

20-3-1 F6 Nr 8
20-3-2 PL Nr 14
20-3-3 PL2A Nr 2
20-3-4 F44 Nr 46
20-3-5 F5-1 Nr 0
20-3-6 L01 Nr 10
20-3-7 W1 Nr 0
20-3-8 W5 Nr 1
20-3-9 D3 Nr 20
20-3-10 W6 Nr 38
21 SMALL POWER SYSTEMS
21-1 Electrical Outlets:
‫انظمة القوى‬
‫مخارج القوى والبرايز‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )

Supply, install, connect and test and put into


operation electrical outlet, complete with all outlet
boxes, conduits, conduit fittings, cable trunking,
terminations, thermoplastic cables to other socket,
isolating switch, electrical outlet or back to
panelboard, junction boxes, pullboxes, cap
connectors, accessories and all related ancillary
works as shown on drawings and specified in
specifications.

Single Phase single/duplex outlet by copper wires


21-1-1 Nr 2488
3(1x3) mm2 in 20 mm medium gauge pvc conduit.

Single Phase single/duplex outlet by copper wires


21-1-2 3(1x3) mm2 in 20 mm medium gauge pvc conduit Nr 631
fed from UPS

Single Phase duplex outlet by copper wires 3(1x3)


21-1-3 mm2 in 20 mm medium gauge pvc conduit for floor Nr 101
box

Single Phase duplex outlet by copper wires 3(1x3)


21-1-4 mm2 in 20 mm medium gauge pvc conduit for floor Nr 108
box fed from UPS

Single Phase Electrical Power single/duplex outlet 20


21-1-5 AMP by copper wires 3(1x4) mm2 in 25 mm medium Nr 124
gauge pvc conduit

Single Phase Electrical Power single/duplex outlet 20


21-1-6 AMP by copper wires 3(1x4) mm2 in 25 mm medium Nr 85
gauge pvc conduit fed from UPS

Single Phase Electrical Power single/duplex outlet 32


21-1-7 AMP by copper wires 3(1x6) mm2 in 25 mm medium Nr 23
gauge pvc conduit fed from UPS for DATA RACKS

Single Phase Electrical outlet 20 AMP by copper


21-1-8 wires 3(1x4) mm2 in 25 mm medium gauge pvc Nr 2
conduit for FACP / Repeater

Single Phase Electrical outlet 20 AMP by copper


21-1-9 wires 3(1x4) mm2 in 25 mm medium gauge pvc Nr 3
conduit for GATE PARRIER

Single Phase Electrical outlet 16 AMP by copper


21-1-10 wires 3(1x3) mm2 in 20 mm medium gauge pvc Nr 14
conduit for ACP

Single Phase Electrical outlet 16 AMP by copper


21-1-11 wires 3(1x3) mm2 in 20 mm medium gauge pvc Nr 10
conduit for Time Attendance

Single Phase Electrical Power outlet 20 AMP by


21-1-12 copper wires 3(1x4) mm2 in 25 mm medium gauge Nr 327
pvc conduit for exh. Fan & F.C.U

Single Phase Electrical Power outlet 32 AMP by


21-1-13 copper wires 3(1x6) mm2 in 25 mm medium gauge Nr 3
pvc conduit for exh. Fan
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Single Phase Electrical Power outlet 40 AMP by
21-1-14 copper wires 3(1x10) mm2 in 32 mm medium gauge Nr 8
pvc conduit for AC

Wall sockets Consule all outlets by copper wires


21-1-15 Nr 42
3(1x4) mm2 in 20 mm medium gauge pvc conduit

BHU-02 all outlets by copper wires 3(1x6) mm2 in 20


21-1-16 mm medium gauge pvc conduit Nr 42

BHU-03 all outlets by copper wires 3(1x4) mm2 in 25


21-1-17 Nr 159
mm medium gauge pvc conduit
Single Phase Electrical outlet 16 AMP by copper
21-1-18 wires 3(1x3) mm2 in 20 mm medium gauge pvc Nr 10
conduit for Air Curtain

Single Phase Electrical Power outlet 20 AMP by


21-1-19 copper wires 3(1x4) mm2 in 25 mm medium gauge Nr 50
pvc conduit for M.F.S.D

Single Phase Electrical Power outlet 25 AMP by


21-1-20 copper wires 3(1x4) mm2 in 25 mm medium gauge Nr 10
pvc conduit for Operation Theater Pendant

Single Phase Electrical outlet 16 AMP by copper


21-1-21 wires 3(1x3) mm2 in 20 mm medium gauge pvc Nr 29
conduit for anti pacterial single / duplex socket

Single Phase Electrical outlet 20 AMP by copper


21-1-22 wires 3(1x4) mm2 in 25 mm medium gauge pvc Nr 37
conduit for anti pacterial duplex power socket

Single Phase Electrical outlet 32 AMP by copper


21-1-23 wires 3(1x6) mm2 in 25 mm medium gauge pvc Nr 4
conduit for anti pacterial single power socket

Single Phase Electrical outlet 32 AMP by copper


21-1-24 wires 3(1x6) mm2 in 25 mm medium gauge pvc Nr 5
conduit for sterlization machine

Single Phase Electrical Power outlet 20 AMP by


copper wires 3(1x4) mm2 in 25 mm medium gauge
21-1-25 Nr 4
pvc conduit for clinic connected to disconnect
switch 26A

Wall sockets Consule all outlets by copper wires


21-1-27 3(1x4) mm2 in 20 mm medium gauge pvc 42
conduit.FOR UPS
21-2 WIRING DEVICES AND ACCESSORIES
‫وحدات البرايز والقوى‬

Supply, install, connect, test and put into operation


sockets, complete with all fittings, terminations,
accessories and all related ancillary works as shown
on drawings and specified in specifications.

