You are on page 1of 20

DESIGN BRIEF

Project Name INDAH KIAT KARAWANG PROJECT Location KARAWANG-INDONESIA


Building Name FBB1 BUILDING CONSTRUCTION Project No. H-NBI-1000….
IKK
Customer PT. …. Doc. No.

DESIGN BRIEF

Job No.: Building: FBB1


Revision: 00 Dated: 18-May-2023

Project Name: INDAH KIAT KARAWANG


Building Name: FBB1
The Total No. of Pages in this Document Are 23
Page 2 of 19

Introduction
This Design Calculations Package has been prepared using the applicable Indonesian
and American codes and standards and the latest developments in engineering practices.
A competent design engineer prepared the calculations and another competent engineer
checked his work.
Computer programs have been used where applicable to determine structural
requirements. The output of these programs has been incorporated in this package
together with explanation text where possible. The whole package has been prepared
using an advanced computer text processor.

For your easy reference, all pages have been numbered and a table of contents has been
provided. We have divided the package into two sections as follows:

1. Design Information: This section contains the description of the building


designed, design codes and material specifications used, design assumptions,
loads and design sketches showing building components layouts and members
sizes.

2. Software Design Printouts: This section includes the output of software


programs used in the design along with explanations for the output where
possible.

Please use this calculations package in conjunction with the drawings provided. You
can resubmit this package with the drawings to other parties for their approval as
required, or keep this package for future reference. Nova Buildings does not require
these calculations to be returned.

For any questions regarding this package please do not hesitate to contact our sales
office. Nova Buildings keeps records of reference on design calculations for each
building designed as a part of Nova Buildings total quality system.

Engineering Department
Page 3 of 19

Table of Contents

Introduction.........................................................................................................................................2

Section 1 : Design Information ..........................................................................................................4


Applicable Design Codes ........................................................................................................5
Material Specifications ...........................................................................................................6
Design Assumptions ................................................................................................................7
Input Loads .............................................................................................................................8
Load Combinations ..............................................................................................................10
Deflection Criteria ................................................................................................................11

Section 2 : Computer Design Printouts ..........................................................................................12


DESIGN CALCULATION SHEET Page 4 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

Section 1: Design Information

• Applicable Design Codes


• Material Specifications
• Design Assumptions
• Input Loads
• Load Combinations
• Deflection Criteria
DESIGN CALCULATION SHEET Page 5 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

Applicable Design Codes


The Pre-Engineered Building described in these calculations was designed according to the U.S.A.
Buildings and Design Codes that have been referred to in the design:

Loads applied on buildings are in accordance with:

The 2012 Edition of the Metal Building Systems Manual Metal Building
Manufacturers Association, Inc. (MBMA)
1300 Summer Ave., Cleveland, Ohio 44115, USA

The 2016 Edition of the Minimum Design Loads for Buildings and Other Structures
American Society of Civil Engineers (ASCE)
1801 Alexander Bell Drive, Reston, Virginia 20191

Hot rolled sections and built up sections are designed in accordance with:

The 2016 Edition of the Specification for Structural Steel Buildings – Load and
Resistance Factor Design
American Institute of Steel Construction, Inc. (AISC)
1 East Wacker Drive, Suite 700, Chicago, Illinois 60601-2001, USA

Cold formed members are designed in accordance with:

The 2001 Edition with 2004 Supplement of the North American Specification for the
Design of Cold-Formed Steel Structral Members
American Iron and Steel Institute (AISI)
1140 Connecticut Avenue, NW, Washington, DC 20036, USA

Welding is applied in accordance with:

The 2004 Edition of the American Welding Society (AWS D.1.1/ D.1.1 M: 2004)
Structural Welding Code - Steel Manual
550 NW Lejeune Road, Miami, FL 33126, USA

Wind speed is applied in accordance with:

The 2016 Edition of the Minimum Design Loads for Buildings and Other Structures
American Society of Civil Engineers (ASCE)
1801 Alexander Bell Drive, Reston, Virginia 20191

Seismic load is applied in accordance with:

The 2016 Edition of the Minimum Design Loads for Buildings and Other Structures
American Society of Civil Engineers (ASCE)
1801 Alexander Bell Drive, Reston, Virginia 20191
DESIGN CALCULATION SHEET Page 6 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

Material Specifications
The following is the list of the material standards and specifications for which the building components
have been designed:

