You are on page 1of 5

Type test certificate

CONFIDENTIAL
Products: InteliGen4 200
Order codes: IG4200XXBAA

List of required tests

Test Test Norm Test details


group
Electrical Reset behavior ISO 16750-2 ---

Power supply failure --- ---

Power supply variation --- ---

Weak battery test --- ---

Operating voltage EN 61000-4-29 Short time voltage drops (40-70% of Unom


0.1 s), interrupts (0.05 s) and slow
voltage changes (66-150% of Unom, 5 s)

Reverse supply polarity --- 36V with reversed polarity, 5 minutes.

Current measurement --- ±20 mA for 0-2 A; 1 % of value for 2-5 A

Frequency measurement --- 30-70 Hz (accuracy 0.1 Hz).

Voltage measurement --- 10-277 V AC / 10-480 V AC (EU)

ComAp a.s., U Uranie 1612/14a, 170 00 Prague 7, Czech Republic

Registered in the Commercial register maintained by the Municipal Court in Prague, Section B, file 18788

www.comap-control.com
10-346 V AC / 10-600 V AC (US/Canada)

Accuracy 1%.

Withstand AC voltage test --- 600V between L1-L2-L3 mutually each.

Binary inputs and outputs --- ---

Analog inputs and outputs --- ---

Overvoltage --- ---

Low Voltage (LV) Battery --- ---

Voltage drop --- ---

RPM input --- ---

AC current survival test --- ---

AIN withstand test --- ---

UBAT measurement --- ---

D+ measurement --- ---

Maximal consumption --- ---

References --- ---

PF measurement --- ---

Power fail function --- ---

Total power dissipation --- ---

Mechanical Sinusoidal vibration EN (IEC) 60068-2-6 Test in axis X, Y, Z

3 hours in each axis

2Hz÷25Hz / ±1,6mm / 1 oct per minute

25Hz÷100Hz / 4,0g / 1 oct per minute

Shock test EN 60068-2-27 A=500m/s2; T=6ms; 10 half sinus shocks


in all axis both directions

Type test report: InteliGen4 200 2


Installation test --- ---

IK protection ČSN EN 50102 UL746C ---

Mold stress test UL746C ---

Flame test UL94 ---

Button lifetime test --- ---

Climate Temperature range test --- ---

Dry heat EN (IEC) 60068-2-2 B 70°C /16 hours

Low temperature EN (IEC) 60068-2-1 A -40°C /16 hours

Cyclic damp heat EN (IEC) 60068-2-30 D 25/55/25°C; humidity at 95%

1cycle = 24h; 2cycles required (48 hours)

Long time temperatures EN (IEC) 60068-2-2 Bd 70°C /20 days

EN (IEC) 60068-2-1 Ad -40°C /20 days

Sunshine EN 60068-2-5 Level of radiation/sunshine: 1090W/m2 ±


10%

Progress B: Cyclic radiation

1 cycle: 20h expose / 4h darkness

55°C / 2cycles

IP IEC 60529 ---

UL temperature test UL508 ---

Storage temperatures EN 60068-2-2 Bd 80°C /16 hours

EN 60068-2-1, Ab, Ad -40°C /16 hours

Thermal shocks EN 60068-2-14 Lower temperature: -20°C

Higher temperature: +60°C

Exposure time: 1hour

Change-over time: 5min

Type test report: InteliGen4 200 3


Total duration of test: 5cycles (approx.
10h)

EMC 4-2 ESD EN 61000-4-2 Contact discharge: ±4kV / ±48V


Industrial
Air discharge: ±8kV / ±16kV

Indirect discharge: ±4kV / ±8kV

4-3 Radiated field EN 61000-4-3 ed.3 Severity level: 3

Frequency range: 80MHz to 1GHz


(10V/m), 1,4GHz to 6GHz (3V/m)

Sweep rate: ≤ 1,5x10-3 dec/s (1%/3sec)

Modulation: 80% AM, 1kHz sine wave

Polarization: Vertically and horizontally

4-4 Bursts EN 61000-4-4 ed.2 Severity level: 3

Coupling: Line/earth

Test Voltage (open circuit): 2kV (4kV) /


1kV (2kV)

Polarity: Positive/negative

Repetition rate of pulses: 5kHz

Wave shape of Voltage: 5/50 ns

Burst – duration: 15 msec

Burst – period: 300 msec

Test duration per polarity and test point: 5


minutes

4-5 Surges EN 61000-4-5 ed.3 Severity level: 2

Test Voltage (open circuit): 0,5kV / 1kV

Polarity: Positive/negative

Wave shape of Voltage: 1,2/50µs

Repetition rate: Max. 1pulse /minute

Test duration per test point: Min. 5pulses/


Polarity

4-6 Conducted EN 61000-4-6 ed.3 Severity level: 3


disturbance
Coupling: Line/earth

Type test report: InteliGen4 200 4


Carrier signal (open circuit): 10Veff
(140dBµV)

Frequency range: 150kHz to 80MHz

Modulation: 80% AM, 1kHz sine wave

Sweep rate: ≤ 1,5x10-3 dec/s (1%/3sec)

4-8 Magnetic fields EN 61000-4-8 30A/m continuously

Conducted emissions EN 61000-6-4 ed. 3 2018 ---

Radiated emissions EN 61000-6-4 ed. 3 2018 ---

EMC ETSI ETSI ETSI EN 301 489-1 ---


V2.1.1

Reliability Insulation resistance IEC 61010-1:2010 ed.2 Resistance (PWR – Earth): 5,0GΩ >

IEC 60092-504 Resistance (PWR – CAN): 5,0GΩ >

Functional test on --- ---


simulator

Functional test on gen-set --- ---

High voltage test IEC 61010-1 Generator, mains and bus voltage
measurement connectors:
GL 2012
AC High voltage sinus 2500V/50Hz is
UL508
applied 1 min

or DC High voltage 3111V is applied 1


min

Electrical safety --- ---

Type test report: InteliGen4 200 5

You might also like