21-2-1 16 AMP, 220 Volt, single socket wall mounted Nr 1343


21-2-2 16 AMP, 220 Volt, duplex socket ceiling mounted Nr 40
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
16 AMP, 220 Volt, single socket wall mounted,
21-2-3 Weather-Proof Type Nr 531
21-2-4 16 AMP, 220 Volt, duplex socket wall mounted Nr 578
16 AMP, 220 Volt, single socket wall mounted fed
21-2-5 Nr 47
from UPS

21-2-6 16 AMP, 220 Volt, single socket ceiling mounted fed


from UPS Nr 64

16 AMP, 220 Volt, duplex socket wall mounted fed


21-2-7 Nr 520
from UPS
16 AMP, 220 Volt, single socket wall mounted fed
21-2-8 from UPS clean room anti pacterial type Nr 2

16 AMP, 220 Volt, duplex socket wall mounted clean


21-2-9 Nr 15
room anti pacterial type
16 AMP, 220 Volt, duplex socket wall mounted fed
21-2-10 from UPS clean room anti pacterial type Nr 12

20 AMP, 220 Volt, single power socket wall mounted


21-2-11 fed from UPS Nr 62

20 AMP, 220 Volt, single power socket floor


21-2-12 Nr 23
mounted fed from UPS

21-2-13 20 AMP, 220 Volt, single power socket wall mounted Nr 83

20 AMP, 220 Volt, single power socket wall


21-2-14 Nr 41
mounted, Weather-Proof Type

21-2-15 20 AMP, 220 Volt, single power socket wall Nr 6


mounted, Weather-Proof Type fed from UPS

21-2-16 32 AMP, 220 Volt, single power industral socket wall Nr 23


mounted fed from UPS
63 AMP, 220 Volt, single power industral socket wall
21-2-17 Nr 4
mounted fed from UPS

21-2-18 32 AMP, 220 Volt, single power socket wall mounted Nr 1


fed from UPS

21-2-19 32 AMP, 220 Volt, single power socket wall mounted Nr 6

20 AMP, 220 Volt, duplex power socket wall


21-2-20 mounted fed from UPS clean room anti pacterial Nr 37
type

21-2-21 32 AMP, 220 Volt, single power socket wall mounted Nr 5


fed from UPS clean room anti pacterial type

32 AMP, 380 Volt, single power industral socket


21-2-22 socket wall mounted. Nr 3

220V, WALL MOUNTED ELECTRICAL OUTLET FED


21-2-23 Nr 53
THROUGH UPS
FLOOR BOX CONTAINS:1 NO. OF 16A DUPLEX
21-2-24 SOCKET,1 NO. OF 16A DUPLEX UPS SOCKET 1 NO. OF Nr 17
RJ45 DATA SOCKET.
WALL MOUNTED FLEXIBLE OUTLET FOR CCTV
21-2-25 Nr 2
CAMERA FED THROUGH UPS
380V, 32A WALL MOUNTED SINGLE SOCKET
21-2-26 WEATHER PROOF TYPE Nr 4
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
ELECTRIC CEILING OUTLET TYPE 2 CONTAINS (2x20A
UPS POWER SINGLE SOCKET OUTLETS 1RJ45 SINGLE
21-2-27 Nr 4
DATA SOCKET, CODE BLUE CALL, STAFF EMERGENCY
ASSIST )

ELECTRIC CEILING OUTLET TYPE 1 CONTAINS( 2x20A


21-2-28 UPS POWER SINGLE SOCKET OUTLETS) Nr 4

ELECTRIC WALL OUTLET TYPE 1 CONTAINS (2x20A


21-2-29 UPS POWER SINGLE SOCKET OUTLETS, 2xRJ45 Nr 1
SINGLE DATA SOCKET OUTLET )
ELECTRIC CEILING OUTLET TYPE 2 CONTAINS ( 2x20A
21-2-30 UPS POWER SINGLE SOCKET OUTLETS Nr 3

ELECTRIC CEILING OUTLET TYPE 2 CONTAINS (4x20A


21-2-31 Nr 5
UPS POWER SINGLE SOCKET OUTLETS
21-3 CIRCUIT AND MOTOR DISCONNECTORS
‫وحدات مفاتيح الفصل‬

Supply, install, connect, test and put into operation


disconnectors, complete with all fittings,
terminations, accessories and all related ancillary
works as shown on drawings and specified in
specifications.
1 PHASE ISOLATORS

‫وحدات مفاتيح احادية الطور‬


21-3-1 I.S, 1PH, 25A Nr 4
21-3-2 I.S, 1PH, 20 A (W.P) Nr 432
21-3-3 I.S, 1PH, 25 A (W.P) Nr 16
21-3-4 I.S, 1PH, 32 A (W.P) Nr 34
21-3-5 I.S, 1PH, 40A (W.P) Nr 43
3 PHASE ISOLATORS
‫وحدات مفاتيح ثالثية الطور‬
21-3-6 I.S, 3PH, 32A MCCB WITH ENCLOSURE Nr 1
21-3-7 I.S, 3PH, 100 A Nr 1
21-3-8 I.S, 3PH, 125 A Nr 1
21-3-9 I.S, 3PH, 250A Nr 2
21-3-10 I.S, 3PH, 25 A (W.P) Nr 86
21-3-10 I.S, 3PH, 32 A (W.P) Nr 44
21-3-11 I.S, 3PH, 40 A (W.P) Nr 39
21-3-13 I.S, 3PH, 50 A (W.P) Nr 7
21-3-14 I.S, 3PH, 63 A (W.P) Nr 34
21-3-15 I.S, 3PH, 80 A (W.P) Nr 15
21-3-16 I.S, 3PH, 100 A (W.P) Nr 5
21-3-17 I.S, 3PH, 125 A (W.P) Nr 5
21-3-18 I.S, 3PH, 200 A (W.P) Nr 6
21-3-19 I.S, 3PH, 250 A (W.P) Nr 1
21-3-20 I.S, 3PH, 300 A (W.P) Nr 8
21-3-21 I.S, 3PH, 1250 A (W.P) Nr 3
I.S, 3PH, 1200A MCCB MAGNETIC TRIP ONLY WITH
21-3-22 ENCLOSURE Nr 1
6 POLES / 3 PHASE ISOLATORS
21-3-23 I.S, 3PH, 25 A (W.P) 6 pole Nr 14
21-3-24 I.S, 3PH, 32 A (W.P) 6 pole Nr 18
21-3-25 I.S, 3PH, 40 A (W.P) 6 pole Nr 10
21-3-26 I.S, 3PH, 63 A (W.P) 6 pole Nr 12
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
21-3-27 I.S, 3PH, 80 A (W.P) 6 pole Nr 5
21-3-28 I.S, 3PH, 100 A (W.P) 6 pole Nr 4
21-3-29 I.S, 3PH, 200 A (W.P) 6 pole Nr 2
21-3-30 I.S, 1PH, 20A Nr 6
21-3-31 I.S, 1PH,40A Nr 7
21-3-32 I.S, 1PH,63A Nr
21-3-33 I.S, 3PH, 20 A (W.P) Nr 66
21-3-34 I.S, 3PH, 150 A (W.P) Nr 7
21-3-35 I.S, 3PH, 1000 A (W.P) Nr 3
21-3-36 I.S, 3PH, 150 A Nr 1
21-3-37 I.S, 3PH, 400 A (W.P) Nr 2
21-3-38 I.S, 3PH, 500 A (W.P) Nr 2
21-3-39 I.S, 3PH, 630 A (W.P) Nr 1
21-4 Floor / DESK Boxes:
‫العلب االرضية‬
Supply, install, connect, test and put into operation
Floor Boxes, complete with all normal sockets, UPS
sockets data RJ45 sockets, Telephone RJ11 sockets,
fittings, terminations, thermoplastic cables to other
floor box or back to panel board, accessories and all
related ancillary works as shown on drawings and
specified in specifications.