Material Specification
Minimum
Category No. Material Specification
Strength
ASTM A 572M Grade 345 Type
1 Built-Up Member Fy = 345 Mpa
1, Q345B (or) its Equivalent
Primary
JIS G3101 SS 400, A36 (or) its
2 Hot-Rolled Member Fy = 235 Mpa
Equivalent
JIS G3101 SS 400, A36 (or) its
Strut Beam 3 Tube Fy = 235 Mpa
Equivalent
JIS G3101 SS 400, A36 (or) its
4 Angle Fy = 235 Mpa
Equivalent
Bracing
JIS G3112 SR 24 Hot-Dipped
5 Round Bar Fy = 235 Mpa
Galvanized (or) its Equivalent
Z/C Galva span® Hi-Ten®G450,
6 Purlin & Girt Fy = 450 Mpa
Coating Z275 (or) its Equivalent
Secondary
JIS G3112 SR 24 Hot-Dipped
7 Sagrod Fy = 235 Mpa
Galvanized (or) its Equivalent
ASTM A325 Hot Dip Galvanized
8 High Strength Bolts Fu = 800 Mpa
(or) its Equivalent
DIN Grade 4.6, ASTM A307
Bolts &
9 Standard Bolts Electro Galvanized (or) its Fu = 400 Mpa
Connection
Equivalent
SGD290D/SGD400D Fy = 450/380
10 Anchor Bolts
Hot-Dipped Galvanized Mpa
Sheeting &
Accessories 11 Metal N/A
(Optional)
DESIGN CALCULATION SHEET Page 7 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

Design Assumptions
• The main frame rafters is Roof System and this Frame are are pinned connection to the
concrete columns. .
• The stability of the building is provided through the frame action of the main frames.
• The longitudinal stability of the building is provided through the truss transmitted to Angle-
diagonal action in the cross braced bays of the building.
• The roof purlins are continuous beams supported at rigid frame locations and span the bay
spacing of the building.
• This building is designed as Enclosed building.
• The concrete works are not under Nova scope.
DESIGN CALCULATION SHEET Page 8 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

Input Loads
1. Dead Load Main roof 0.53 kN/m2

On purlin 1.00 kN/m2


2. Roof Live Load
On frame 1.00 kN/m2
3. Collateral Load Only apply for area ceiling 0.50 kN/m2
4. Wind Load Follow as below

WIND LOAD CALCULATIONS (AS PER ASCE7-16)

EAVE HEIGHT, h (m) 27.6


WIDTH BULDING (m) 65
RATIO h/L 0.425
WIND SPEED V (KM/hour) 186
WIND SPEED V (m/s) 51.80
WIND EXPOSURE C
BAY SPACING (m) 8.00
qh=0.613.Kz.Kzt.Kd.V2[ V in
VELOCITY PRESSURE (N/m2)
m/s]
VELOCITY PRESSURE (kN/m2) qh= 1.74

THE VELOCITY
1.25
PRESSURE EXPOSURE, (Kz)
THE TOPOGRAPHIC FACTOR, (Kzt) 1.00

THE WIND DIRECTIONALITY


0.85
FACTOR, (Kd)

DESIGN PRESSURE, p (N/m2) p=qh[(GCpf)-(GCpi)]


ENCLOSURE CONDITION Enclosed
INTERNAL PRESSURE
±0.18
COEFFICIENT, (Gcpi)
DESIGN CALCULATION SHEET Page 9 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

