Professional Documents
Culture Documents
RV College of
Engineering Department of Electrical and Electronics
Engineering
6 th Sem
Power system analysis-i
(18ee64)
Sushmita Sarkar
Go, change the world
RV College of
Engineering Introduction
Modern power system are controlled from an Energy Control Center (ECC)
Data acquisition & processing, system operating conditions and control are
analyzed with the extensive use of digital computer.
RV College of Go, change the world
Engineering
Helps in
• Mathematical understanding
• Characteristics of
model of system the individual
network • Steady state in elements and their
form of network interconnections
equations
Important Studies:
Load Flow Analysis
Economic Dispatch
Fault Analysis
Stability Analysis
Automatic Generation Control(AGC)
Go, change the world
RV College of
Engineering UNIT-1
Presentation of power system components:
Circuit models of transmission line, synchronous machines, transformer
and load
One line diagram
Impedance and reactance diagram
Per unit system
Per unit impedance of power system
V3
I3
RV College of
Representation of power system components Go, change the world
Engineering
For balanced 3-phase system , the SLD shows the 1-phase equivalent.
Transformer neutral are generally solidly grounded and generator neutrals are
grounded through high resistance and reactance. This information is vital for
The impedance diagram for the power system can be drawn from the SLD.
Go, change the world
RV College of
Engineering Single Line Diagram
Go, change the world
RV College of
Engineering Impedance Diagram
Go, change the world
RV College of
Engineering Reactance Diagram
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
A per-unit system is the expression of system quantities as fractions of a defined base unit quantity.
Calculations are simplified because quantities expressed as per-unit do not change when they are referred from one side of
This can be a pronounced advantage in power system analysis where large numbers of transformers may be encountered.
Moreover, similar types of apparatus will have the impedances lying within a narrow numerical range when expressed as a
per-unit fraction of the equipment rating, even if the unit size varies widely.
Conversion of per-unit quantities to volts, ohms, or amperes requires a knowledge of the base that the per-unit quantities
The per-unit system is used in power flow, short circuit evaluation, motor starting studies etc.
The main idea of a per unit system is to absorb large differences in absolute values into base relationships. Thus,
representations of elements in the system with per unit values become more uniform.
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
Transformation of bases
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
Per unit system for single phase transformer
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
RV College of
Go, change the world
Engineering
PER UNIT SYSTEM
The pu impedance diagram is obtained from the SLD by the following steps:
2. Divide the network into different sections based on the location of the transformers.
4. Fix the base voltages of other sections using the voltage ratio of the transformers.
Introduction
3- power systems are designed to be symmetric and balanced.
Unbalance loading conditions may cause asymmetry in current and voltages.
At higher voltage levels, asymmetry is caused due to system faults.
What is a fault?
A fault in any circuit is any event, which causes a deviation from the normal flow of currents.
RV College of
Engineering Types of Faults Go, change the world
Go, change the world
Series Fault
RV College of
Engineering
Effects
Abnormal operation of the system
Exceeding the voltages beyond normal values in certain parts of the network, which further
Although open circuit faults can be tolerated for longer periods than short circuit faults, these
A short circuit can be defined as an abnormal connection of very low impedance between two points of
different potential, whether made intentionally or accidentally.
These are the most common and severe kind of faults, resulting in the flow of abnormal high currents
through the equipment or transmission lines.
If these faults are allowed to persist even for a short period, it leads to the extensive damage to the
equipment.
Short circuit faults are also called as shunt faults. These faults are caused due to the insulation failure
between phase conductors or between earth and phase conductors or both.
The various possible short circuit fault conditions include three phase to earth, three phase clear of earth,
phase to phase, single phase to earth, two phase to earth and phase to phase plus single phase to earth.
The three phase fault clear of earth and three phase fault to earth are balanced or symmetrical short
circuit faults while other remaining faults are unsymmetrical faults.
Go, change the world
Shunt Fault
RV College of
Engineering
Go, change the world
Shunt Fault
RV College of
Engineering
Causes
These may be due to internal or external effects
External effects include overloading of equipments, insulation failure due to lighting surges and
mechanical damage by public.
Go, change the world
Shunt Fault
RV College of
Engineering
Effects
Arcing faults can lead to fire and explosion in equipment such as transformers and circuit
breakers.
Abnormal currents cause the equipment to get overheated, which further leads to reduction
of life span of their insulation.
The operating voltages of the system can go below or above their acceptance values that
creates harmful effect to the service rendered by the power system.
The power flow is severely restricted or even completely blocked as long as the short
circuit fault persists.
Go, change the world
Shunt Fault
RV College of
Engineering
A symmetrical fault gives rise to symmetrical fault currents that are displaced with 1200
each other.
Symmetrical fault is also called as balanced fault.
This fault occurs when all the three phases are simultaneously short circuited.
These faults rarely occur in practice as compared with unsymmetrical faults.
Two kinds of symmetrical faults include line to line to line (L-L-L) and line to line to line
to ground (L-L-L-G) .
Go, change the world
Symmetrical faults
RV College of
Engineering
faults.
However, if these faults occur, they cause a very severe damage to the equipment even
The analysis of these faults is required for selecting the rupturing capacity of the circuit
These faults are analyzed on per phase basis using bus impedance matrix or Thevenins’s
theorem.
Go, change the world
Unsymmetrical faults
RV College of
Engineering
The most common faults that occur in the power system network are unsymmetrical faults.
This kind of fault gives rise to unsymmetrical fault currents (having different magnitudes with
unequal phase displacement).