Floor / DESK box with One 220v-16A duplex socket,


One 220v-16A UPS duplex socket, One data RJ45
21-4-1 socket and One telephone RJ45 socket complete Nr 53
with sockets and accessories

Floor / DESK box with One 220v-16A duplex socket,


One 220v-16A UPS duplex socket, One data RJ45
socket , ONE P.O.S socket and One telephone RJ45
21-4-2 socket complete with sockets and accessories Nr 15

Floor / DESK box with One 220v-16A duplex socket,


One 220v-16A UPS duplex socket, One data RJ45
socket and One telephone RJ45 socket, One USB
21-4-3 socket , One HDMIsocket complete with sockets and Nr 4
accessories

Floor / DESK box with One 220v-16A duplex socket,


One 220v-16A UPS duplex socket, One data RJ45
21-4-4 socket complete with sockets and accessories Nr 44

Floor / DESK box with One 220v-16A UPS duplex


21-4-5 socket, One data RJ45 socket complete with sockets
and accessories Nr 3

Floor / DESK box with One 220v-16A UPS duplex


socket, One data RJ45 socket and One telephone
21-4-6 RJ45 socket complete with sockets and accessories Nr 4

21-5 Bed Head Units:


‫وحدات فوق السرير‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
upply, install, connect, test and put into operation
Wall Bed Head Units, complete with all lighting
fixtures, normal sockets, data RJ45 sockets,
Telephone RJ11 sockets, terminations, thermoplastic
cables to other bed head unit or back to panel
board, accessories and all related ancillary
works as shown on drawings and specified in
specifications.

Horizontal wall socket consule, contains 4X16A single


21-5-1 shuko socket,
1RJ45 data socket Nr 42

Bed Head Unit-02: 2X18W Direct Light, 1X36W


Indirect Light, 10A-2gang switch for direct light
control, 10A-1gang switch for Indirect Light control,
3X16A single shuko socket, 1X20A power shuko
21-5-2 socket, 1RJ45 tel socket, 1RJ45 data socket, nurse Nr 42
call hand set outlet, and 32A shuko power socket for
mobile X-RAY.

Bed Head Unit-03: 2X18W Direct Light, 1X36W


Indirect Light, 10A-2gang switch for direct light
control, 10A-1gang switch for Indirect Light control,
21-5-3 3X16A single shuko socket, 1X20A power shuko
socket, 1RJ45 tel socket, 1RJ45 data socket, nurse Nr 158
call hand set outlet.

Horizontal wall socket consule, contains 2X20A UPS


21-5-4 power single socket, 2xRJ45 data socket )
Nr 1

Horizontal wall socket consule, contains 2X20A UPS


power single socket, 1xRJ45 data socket ,CODE BLUE
21-5-5 CALL, STAFF EMERGENCY ASSIST ) Nr 4

21-6 Lighting Switches:


‫مفاتح االنارة‬
Supply, install, connect, test and put into operation
lighting switch complete with the switch fixture and
all outlet boxes, conduits, conduit fittings,
terminations, thermoplastic cables to nearest
lighting fixture, junction boxes, pull boxes, cap
connectors, accessories and all related ancillary
works as shown on drawings and specified in
specifications.

21-6-1 One way, one gang switch 10A, 220v Nr 1100


21-6-2 One way, two gang switch 10A, 220v Nr 106
21-6-3 Two way, one gang switch 10A, 220V Nr 34
21-6-4 Two way, two gang switch 10A, 220V Nr 57
One way, one gang switch 10A, 220V- Cleanroom
21-6-5 Antipacterial Type Nr 20
One way, two gang switch 10A, 220V- Cleanroom
21-6-6 Antipacterial Type Nr 80
Two way, one gang switch 10A, 220V- Cleanroom
21-6-7 Antipacterial Type Nr 8
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Two way, two gang switch 10A, 220V- Cleanroom
21-6-8 Antipacterial Type Nr 34
One way, one gang switch 10A, 220v , Weather-
21-6-9 Proof Type Nr 30
One way, two gang switch 10A, 220v , Weather-
21-6-10 Proof Type Nr 2
Two way, two gang switch 10A, 220V , Weather-
21-6-11 Proof Type Nr 6
22 EARTHING SYSTEMS
22-1 Medium Voltage Earthing System
‫نظام االرضى‬
‫نظام تاريض الجهد المتوسط‬
Supply, install, connect and test earthing systems for
electrical rooms M.V earthing systems. The item
shall includes excavation, wall backfilling and all
necessary accessories and ancillary works including
and not limited to the following according to
drawings, spec. & BS 6651 regulations including:
3:6m copper clad steel earthing rod
Bare copper conductor
Earth pit
Test links
Earth bars
Earthing conductor continuity connection
Cable to cable thermite connection
Cable to rebar thermite connection
And all required materials to complete the earth
networks as per drawings and specifications.
- Earth resistance shall not exceed 5 ohm.

22-1-1 MV Earthing System for MVSG LS 1


22-1-2 MV Earthing System for Transformers room LS 1
22-2 Low Voltage and Pump Room Earthing System
‫نظام تاريض الجهد المنخفض وغرفة الطلمبات‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, connect and test earthing systems for
electrical rooms L.V earthing systems and pump
room. The item shall includes excavation, wall
backfilling and all necessary accessories and ancillary
works including and not limited to the following
according to drawings, spec. & BS 6651 regulations
including:
3:6m copper clad steel earthing rod
Bare copper conductor
Earth pit
Test links
Earth bars
Earthing conductor continuity connection
Cable to cable thermite connection
Cable to rebar thermite connection
And all required materials to complete the earth
networks as per drawings and specifications.
- Earth resistance shall not exceed 2 ohms.