MAIN FRAME WIND LOAD FOR CASE 1 : TRANSVERSE(L), PRESSURE


Height above Ground Level Wall Wind Load
Kz q(KN/m2) Gcpi
m ft Windward Leeward Side
4.6 15.091864 0.8509186 1.19 kN/m² 0.18 3.945 kN/m -8.383 kN/m -10.736 kN/m
9.2 30.183727 0.9811024 1.37 kN/m² 0.18 4.931 kN/m -8.383 kN/m -10.736 kN/m
13.8 45.275591 1.066378 1.49 kN/m² 0.18 5.577 kN/m -8.383 kN/m -10.736 kN/m
18.4 60.367454 1.1314698 1.58 kN/m² 0.18 6.070 kN/m -8.383 kN/m -10.736 kN/m
23 75.459318 1.1918373 1.67 kN/m² 0.18 6.528 kN/m -8.383 kN/m -10.736 kN/m
27.6 90.551181 1.2411024 1.74 kN/m² 0.18 6.901 kN/m -8.383 kN/m -10.736 kN/m
Type Location Horiz dist from windward edge Cp1 Cp2 p1 p2
0m to 13.8 m -0.900 -0.1800 -13.088 kN/m -4.619 kN/m
13.8 m to 27.6 m -0.900 -0.1800 -13.088 kN/m -4.619 kN/m
Windward
27.6 m to 55.2 m -0.500 -0.1800 -8.383 kN/m -4.619 kN/m
greater than 55.2 m -0.300 -0.1800 -6.030 kN/m -4.619 kN/m
Roof
0 to 13.8 m -0.900 -0.1800 -13.088 kN/m -4.619 kN/m
13.8 m to 27.6 m -0.900 -0.1800 -13.088 kN/m -4.619 kN/m
Leeward
27.6 m to 55.2 m -0.500 -0.1800 -8.383 kN/m -4.619 kN/m
greater than 55.2 m -0.300 -0.1800 -6.030 kN/m -4.619 kN/m
MAIN FRAME WIND LOAD FOR CASE 2 : TRANSVERSE(L), SUCTION
Height above Ground Level Wall Wind Load
Kz q(KN/m2) Gcpi
m ft Windward Leeward Side
4.6 15.091864 0.8509186 1.19 kN/m² -0.18 8.947 kN/m -3.381 kN/m -5.733 kN/m
9.2 30.183727 0.9811024 1.37 kN/m² -0.18 9.933 kN/m -3.381 kN/m -5.733 kN/m
13.8 45.275591 1.066378 1.49 kN/m² -0.18 10.579 kN/m -3.381 kN/m -5.733 kN/m
18.4 60.367454 1.1314698 1.58 kN/m² -0.18 11.072 kN/m -3.381 kN/m -5.733 kN/m
23 75.459318 1.1918373 1.67 kN/m² -0.18 11.530 kN/m -3.381 kN/m -5.733 kN/m
27.6 90.551181 1.2411024 1.74 kN/m² -0.18 11.903 kN/m -3.381 kN/m -5.733 kN/m
Type Location Horiz dist from windward edge Cp1 Cp2 p1 p2
0m to 13.8 m -0.900 -0.1800 -8.086 kN/m 0.384 kN/m
13.8 m to 27.6 m -0.900 -0.1800 -8.086 kN/m 0.384 kN/m
Windward
27.6 m to 55.2 m -0.500 -0.1800 -3.381 kN/m 0.384 kN/m
greater than 55.2 m -0.300 -0.1800 -1.028 kN/m 0.384 kN/m
Roof
0 to 13.8 m -0.900 -0.1800 -8.086 kN/m 0.384 kN/m
13.8 m to 27.6 m -0.900 -0.1800 -8.086 kN/m 0.384 kN/m
Leeward
27.6 m to 55.2 m -0.500 -0.1800 -3.381 kN/m 0.384 kN/m
greater than 55.2 m -0.300 -0.1800 -1.028 kN/m 0.384 kN/m
MAIN FRAME WIND LOAD FOR CASE 3: LONGITUDINAL(B), PRESSURE
Height above Ground Level Wall Wind Load
Kz q(KN/m2) Gcpi
m ft Windward Leeward Side
4.6 15.091864 0.8509186 1.19 kN/m² 0.18 3.945 kN/m -4.854 kN/m -10.736 kN/m
9.2 30.183727 0.9811024 1.37 kN/m² 0.18 4.931 kN/m -4.854 kN/m -10.736 kN/m
13.8 45.275591 1.066378 1.49 kN/m² 0.18 5.577 kN/m -4.854 kN/m -10.736 kN/m
18.4 60.367454 1.1314698 1.58 kN/m² 0.18 6.070 kN/m -4.854 kN/m -10.736 kN/m
23 75.459318 1.1918373 1.67 kN/m² 0.18 6.528 kN/m -4.854 kN/m -10.736 kN/m
27.6 90.551181 1.2411024 1.74 kN/m² 0.18 6.901 kN/m -4.854 kN/m -10.736 kN/m
Type Location Horiz dist from windward edge Cp1 Cp2 p1 p2
Windward 0m to 13.8 m -0.900 -0.1800 -13.088 kN/m -4.619 kN/m
13.8 m to 27.6 m -0.900 -0.1800 -13.088 kN/m -4.619 kN/m
Roof And
27.6 m to 55.2 m -0.500 -0.1800 -8.383 kN/m -4.619 kN/m
Leeward greater than 55.2 m -0.300 -0.1800 -6.030 kN/m -4.619 kN/m
MAIN FRAME WIND LOAD CASE 4: LONGITUDINAL(B), SUCTION
Height above Ground Level Wall Wind Load
Kz q(KN/m2) Gcpi
m ft Windward Leeward Side
4.6 15.091864 0.8509186 1.19 kN/m² -0.18 8.947 kN/m 0.148 kN/m -5.733 kN/m
9.2 30.183727 0.9811024 1.37 kN/m² -0.18 9.933 kN/m 0.148 kN/m -5.733 kN/m
13.8 45.275591 1.066378 1.49 kN/m² -0.18 10.579 kN/m 0.148 kN/m -5.733 kN/m
18.4 60.367454 1.1314698 1.58 kN/m² -0.18 11.072 kN/m 0.148 kN/m -5.733 kN/m
23 75.459318 1.1918373 1.67 kN/m² -0.18 11.530 kN/m 0.148 kN/m -5.733 kN/m
27.6 90.551181 1.2411024 1.74 kN/m² -0.18 11.903 kN/m 0.148 kN/m -5.733 kN/m
Type Location Horiz dist from windward edge Cp1 Cp2 p1 p2
Windward 0m to 13.8 m -0.900 -0.1800 -8.086 kN/m 0.384 kN/m
13.8 m to 27.6 m -0.900 -0.1800 -8.086 kN/m 0.384 kN/m
Roof And
27.6 m to 55.2 m -0.500 -0.1800 -3.381 kN/m 0.384 kN/m
Leeward greater than 55.2 m -0.300 -0.1800 -1.028 kN/m 0.384 kN/m
DESIGN CALCULATION SHEET Page 10 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