These faults are also called as unbalanced faults as it causes unbalanced currents in the
system.
namely phase or line to ground (L-G) fault, phase to phase (L-L) fault and double line to
ground (L-L-G) fault.
Go, change the world
Unsymmetrical faults
RV College of
Engineering
A single line-to-ground (LG) fault is one of the most common faults and experiences show that 70-80 %
of the faults that occur in power system are of this type. This forms a short circuit path between the line
and ground. These are very less severe faults compared to other faults.
A line to line fault (LL) fault occur when a live conductor get in contact with other live conductor.
Heavy winds are the major cause for this fault during which swinging of overhead conductors may touch
together. These are less severe faults and its occurrence range may be between 15-20%.
In double line to ground faults (LLG) fault , two lines come into the contact with each other as well as
with ground. These are severe faults and the occurrence these faults is about 10% when compared with
total system faults.
Unsymmetrical faults are analyzed using methods of symmetrical components in order to determine the
voltage and currens in all parts of the system.
The analysis of these faults is more difficult compared to symmetrical faults.
This analysis is necessary for determining the size of a circuit breaker for largest short circuit current.
The greater current usually occurs for either L-G or L-L fault.
Go, change the world
Symmetrical Faults
RV College of
Engineering
Classified as
1) Positive sequence reactance(xd, xd', xd")
2) Negative sequence reactance (x2)
3) Zero sequence reactance (x0)
Note: While any machine has only one zero and negative sequence reactance, it has several positive
sequence reactances.
Go, change the world
Symmetrical Faults
RV College of
Engineering
𝐸𝑔 𝑜𝑎
Is = =
𝑋𝑑 2
𝐸𝑔 𝑜𝑏 𝐸𝑔 𝐸𝑔 1 1
I'= I0'+Is = = ; I0' = I' – Is = - = Eg −
𝑋𝑑′ 2 𝑋𝑑′ 𝑋𝑑 𝑋𝑑′ 𝑋𝑑
𝐸𝑔 𝑜𝑐 𝐸𝑔 𝐸𝑔 1 1
I"= I0" + I0' + Is = = ; I0" = I"- (I0' + Is ) = - = Eg −
𝑋𝑑" 2 𝑋𝑑" 𝑋𝑑′ 𝑋"𝑑 𝑋′𝑑
1 1 1 −𝑡/𝑇𝑑′ 1 1
Iac = Is + I0'𝑒 −𝑡/𝑇𝑑′
+ I0"𝑒 −𝑡/𝑇𝑑"
= Eg{ + − 𝑒 + − 𝑒 −𝑡/𝑇𝑑" }
𝑋𝑑 𝑋𝑑′ 𝑋𝑑 𝑋"𝑑 𝑋′𝑑
RV College of
Engineering Symmetrical Faults Go, change the world
The D.C components of the three armature currents will all be different and will decay to zero
with a time constant Ta (armature winding constant). This typically has a value between
0.005 to 0.15s.
2 2
Isc= 𝐼𝑎𝑐 + 𝐼𝑑𝑐
The maximum value this can attain at the beginning of a short circuit is:
2 𝐸𝑔 2 𝐸𝑔 𝐸𝑔
Isc= 𝐼"2 + 𝐼𝑑𝑐 = +( 2 )² = 3 = 3 𝐼"
𝑋𝑑 " 𝑋𝑑" 𝑋𝑑"
RV College of
Engineering Symmetrical Faults Go, change the world
Problem-1
A 50MVA, 13.2kV generator, with reactances Xd˝=12%, Xd́' = 25%, Xd=100%, is connected to a 50
MVA, 13.2/132kV transformer with XT=15%. It is operating on no-load at rated voltage, Eg=1.0pu.
Find the (i) subtransient , transient and steady state symmetrical fault currents in actual values, (ii) the
maximum possible DC component (iii) maximum value of instantaneous current and (iv) maximum
rms value of asymmetrical current when a symmetrical fault occurs at the HT terminals of the
transformer.
RV College of
Engineering Symmetrical Faults Go, change the world
Problem-2
Two generators are connected in parallel to the LV side of a three phase ∆ – Υ transformer. Gen1. is
rated 50 MVA, 13.8 kV and Gen 2. is rated 25 MVA, 13.8 kV. Each generator has subtransient
reactance of 25%. The transformer is rated 75MVA, 13.8 kV (∆) – 132 kV(Υ) with a reactance of
10%. Before the fault, the voltage on HV side of the transformer is 130kV. The transformer is
unloaded when a tree phase short circuit occurs on the HV side of the transformer. Find the
subtransient current of the generators.
RV College of
Engineering Symmetrical Faults Go, change the world
Problem-3
A 25 MVA, 13.2 kV synchronous generator is connected to a synchronous motor of same rating. Both
have a subtransient reactance of 15%. The line connecting them has a reactance of 10% on the
machine base. The motor is drawing a power of 18MW at 0.8 pf lead at 12.9 kV, when a short circuit
occurs at its terminals. Find the subtransient currents in the motor, generator and fault.
RV College of
Engineering Symmetrical Faults Go, change the world
RV College of
Engineering Symmetrical Faults Go, change the world
Problem:
For the system shown below, determine the fault current, bus voltages and line currents
when a balanced 3 phase fault occurs on bus 1. Assume the system is running on no
load and neglecting shunt capacitances. The fault impedance is j0.15 pu.
RV College of
Engineering Symmetrical Faults Go, change the world
RV College of
Engineering Symmetrical Faults Go, change the world
RV College of
Engineering Symmetrical Faults Go, change the world