22-2-1 L.V Erathing System LS 1


22-2-2 Generators Erathing System LS 1
22-2-3 Pump Room Erathing System LS 1
22-3 Structure Earthing System
‫نظام تاريض المبنى‬
Supply, install, connect and test earthing systems for
building structure. The item shall includes
excavation, wall backfilling and all necessary
accessories and ancillary works including and not
limited to the following according to drawings, spec.
& BS 6651 regulations including:
3:6m copper clad steel earthing rod
Bare copper conductor
Earth pits
Test links
Earth bars
Earthing conductor continuity connection
Cable to cable thermite connection
Cable to rebar thermite connection
And all required materials to complete the earth
networks as per drawings and specifications.
- Earth resistance shall not exceed 3 ohms.

22-3-1 Structure Erathing System LS 1


22-4. Medical Equiments Earthing System:
‫نظام تاريض االجهزة الطبية‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, connect and test earthing systems for
medical equipments earthing systems covers NICU,
Operation rooms, ICU and any medical equipments.
The item shall includes excavation, wall backfilling
and all necessary accessories and ancillary works
including and not limited to the following according
to drawings, spec. & BS regulations including:
3:6m copper clad steel earthing rod
Bare copper conductor
Earth pit
Test links
Earth bars
Earthing conductor continuity connection
Cable to cable thermite connection
Cable to rebar thermite connection
And all required materials to complete the earth
networks as per drawings and specifications.
- Earth resistance shall not exceed 0.2 ohms.

22-4-1 Medical Equiments Earthing System LS 1


22-5 Clean Earthing System
Supply, install, connect and test earthing systems for
Low Current Equipments with earthing cables to test
links, U.P.S, control room, IT rooms & all low current
and telecom equipments. The item shall includes
excavation, wall backfilling and all necessary
accessories and ancillary works including and not
limited to the following according to drawings, spec.
& BS 6651 regulations including:
3:6m copper clad steel earthing rod
Bare copper conductor
Earth pit
Test links
Earth bars
Earthing conductor continuity connection
Cable to cable thermite connection
Cable to rebar thermite connection
And all required materials to complete the earth
networks as per drawings and specifications.
- Earth resistance shall not exceed 0.5 ohms.

22-5-1 Clean Earthing System LS 1


23 LIGHTNING SYSTEMS
‫نظام مانعة الصواعق‬
23-1 Lightning protection system
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, connect, test and put into operation
complete lightning protection system, including
earth pits, test links, earth bars, earth rods, welding
joints, 25*3mm copper tape, down conductors, air
terminals, earthing pits, rods, ...etc , and all
accessories and related ancillary works as shown on
drawings and specified in specifications.
- Earth resistance shall not exceed 10 ohms.

Lightning protection system reference to IEC-62305


23-1-1 LS 1
24 DC/DC CENTRAL BATTERY SYSTEM
‫نظام البطاريات المركزية‬
Supply, install, connect, test and into operation
Complete central battery systems DC type including
Protection devices, Battery and electronic cabinet,
1.5 hours duration battery, measuring instruments,
Processors, load break switches, Batteries, Inverters,
Rectifiers, Main Controller, Communication
Module/Gateway, All Control Cables, Connection to
Building Management System, All Lines/Units
addressable Interface Modules, Battery Interface
Modules, Presence Of Mains Input, Sensing
switching signals from knx switch actuator/local
switch to CBS switching module, switching modules,
built-in protection (Fuses) and monitoring devices,
terminal blocks, busbars, termination of incoming
and outgoing cables including cable glands, labels,
tags, components, Monitoring of addressable Exit
signs and life safty lighting fixtures (If any), and all
related accessories required for fixation as specified
and shown on drawings

24-1 Central Panel Nr 1


24-2 Slave Panel Nr 10
25 DC/DC CENTRAL BATTERY SYSTEM OUTLETS
‫مخارج البطاريات المركزية‬
Supply, install, connect, test and put into operation
Central Battaries lighting outlets complete with all
conduits, conduit fittings, terminations, fittings,fire
resistance cables, addressing control casbles,
junction boxes, pull boxes, cap connectors,
components, accessories and all related ancillary
works as shown on drawings and specified in
specifications.

Lighting outlets by copper wire 3(1x3) sqmm


25-1 CU/MICA/LSHF in 20 mm medium gauge pvc conduit
for Safety Light - Ceiling Mounted Nr 242
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Lighting outlets by copper wire 3(1x3) sqmm
25-2 CU/MICA/LSHF in 20 mm medium gauge pvc conduit
for Safety Light - Wall Mounted Nr 612

Lighting outlets by copper wire 3(1x3) sqmm


25-3 CU/MICA/LSHF in 20 mm medium gauge pvc conduit
for Exit Sign - Ceiling Mounted Nr 75

Lighting outlets by copper wire 3(1x3) sqmm


25-4 CU/MICA/LSHF in 20 mm medium gauge pvc conduit
for Exit Sign - Wall Mounted Nr 124

26 DC/DC CENTRAL BATTERY SYSTEM FIXTURE


‫وحدات البطاريات المركزية‬
Supply, install, connect, test and put into operation
Central Battaries
lighting fixtures, complete with all LED, drives,
addressing modules,
indication led lamps,, terminations, components,
accessories and all
related ancillary works as shown on drawings and
specified in
specifications

26-1 Safety Light - Ceiling Mounted (SF-C) Nr 103


26-2 Safety Light - Wall Mounted Nr 568
26-3 Exit Sign - Ceiling Mounted (CEX) Nr 75
26-4 Exit Sign - Wall Mounted (WEX) Nr 124
26-5 Safety Light - (SF-CW1) Nr 41
Safety Light - Ceiling Mounted (Anti Pecterial) (SF-
26-6 CW3) Nr 98