Load Combinations
In the design of steel structure, member is designed in accordance with LRFD method, with the following
combination below :
1. Applied for Main-frame:

• 1.4 (Dead Load + Collateral Load)


• 1.2 (Dead Load + Collateral Load) + 1.6(Roof Live Load)+0.5Wind Load
• 1.2 (Dead Load + Collateral Load) + 1.6 (Roof Live Load)
• 1.2 (Dead Load + Collateral Load + 1.0Wind Load + 0.5(Roof Live Load)
• 0.9 Dead Load + Wind Load
• 1.2(Dead Load + Collateral Load) + 1.0 Earthquake Load
• 0.9 (Dead Load + Collateral Load) + 1.0Earthquake Load
2. Applied for Cold-formed Section:
• 1.4 (Dead Load + Collateral Load)
• 1.2 (Dead Load + Collateral Load) + 1.6 (Roof Live Load)
• 0.9Dead Load + Wind Load
DESIGN CALCULATION SHEET Page 11 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

Deflection Criteria
Maximum allowable vertical deflection & horizontal deflection are follow:

Structural Member Max Limit Loading


Span / 120 Dead + Live
Rafter Supporting Metal Roofing
Deflection

Live or Wind(a)
Vertical

Span / 180
Span / 150 Live
Roof Purlin
Span / 180 Wind(a)

Note :
a) The wind load to be taken as 0.42 times the Main Wind Force Resisting System (MWFRS) Load
DESIGN CALCULATION SHEET Page 12 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

Section 2: Software Design


1.Frame Typical Section

Frame Typical
DESIGN CALCULATION SHEET Page 13 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

1. Dead Load.

2. Roof Live Load


DESIGN CALCULATION SHEET Page 14 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

3. Collateral Load (only apply for area ceiling)


4. Wind Left

5. Wind Right
DESIGN CALCULATION SHEET Page 15 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

6. Wind Left 1

7. Wind Right 1
DESIGN CALCULATION SHEET Page 16 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

8. Wind Left 2

9. Wind Right 2
DESIGN CALCULATION SHEET Page 17 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

10. Wind Left 3

11. Wind Right 3


DESIGN CALCULATION SHEET Page 18 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

12. Wind End 1

13. Wind End 2


DESIGN CALCULATION SHEET Page 19 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

14. Crane Load

Ratio
DESIGN CALCULATION SHEET Page 20 of 23
Building Name INDAH KIAT KARAWANG PROJECT Rev. No. 00
Date 18-MAY-23
Customer
Designed By VAN
Description Checked By NVQ

2. Crane Beam