Edge Elements

Short-Circuit Calculation / Method : IEC 60909 3-Phase Short-Circuit / Max. Short-Circuit Currents

Asynchronous Motors Grid Identification Short-Circuit Duration


Always Considered Automatic Break Time 0,10 s
Fault Clearing Time (Ith) 1,00 s
Decaying Aperiodic Component (idc) Conductor Temperature c-Voltage Factor
Using Method B User Defined No User Defined No

Grid: Study Case: Study Case Page:


Type Voltage c- Busbar Sk" Ik" ip Ib Ik Ith
[kV] Factor [MVA/MVA] [kA/kA] [kA/kA] [kA] [kA] [kA]
RESORT M Asm TRANSRES3_0.38KV 0,37 MVA 0,57 kA 1,30 kA
TaCU1 M Asm TaCU1-M_0.38KV 0,31 MVA 0,47 kA 0,78 kA
TaSG1 M Asm TaSG1-M_0.38KV 0,34 MVA 0,51 kA 0,86 kA
NEC/NER Nec TRANSDIS3_13.2KV 0,00 MVA 0,00 kA 0,00 kA
GENERADOR SINCRONO Sym GEN40MVA_11KV 220,53 MVA 11,57 kA 27,85 kA
SISTEMA INTERCONEC Xnet REQUIV2_132KV 1300,00 MVA 5,69 kA 13,99 kA
Breaker/Switch(1) Coup N2 0,00 MVA 0,00 kA 0,00 kA
N1 0,00 MVA 0,00 kA 0,00 kA
Breaker/Switch(2) Coup N5 0,00 MVA 0,00 kA 0,00 kA
N6 0,00 MVA 0,00 kA 0,00 kA
Breaker/Switch(3) Coup BUS2_132KV 0,00 MVA 0,00 kA 0,00 kA
N8 0,00 MVA 0,00 kA 0,00 kA
Breaker/Switch(4) Coup N10 0,00 MVA 0,00 kA 0,00 kA
N11 0,00 MVA 0,00 kA 0,00 kA
Breaker/Switch(5) Coup BUS2_132KV 0,00 MVA 0,00 kA 0,00 kA
N15 0,00 MVA 0,00 kA 0,00 kA
Breaker/Switch(6) Coup TRANSSA1.1_0.38KV 0,62 MVA 0,95 kA 2,63 kA
N22 0,00 MVA 0,00 kA 0,00 kA
Breaker/Switch(7) Coup TRANSSA2.1_0.38KV 0,00 MVA 0,00 kA 0,00 kA
N23 0,00 MVA 0,00 kA 0,00 kA
Breaker/Switch(8) Coup TaD1_0.38KV 0,30 MVA 0,46 kA 1,16 kA
TaD2_0.38KV 8,12 MVA 12,33 kA 30,95 kA
Breaker/Switch(9) Coup N16 0,00 MVA 0,00 kA 0,00 kA
N17 0,00 MVA 0,00 kA 0,00 kA
. Lne N2 0,00 MVA 0,00 kA 0,00 kA
BUS1_132KV 171,12 MVA 0,75 kA 1,67 kA
BUS 1 132 KV Lne TRANSDIS1_132KV 505,77 MVA 2,21 kA 4,93 kA
N11 0,00 MVA 0,00 kA 0,00 kA
BUS 1 132 KV(1) Lne REQUIV1_132KV 172,11 MVA 0,75 kA 1,68 kA
N6 0,00 MVA 0,00 kA 0,00 kA
BUS 1 132 KV(2) Lne N10 0,00 MVA 0,00 kA 0,00 kA
BUS1_132KV 1,01 MVA 0,00 kA 0,01 kA
BUS 2 132 KV Lne TRANSDIS1_132KV 0,00 MVA 0,00 kA 0,00 kA
N15 0,00 MVA 0,00 kA 0,00 kA
Grid: Study Case: Study Case Page:
Type Voltage c- Busbar Sk" Ik" ip Ib Ik Ith
[kV] Factor [MVA/MVA] [kA/kA] [kA/kA] [kA] [kA] [kA]
BUS 2 132 KV(1) Lne REQUIV1_132KV 0,00 MVA 0,00 kA 0,00 kA
N8 0,00 MVA 0,00 kA 0,00 kA
BUS-TRAFO 1.25MVA Lne TRANSDIS_132KV 505,69 MVA 2,21 kA 4,93 kA
TRANSDIS1_132KV 1,01 MVA 0,00 kA 0,01 kA
BUS1 132 KV Lne N5 0,00 MVA 0,00 kA 0,00 kA
BUS1_132KV 337,66 MVA 1,48 kA 3,29 kA
DBFNS MT 2500A 80x Lne GEN40MVA_11KV 230,18 MVA 12,08 kA 29,06 kA
TRANSFUN1_11KV 219,09 MVA 11,50 kA 27,64 kA
DBFNS MT 2500A EXC Lne EXCITAC1_11KV 435,19 MVA 22,84 kA 55,23 kA
GEN40MVA_11KV 0,00 MVA 0,00 kA 0,00 kA
