R 450 A.V.R.

R 450 FOR SHUNT, AREP or PMG ALTERNATORS

1 - Description

R 450 is an analog A.V.R..


It is designed for alternators with a
SHUNT, AREP or PMG excitation .
R 250 controls the excitation current in order
to maintain the output voltage of the alternator.
R 250 is performant in terms of voltage
regulation, simple to set , to use and is reliable.
Rotating switch for U/f, LAM, excitation type and
voltage sensing are available.

,WLVLQFRPSOLDQFHZLWK,(&VWDQGDUG
and U.L. 508 / C.S.A. approved

2 - Operation range
LSA 40 42.2 43.2 44.2 46.2 47.2 49.1 50.2 51.2

Shunt - - - - - - - - -

AREP - - - - - - - - -

PMG - - - - - - - - -
Operation mode : Standalone

3 - Main feature and characteristics


- Voltage regulation : ± 0.5 %.
- Under-speed protection by function : Voltage
Knee 57 Hz
1 U/f (LAM : OFF). 60 Hz
2 U/f (LAM : MODE1). Knee
Auto-adaptating LAM + 2 U/f (LAM : MODE 2). 48 Hz
100 %
- Nominal excitation current : 6A. U/UN 50 Hz
- Maximum excitation current : 10A during 10 s.
- Supply range 150V (50Hz/60Hz).
9ROWDJHGpWHFWLRQ”9. Frequency
Hz
50 Hz 60 Hz
- Protection : fuse fast 10A.
- Protection on load, short-circuit (1) U/F function
and voltage reference loss.

Transient voltage drop


UN Max. speed drop with
LAM LAM
fN
the shaft (kW)

0,9
Load on

(U/f) 0,9 Variation in the load


without LAM without
0,8 with LAM LAM Load shedding due to LAM
Time 0,8 Time Time

0 1s 2s V 0 1s 2s V
0 1s 2s V
(2) LAM Function

Ref : 4550en-2011.04/a Page 1


R 450 A.V.R.

4 - Opération conditions
- Operating temperature range : - 40° C à + 65° C.
- Storage temperature range : - 55° C à + 85° C.
- Hygrometry : 98%.
- Maximum choc : 9 g on 3 axis..
- Vibrations : less than 10 Hz , 2 mm peak magnitude.
From 10 Hz to 100 Hz : 100 mm/s, below 100 Hz : 8g.

Optional modules compatible


- R 731 : three phase voltage sensing.
- R 734 : 3-phase current and voltage sensing for parallel operation
- R 726 : regulation system changed to “4 - function”

5 - Connexion and setting


Settings are done through the A.V.R.
- Potentiometer P1 : voltage setting.
- Potentiometer P2 : stability setting.
- Potentiometer P3 : excitation.
- Rotating switch selection 1 : frequency, U/F function, LAM function
- Rotating switch selection 2 : alternator type and voltage sensing (1 ph. ou 3 ph.).
- Rotating switch selection 3 : excitation type (AREP or PMG) and time response.
- Potentiometer P4 : quadrature droop.

140 mm

4 holes Ø 6.5 mm 115 mm

50 Hz EXT FREQ
R 450 60 Hz SETTING

P1 Voltage
VOLT.

Rotating switch
LSA 49.1/50.2

LSA 49.1/50.2

ONLY FOR
65Hz

SPECIAL
CONFIG.

EXT.FREQ.
7000/8000 2

7000/8000

LAM OFF
RAPIDE

RAPIDE 3

LAM

LAM
OFF
KNEE

ON
FAST 2

FAST

SERIES

SERIES

- Lam and U/F P2


3 PHASES SENSING

1 PHASE SENSING
SHUNT / AREP

Stability
7

SET.
9

- Voltage
3

78
3PH.

STAB. I EXC
PMG

2
2

3
3

4 56
90 1

- Excitation 0 0
5

0
50Hz
60Hz

1 1 23
1k

1 5000/6000
0 NORMAL

0 LSA 46.2/47.2
1 NORMAL

1
LSA 46.2/47.2
NORMAL

NORMAL

3
2
5000 /6000
SERIES

SERIES

MODE 1

MODE 1
MODE 2

MODE 2
LAM

LAM
LAM

LAM
LAM

LAM
OFF

OFF
S1
S2

P3 Excitation
200 mm

175 mm

STAT.

LEDS

Overrun
P4 indications
Installation & maintenance manual :
www.leroy-somer.com

Quad
FUSIBLES / FUSES

droop
Fuses 10A
SEE NOTICE
VOIR NOTICE

380V 220 110 0V E- E+ Z2 X1 Z1 X2 C US

Ref : 4550en-2011.04/a Page 2