26-7 SF-WW1 Nr 81
26-8 SF-W Nr 166
26-9 SF-WW3 Nr 182
26-10 SF-WW2 Nr 182
26-11 SF-WW4 Nr 2
27 FIRE ALARM SYSTEM
27-1 FIRE ALARM CONTROL PANEL
‫نظام انذار الحريق‬
‫لوحة انذار الحريق‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, testing, commissioning and put into
operation expandable Main fire alarm intelligent
addressable control panel class A with voice alarm
and amplifiers complete with PC, Event Dot matrix
printer, autodialer, all control modules, all monitor
modules, relays, wiring, printer, power supplies, fire
pumps monitoring, water storage tank monitoring
(low level and high level) and alarm, fire fighting
tamper switches, emergency generator monitoring
and alarm, interface units with HVAC, MDBs, Fire
fighting, elevators, FM200 systems, Public address
system, Fire zone doors with built in SLA (Sealed
Lead Acid) battery and battery charger, all nterface
with other trades, cabling, conduits etc...., and all
necessary ancillary works and accessories required
For complete installation as per drawings and specs

27-1-1 FACP -- 10 loops expandable to 12 Loop Nr 2


27-1-2 FARP -- Repeater panel Nr 2
27-2 FIRE ALARM OUTLETS
‫مخارج انذار الحريق‬
Supply, install, connect, test and put into operation
alarm outlets complete with hot dip galvanized steel
conduits 20 mm dia. for exposed installation,
medium gauge fire retandant pvc conduits 20 mm
dia. for embedded installation, conduit fittings, back
boxes, junction box, shielding 105C degree
2x1.5sqmm copper conductor fire resistance wiring,
components, accessories and all related ancillary
works as shown on drawings and specified in
specifications.

Intelligent Addressable fire alarm detector outlet


27-2-1 Nr 2175
Intelligent Addressable fire alarm call point outlet
27-2-2 Nr 65
27-2-3 Intelligent Addressable Fire alarm bell outlet Nr 65
Intelligent Addressable Fire alarm bell outlet DC
27-2-4 outlet Nr 65
27-2-5 Fire Man Telephone outlet Nr 57
27-3 FIRE ALARM DEVICES
‫وحدات انذار الحريق‬
Supply, install, testing, commissioning and put into
operation complete with all terminations,
components, accessories and all related ancillary
works as shown on drawings and specified in
specifications.

Intelligent Addressable fire alarm smoke detector


27-3-1 ceiling mounted Nr 1022
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Intelligent Addressable fire alarm smoke detector
27-3-2 ceiling mounted with Sounder Base Nr 31
Intelligent Addressable fire alarm smoke detector
27-3-3 ceiling mounted above
false ceiling Nr 986

Intelligent Addressable fire alarm combind (smoke-


27-3-4 heat) detector ceiling
mounted Nr 42

Intelligent Addressable fire alarm smoke detector


27-3-5 wall mounted Nr 42
Intelligent Addressable fire alarm heat detector
27-3-6 ceiling mounted Nr 55
Intelligent Addressable fire alarm call point wall
27-3-7 mounted Nr 65
Intelligent Addressable Fire alarm Bell wall mounted
27-3-8 Nr 59
Intelligent Addressable Fire alarm Bell wall mounted
27-3-9 weather proof and with strob light Nr 6
Intelligent Addressable Fire alarm Control Module
27-3-10 Nr 53
Intelligent Addressable Fire alarm Monitor Module
27-3-11 Nr 80
27-3-12 Fault line isolator Nr 130
27-3-13 Fire Man Telephone Nr 24
Power Supplies for DC Feeders of CM / MM / Bells
27-3-14 ……etc Nr 1
27-4 iP-PABX

Supply, Install, test, connect and put into operation


IP-PABX complete with All equipments needed,
power supplies, charger, back up battery,
terminations, fittings, components, accessories as
per drawings, specification and standard

27-4-1 IP-PABX with (Internal lines 800 / 50lines) Nr 1


28 IP SYSTEM
OVER IP TELEPHONE, DATA AND CCTV
IP TELEPHONE, DATA AND CCTV
28-1 Main DATA RACK
‫نظام المعلومات‬
‫راك المعلومات الرئيسي‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, testing, commissioning and put into
operation Main Data Rack (Rack Able to serve all
Data Racks as per riser Diagram) complete with
Passive & Active components, Core / Ethernet
switches, patch panels, PDUs,, All equipments
needed , cable organizers, metal enclosures,
Ethernet switches, patch panels, power supplies,
Servers as required and specified by owner, patch
cords, terminations, fittings, components,
workstation, accessories and all necessary
accessories to finish works as
per drawings, specification and standard

28-1-1 MAIN DATA RACK Nr 1


28-2 FIBER OPTICS CABLES
Supply, install, connect, test and put into operation
S.M.F.O or M.M.F.O
(Single Multi Mode Fiber Optics Cable) as
recommendation of the supplier, complete with
splicing boxes, terminations, routing, risers, conduits
and all necessary accessories as specified and as
shown in the drawings.

28-2-1 24 cores, color-coded optical fiber cable ML 0


28-2-2 16 cores, color-coded optical fiber cable ML 759
28-2-3 12 cores, color-coded optical fiber cable ML 297
28-2-4 8 cores, color-coded optical fiber cable ML 638
28-2-5 4 cores, color-coded optical fiber cable ML 352
28-3 DATA RACK
‫راك المعلومات‬
Supply, install, testing, commissioning and put into
operation Data Rack complete with Passive & Active
components, Edge/Ethernet switches, patch panels,
PDUs, and all equipments needed , metal enclosures,
power supplies, cable organizers, Servers as required
and specified by owner, patch cords, terminations,
fittings, components, workstation, accessories and
all necessary accessories to finish works as per
drawings, specification and standard