LINEA BT TaCU1 3x1 Lne TaD2_0.38KV 0,30 MVA 0,46 kA 1,16 kA
TaCU1_0.38KV 6,87 MVA 10,43 kA 21,91 kA
LINEA BT TaD1 3x1x Lne N22 0,00 MVA 0,00 kA 0,00 kA
TaD1_0.38KV 7,79 MVA 11,84 kA 29,71 kA
LINEA BT TaD1 3x1x Lne N23 0,00 MVA 0,00 kA 0,00 kA
TaD2_0.38KV 0,00 MVA 0,00 kA 0,00 kA
LINEA BT TaPIL 3x3 Lne TaD1_0.38KV 0,00 MVA 0,00 kA 0,00 kA
TaPIL_0.38 KV 4,33 MVA 6,57 kA 9,64 kA
LINEA BT TaSG1 3x1 Lne TaD1_0.38KV 0,33 MVA 0,50 kA 1,25 kA
TaSG1_0.38KV 6,03 MVA 9,16 kA 18,89 kA
LINEA MT AEREA RES Lne TRANSRES1_13.2KV 0,42 MVA 0,02 kA 0,05 kA
TRANSRES2_13.2KV 18,83 MVA 0,82 kA 1,52 kA
LINEA MT SUBTERRAN Lne TRANSRES1_13.2KV 24,28 MVA 1,06 kA 2,93 kA
TRANSDIS3_13.2KV 0,42 MVA 0,02 kA 0,05 kA
LINEA SUBTERRANA S Lne TRANSSA1_13.2KV 24,04 MVA 1,05 kA 2,89 kA
N17 0,00 MVA 0,00 kA 0,00 kA
LINEA SUBTERRANA S Lne TRANSSA2_13.2KV 0,00 MVA 0,00 kA 0,00 kA
N20 0,00 MVA 0,00 kA 0,00 kA
LINEA SUBTERRANEA Lne N16 0,00 MVA 0,00 kA 0,00 kA
TRANSDIS3_13.2KV 0,64 MVA 0,03 kA 0,08 kA
LINEA SUBTERRANEA Lne N18 0,00 MVA 0,00 kA 0,00 kA
TRANSDIS3_13.2KV 0,00 MVA 0,00 kA 0,00 kA
LINEA TRANSMISION Lne REQUIV1_132KV 337,72 MVA 1,48 kA 3,29 kA
REQUIV2_132KV 125,77 MVA 0,55 kA 1,35 kA
LINEA TRANSMISION Lne TRANSFUN2_132KV 338,65 MVA 1,48 kA 3,30 kA
N1 0,00 MVA 0,00 kA 0,00 kA
LINEA TRANSMISION Lne N1 0,00 MVA 0,00 kA 0,00 kA
N3 0,00 MVA 0,00 kA 0,00 kA
LINEA TRANSMISION Lne N4 0,00 MVA 0,00 kA 0,00 kA
BUS2_132KV 0,00 MVA 0,00 kA 0,00 kA
TaCU1 E 3x1x150 0. Lne TaCU1_0.38KV 0,00 MVA 0,00 kA 0,00 kA
TaCU1-E_0.38KV 6,88 MVA 10,46 kA 20,03 kA
TaCU1 M 3x1x35 0.3 Lne TaCU1_0.38KV 0,31 MVA 0,47 kA 0,98 kA
TaCU1-M_0.38KV 5,55 MVA 8,44 kA 14,11 kA
TaPIL E 3x1x35+35 Lne TaPIL_0.38 KV 0,00 MVA 0,00 kA 0,00 kA
TaPIL1_0.38 KV 3,45 MVA 5,24 kA 7,59 kA
Grid: Study Case: Study Case Page:
Type Voltage c- Busbar Sk" Ik" ip Ib Ik Ith
[kV] Factor [MVA/MVA] [kA/kA] [kA/kA] [kA] [kA] [kA]
TaSG1 E 3x1x50 0.3 Lne TaSG1_0.38KV 0,00 MVA 0,00 kA 0,00 kA
TaSG1-E_0.38KV 5,33 MVA 8,10 kA 14,05 kA
TaSG1 M 3x1x50 0.3 Lne TaSG1_0.38KV 0,33 MVA 0,50 kA 1,04 kA
TaSG1-M_0.38KV 4,30 MVA 6,53 kA 10,94 kA
TANSFORMADOR EXCIT Tr2 EXCITAC1_11KV 0,00 MVA 0,00 kA 0,00 kA
EXCITAC2_0.35KV 6,41 MVA 10,57 kA 29,81 kA
TRANSFORMADOR 1.25 Tr2 TRANSDIS_132KV 1,01 MVA 0,00 kA 0,01 kA
TRANSDIS3_13.2KV 23,66 MVA 1,03 kA 2,87 kA
TRANSFORMADOR 44MV Tr2 TRANSFUN2_132KV 171,12 MVA 0,75 kA 1,67 kA
TRANSFUN1_11KV 231,80 MVA 12,17 kA 29,24 kA
TRANSFORMADOR DIST Tr2 TRANSRES2_13.2KV 0,42 MVA 0,02 kA 0,03 kA
TRANSRES3_0.38KV 7,09 MVA 10,77 kA 24,54 kA
TRANSFORMADOR SA1 Tr2 TRANSSA1_13.2KV 0,64 MVA 0,03 kA 0,08 kA
TRANSSA1.1_0.38KV 9,14 MVA 13,88 kA 38,44 kA
TRANSFORMADOR SA2 Tr2 TRANSSA2_13.2KV 0,00 MVA 0,00 kA 0,00 kA
TRANSSA2.1_0.38KV 0,00 MVA 0,00 kA 0,00 kA