Abstract: This study discusses a new methodology for restoration of overhead distribution networks based on the
application of temporary fault indicators. Unlike the traditional fault indicators, these are installed in the network only
after the occurrence of the fault. Placed in key points of the network after the disconnection of a feeder, for example,
the temporary fault indicators can sense the fault current after the first manual re-closing attempt. Then, they send this
information to a portable operation unit that helps to pinpoint the faulty branch of the network by showing the fault’s
path in a map. All the devices communicate in a ZigBee mesh network and the fault indicators are georeferenced by
global positioning system, which give their location in the network map.
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1434–1437
1434 This is an open access article published by the IET under the Creative Commons
Attribution License (http://creativecommons.org/licenses/by/3.0/)
Fig. 1 Hypothetic overhead distribution network
However, the blocks to be tested are selected by the operation occurrence, the maintenance crew managed to totally restore the
crew not only by following the procedure described above, but network in 24 h, as it can be seen in a previous paper [2].
also based on their failure history and the expertise of the operators. The main feeder was composed of three knife switches and two
For example, from Fig. 1 it can be observed that the distance long rural branches that were connected to it by jumpers. In one of
between the two normally closed switches (switch NC) is very these branches the fault took place.
high. By the expertise of the operators, the block delimited by the By applying the traditional methodology, the maintenance crew
two switches could be split into three smaller blocks if the switched the load blocks and, after restoring power to the most of
jumpers are considered. Then, testing these smaller blocks requires the clients, investigated the two rural branches. These branches
cutting the jumpers off and installing new ones, what takes more demanded the most of the time spent in the restoration.
time than just switching on and off a knife switch. According to a simulation described in that work, if the proposed
methodology was applied, the occurrence would be resolved in 65%
less time.
2.2 Proposed methodology
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1434–1437
This is an open access article published by the IET under the Creative Commons 1435
Attribution License (http://creativecommons.org/licenses/by/3.0/)
Fig. 2 TFI diagram block
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1434–1437
1436 This is an open access article published by the IET under the Creative Commons
Attribution License (http://creativecommons.org/licenses/by/3.0/)
Once the laboratory tests were completed, possible corrections
made and when the TFI body was finished, the whole system will
be tested in the field. For this, a study has been developed with
the sponsor of this research in order to identify critical overhead
distribution networks.
Unlike in the laboratory tests, in the field tests it will be possible to
assess the performance of the system regarding the communication
distance that is affected by the topology and weather conditions.
4 Conclusion
CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 1434–1437
This is an open access article published by the IET under the Creative Commons 1437
Attribution License (http://creativecommons.org/licenses/by/3.0/)