28-3-1 DR-M1 Nr 0
28-3-2 DR-M2 Nr 0
28-3-3 DR-CCTV-M1 Nr 0
28-3-4 DR-CCTV-M2 Nr 0
28-3-5 DR-G1 Nr 1
28-3-6 DR-G2 Nr 1
28-3-7 DR-CCTV-G1 Nr 1
28-3-8 DR-CCTV-G2 Nr 1
28-3-9 DR-F1 Nr 1
28-3-10 DR-F2 Nr 1
28-3-11 DR-CCTV-F1 Nr 1
28-3-12 DR-CCTV-F2 Nr 1
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
28-3-13 DR-S1 Nr 1
28-3-14 DR-S2 Nr 1
28-3-15 DR-CCTV-S1 Nr 1
28-3-16 DR-CCTV-S2 Nr 1
28-3-17 DR-TH1 Nr 1
28-3-18 DR-TH2 Nr 1
28-3-19 DR-CCTV-TH1 Nr 1
28-3-20 DR-CCTV-TH2 Nr 1
28-3-21 DR-R2 Nr 1
28-3-22 DR-CCTV-R2 Nr 1
28-3-23 DR-FO1 Nr 1
28-3-24 DR-FO2 Nr 1
28-3-25 DR-CCTV-FO1 Nr 1
28-3-26 DR-CCTV-FO2 Nr 1
28-4 IP TELEPHONE, DATA OUTLETS
‫مخارج المعلومات والهاتف‬
Supply, install, testing and put into operation Data
outlet complete with conduits, CAT-06 cable in 20
mm PVC conduit, back box with junction box and all
necessary accessories to finish works as per
drawings, specification and standard

TEL / Data outlets using CAT-06 Cable medium


28-4-1 gauge pvc 20 mm conduit Nr 842
TEL / Data outlets using CAT-06 Cable medium gauge
28-4-2 pvc 20 mm conduit for Wall sockets Consule &
B.H.U. Nr 408

Data outlets using CAT-06 Cable medium gauge pvc


28-4-3 20 mm conduit for Operation Theater Pendant
Nr 3

Data outlets using CAT-06 Cable medium gauge pvc


28-4-4 20 mm conduit for W.A.P Nr 88
TEL / Data outlets using CAT-06 Cable medium
28-4-5 gauge pvc 20 mm conduit for floor box. Nr 162
Data outlets using CAT-06 Cable medium gauge pvc
28-4-6 20 mm conduit for projector. Nr 3
Data outlets using CAT-06 Cable medium gauge pvc
28-4-7 20 mm conduit for P.O.S at Floor Box .
Nr 1

Data outlets using CAT-06 Cable medium gauge pvc


28-4-8 20 mm conduit for ACP , Time Attendance
Nr 0

28-5 IP TELEPHONE, DATA FIXTURES


‫وحدات المعلومات والهاتف‬
Supply, install, testing ,commissioning and put into
operation Data Sockets type RJ-45 with face plate
connecting block, labeling complet with all
terminations, fittings, components, accessories and
all necessary accessories to finish works as per
drawings, specification and standard

28-5-1 Single Wall mounted RJ-45 socket. Nr 844


UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Wireless Access Point (WAP) ceiling / wall mounted
28-5-2 POE type. Nr 88
28-5-3 WALL / DESK IP TEL SET Nr 506
OVER IP CLOSED CIRCUIT TELEVISION SYSTEM (IP-
29 CCTV)
29-1 IP - CCTV MAIN EQUIPMENTS
‫نظام المراقبة التليفزيونية‬
‫راك الدوائر التلفزيونية المغلقة الرئيسية‬
Supply, install, testing, commissioning and put into
operation CCTV system complete with CCTV
Workstation, Termination, and all necessary
accessories to finish works as per drawings,
specification and standard The system Includes :-
9 no.32 Channels NVR with Record capacity 30
Days / 24 Hours at 25 fps per camera
4 no. Control Keypads with Joysticks
9 no. 50" LCD monitors
No. of 2 Management PCs With License Software
29-1-1 Power supplies LS 1
Interfaces with all Security systems
CCTV Console
CCTV RACK at monitoring room

29-2 IP - CCTV OUTLETS


‫مخارج الكاميرات التلفزيونية‬
Supply, install, connect and test and put into
operation CCTV outlet, complete with Cat-06 cables,
outlet boxes, conduits, conduit fittings, cable
trunking, terminations, junction boxes, pullboxes,
accessories and all related ancillary works as shown
on drawings and specified in
specifications.

Fixed CCTV outlet using Cat-06 cable inside 20mm


29-2-1 medium gauge PVC
Conduit Nr 277

PTZ CCTV outlet using Cat-06 cable with control


29-2-2 cable inside 20mm medium gauge PVC Conduit
Nr 2

29-3 IP - CCTV FIXTURES


‫وحدات الكاميرات التلفزيونية‬
Supply, install, testing, commissioning and put into
operation IP CCTV Cameras of POE Type, complete
with all terminations, components, accessories and
all related ancillary works as shown on drawings and
specified in specifications.

Ceiling Mounted Fixed Indoor DOME TYPE IP Camera


29-3-1 - POE Type. Nr 248
Wall Mounted Fixed Indoor IP Camera -IP65 - POE
29-3-2 Type. Nr 0
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Wall Mounted Fixed outdoor Camera - IP65 - POE
29-3-3 Type. Nr 30
Wall Mounted PTZ outdoor Camera - IP65 - POE
29-3-4 Type. Nr 2
Observation worstation complete with 4 No. of 24``
LCD Monitors for ICU with Encoders, power supplies,
components, accessories and all related ancillary
29-3-5 works as shown on drawings and specified in Nr 0
specifications.

30 SMATV SYSTEM
‫نظام التلفزيون‬
30-1 SMATV HEAD END UNIT EQUIPMENTS
Supply, install, testing, commissioning and put into
operation SMATV system complete with SMATV
Workstation, Termination, PVC conduit, co-axial
cable to achieve 75 db at least at outlets and all
necessary accessories to finish works as per
drawings, specification and standard The system
Includes :-
VHF antenna
UHF antenna
FM antenna
UHF/VHF booster amplifier as per spec's
1 No.1.8 meter parabolic satellite dish with quatro
30-1-1 LNB LS 1
No. Amplifiers as required by supplier
with all required cables, accessories for connecting
between the system for complete installation and
proper operation as shown on drawings and
specified in specifications.

30-2 SMATV OUTLETS


‫مخارج التلفزيون‬
Supply, install, connect and test and put into
operation SMATV outlet, complete with RG11 coaxial
cables for virtical risers routing and RG6 coaxial
cables for horizontal routing, outlet boxes, conduits,
conduit fittings, cable trunking, terminations,
junction boxes, pullboxes, accessories and all related
ancillary works as shown on drawings and specified
in specifications.

Wall mounted TV outlet 75 ohm coaxial cable in 20


30-2-1 mm medium gauge pvc conduit. Nr 164
Ceiling mounted TV outlet 75 ohm coaxial cable in 20
30-2-2 mm medium gauge pvc conduit. Nr 39
RG11 coaxial cables for virtical risers routing in 20
30-2-3 mm medium gauge pvc conduit / Cable trunk riser.
Mt 1305

30-3 SMATV FIXTURES


‫وحدات مخارج التلفزيون‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, testing, commissioning and put into
operation complete with all terminations,
components, accessories and all related ancillary
works as shown on drawings and specified in
specifications.

30-3-1 Passive multi switch 9/6 Nr 0


30-3-2 Passive multi switch 9/9 Nr 3
30-3-3 Passive multi switch 9/16 Nr 6
30-3-4 Passive multi switch 9/32 Nr 4
30-3-5 Wall mounted TV socket Nr 164
30-3-6 CEILING mounted TV socket Nr 39
31 PUBLIC ADDRESS SYSTEM
MAIN PUBLIC ADDRESS SYSTEM RACK AND
31-1 COMPONENTS
‫نظام الصوتيات‬
‫راك الصوتيات الرئيسي‬
Supply, install, testing, commissioning and put into
operation Public Address system complete with
Sound system Metal racks with lockable glass door
ventilation fans, Digital pre-recorded massage,
Graphic equalizer, Multi CD player, AM/FM tuner
with antenna, zone selectors, zone indicators, input
Mics, 16 zones call station unit, interface unit with
Fire alarm control panel, interface units with A/V
31-1-1 racks, All other sound system racks, cabling, conduits LS 1
etc...., and all necessary ancillary works and
accessories required for complete installation as per
drawings and specs.

31-2 AMPLIFIERS AND MATRIX


‫مكبرات الصوت ومصفوفة التحكم‬
Supply, install, testing, commissioning and put into
operation Sound system Digital Main controller 8
31-2-1 input/ 16 output with necessary accessories Nr 1

31-2-2 Power amplifier 500W Nr 0


31-2-3 Power amplifier 300W Nr 7
31-2-4 Power amplifier 240W Nr 4
31-2-5 Power amplifier 360W Nr 5
PUBLIC ADDRESS OUTLETS
‫مخارج السماعات‬
Supply, install, connect, test and put into operation
public address outlets complete with all conduits,
conduit fittings, terminations, fittings, cabling, to
volume controls, junction boxes, pull boxes,
components, accessories and all related ancillary
works as shown on drawings and specified in
specifications.

Ceiling loud speaker outlet by copper wires (2x1.5)


31-3-1 mm2 sound cable in 20 mm medium gauge pvc
conduit. Nr 393
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Wall Horn speaker outlet by copper wires (2x3) mm2
31-3-2 sound cable in 20 mm medium gauge pvc conduit.
Nr 1

31-4 PUBLIC ADDRESS FIXTURES


‫وحدات السماعات‬
Supply, install, connect, test and put into operation
public address fixtures complete with all
terminations, fittings, components, accessories and
all related ancillary works as shown on drawings and
specified in specifications.

31-4-1 Ceiling mounted loud speaker 6 W Nr 393


31-4-2 Wall mounted Horn speaker 15/30 W Nr 1
32 QUEUING SYSTEM
‫نظام ترتيب الدخول للعيادات الخارجية وقسم الغسيل الكلوى‬

Supply, install, testing, commissioning and put into


operation Queuing system complete with all
equipment, control panels, tickets dispensers for
each entrance, wide area displays for waiting areas,
7 segment displays for each clinic, sounder speakers,
racks, push buttons, Counter keypads, power
supplies, cabling and conduits and all necessary
32-1 ancillary works and accessories required for LS 2
complete installation as per drawings and specs.

33 MEETING ROOM AUDIO/VISUAL SYSTEM


‫نظام الصوتيات والمرئيات لغرفة االجتماعات‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, program, test and put into operation
a complete; state of the art audio visual system as
specified, shown on drawings The work should
include cabling, conduits, raceways etc and all
items/accessories that considered necessary for
proper system operation. The scope of work includes
all equipment and cables.The work includes but not
limited to the following items: AUDIO/VISUAL
SYSTEM FOR MEETING ROOM Equipment AV rack
enough for all equipment plus 20% space spare for
future expansion. The item includes all necessary
power switching units, perforated panels etc., and
any needed/related accessories.
The System includes the following items :-
- AV Rack
- AV Controller.
- All PC floor box and wall outlets including multi
media (HDMI, VGA, Audio, USB), mic outlet and
33-1 integrated computer line driver.The item includes all
cables/plugs from the floor/wall outlets to the AV
rack.
- DVD player/recorder. The item includes
cables/plugs to the AV rack.
- Master Dynamic microphone with cable/plug and
Wireless micro, wireless microphone receiver
- Video to VGA scaler including all cables/plugs and
Video switching,

transcoding and scaling.


- Graphic equalizer
- Audio power amplifier including all cables/plugs.
- Audio mixer
- 2 Multi format video output and 4 Multi format
video input.
- 8 ceiling speaker 6w including all cables/plugs.
The item includes all needed cables/plugs and
outlets.
- 60" LED with projection frame.
- Interface with main public address system rack LS 2
- Power supply unit.
- Ceiling suspended projector.

34 LECTURE ROOM AUDIO/VISUAL SYSTEM


‫نظام الصوتيات والمرئيات لغرفة المحاضرات‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, program, test and put into operation
audio visual system as specified, shown on drawings
The work should include cabling, conduits, raceways
etc and all items/accessories that considered
necessary for proper system operation. The scope of
work includes all equipment and cables.The work
includes but not limited to the following items:
- All PC floor box and wall outlets including multi
media (HDMI, VGA, Audio, USB),The item includes all
34-1 cables/plugs from the floor/wall outlets. LS 1
- 50" LED.

35 NURSE CALLING SYSTEM


35-1 NURSE CALLING MASTER STATIONS
‫نظام استدعاء الممرضات‬
‫الوحدة الرئيسية لنظام استدعاء الممرضات‬
Supply, install, testing, commissioning and put into
operation nurse calling system stations complete
with All equipments needed, power supplies,
terminations, fittings, components, accessories,
junction box, interfacing, Equipments fixing,
35-11 Programming, accessories and all necessary Nr 34
accessories to finish worksas shown on drawings and
as described in specifications.

35-2 NURSE CALLING OUTLET


‫مخارج وحدات استدعاء الممرضات‬
Supplying, installing, connecting, testing and put into
operation nurse call outlets including 4 pair cables,
conduits, conduit fittings, cable ducts, boxes and all
necessary accessories and ancillary works and
materials required for complete installations as
specified and as indicated on the drawings.

Nurse call Outlet using 4 pair CAT-6 cable inside


35-2-1 20mm PVC Conduit. Nr 954
35-3 NURSE CALLING FIXTURES
‫وحدات استدعاء الممرضات‬
Supply, install, testing, commissioning and put into
operation nurse call fixtures, labeling complete with
power supplies, back boxes and all terminations,
fittings, components, accessories and all necessary
accessories to finish works as per drawings,
specification and standard

Main Workstation for management with license


35-3-1 software Nr 1
35-3-2 Room Controller Unit (4 Beds) Nr 72
35-3-3 Room Controller Unit (2 Beds) Nr 26
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
35-3-4 Cancel switch Nr 154
35-3-5 Code blue and'Cancel switch Nr 102
35-3-6 Pull Cord Call Station Nr 141
Wall mounted corridor Bulkhead Nurse call lights
35-3-7 Nr 108
35-3-8 Corridor Bulkhead Nurse call lights Nr 148
35-3-9 Patient Hand Set With Flexible Cord Nr 203
36 MASTER ANALOGUE CLOCK SYSTEM
‫نظام الساعات المركزية‬
Supply, install, testing, commissioning and put into
operation Master Clock system complete with
Master clock power supply and able to connect to
analogue / Digital clocks including GPS antenna,
Control equipment, signal repeaters and all
36-1 accessories, cabling, conduits etc...., and all
necessary ancillary works and accessories required LS 1
for complete installation as per drawings and specs

36-2 SLAVE CLOCK OUTLETS


‫مخارج الساعات التابعة‬

Supply, install, testing and put into operation Slave


clock outlet complete with conduits, 2X1.5mm2
Twisted Shield cable, back box with junction box and
all necessary accessories to finish works as per
drawings, specification and standard

Slave Clock outlet using 2x1.5 mm2 cable inside


36-2-1 20mm PVC Conduit. Nr 93
36-3 SLAVE CLOCK FIXTURES
‫وحدات الساعات التابعة‬

Supply, install, testing, commissioning and put into


operation Slave Clocks complete with all
terminations, fittings, components, accessories and
all necessary accessories to finish works as per
drawings, specification and standard

SLAVE CLOCK DOUBLE SIDE ANALOGUE TYPE,


36-3-1 CEILING MOUNTED with power supply and all
accessories Nr 63

SLAVE CLOCK SINGLE SIDE ANALOGUE TYPE, WALL


36-3-2 MOUNTED with power supply and all accessories
Nr 30

37 ACCESS CONTROL PANEL


‫نظام التحكم فى االبواب‬
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )

Supply, install, testing, commissioning and put into


operation access control panel complete with All
equipments needed, metal enclosures, power
supplies, terminations, fittings, components, battery,
battery charger, workstation, connection to B.M.S &
Fire Alarm systems, accessories and all necessary
accessories to finish works as per drawings,
specification and standard

37-1 ACP -- Four doors Nr 5


37-2 ACP -- Two doors Nr 8
38 ACCESS CONTROL SYSTEM OUTLETS
‫مخارج نظام التحكم فى االبواب‬
Supplying, installing, connecting, testing and put into
operation access control outlets including Cat6
cables, conduits, conduit fittings, cable ducts, boxes
and all necessary accessories and ancillary works and
materials required for complete installations as
specified and as indicated on the drawings.

ACP Outlet using CAT-06 Cable inside 20mm medium


38-1 gauge pvc conduit. Nr 112
Finger Print Time Attendance Outlet using CAT-06
38-2 Cable inside 20mm medium gauge pvc conduit.
Nr 0

39 ACCESS CONTROL SYSTEM FIXTURES


‫وحدات نظام التحكم فى االبواب‬
Supply, install, testing, commissioning and put into
operation access control fixtures, labeling, Card
programming / printer complete with all
terminations, fittings, components, accessories and
all necessary accessories to finish works as per
drawings, specification and standard

39-1 Card reader Nr 32


39-2 Request to exit push button Nr 32
39-3 Door Lock Nr 29
39-4 DOUBLE DOOR LOCK Nr 3
39-5 Acceess Cards as rerquired by owner LS 1
39-6 Finger Print time attendance Nr 5
40 BARRIER GATE ACCESS CONTROL SYSTEM
‫نظام التحكم فى دخول الجراجات‬
40-1 MAIN CONTROL UNIT
UP Total
Item Description Unit BOQ Qty
( EGP ) ( EGP )
Supply, install, testing, commissioning and put into
operation main control unit for gate barriers
complete with control panels and all equipments
needed, metal enclosures, power supplies,
terminations, fittings, components, battery, battery
charger, Parking system management PC, Parking
management software, programming, barrier gates,
cables, controller, card readers, cameras,
workstation, connection to B.M.S & Fire Alarm LS 1
systems, accessories and all necessary accessories to
finish works as per drawings, specification and
standard

40-1-1 Gate Barrier 5m width Nr 3


40-1-2 Gate Barrier 3m width Nr
41 LIQUID LEAKAGE DETECTION SYSTEM
‫نظام انذار تسرب السوائل‬
Supply, install, testing, commissioning and put into
operation a complete leak detection system
including but not limited to:
control panel, detection cables/sensors, control
cables, back-up batteries and all needed/related
accessories The system should covers MAIN
TELECOM ROOM at Basement floor, complete with
All equipments needed , power supplies,
terminations, fittings, components, battery charger,
41-1 connection to B.M.S system, accessories and all LS 1
necessary accessories to finish works as per
drawings, specification and standard

42 BUILDERS WORKS
‫أعمال البنائين‬
Supply, install, testing, commissioning and put into
operation all builder work (not include any civil
work) complete with PVC conduits, road crossing for
lighting, power, light current, fire alarm, sleeves for
lighting, power, light current, fire alarm, shafts and
opening works with all related accessories as per
specifications and details drawings. The drawings
details are for guidance only, the contractor is
responsible for all sizing, calculations, coordination
42-1 with other trades,.. etc. and all necessary ancilitary LS 1
works and accessories required for complete
installation as per drawings and specs