You are on page 1of 1

NOTES:

SAUDIARAMCO.
1. ALL MATERIALS AND FABRICATION SHALL
BE IN ACCORDANCE WITH COMPANY
SPECIFICATIONS.

OF
CONSENT
2. FINAL MAIN CIRCUIT BREAKER SIZE SHALL
BE BY THE PANELBOARD MANUFACTURER.

3. RELEVANT REFERENCE DRAWINGS TO BE ADDED

TTEN
PANELBOARD : LP-002 TYPE : NEMA 4X ENCLOSURE BOTTOM FEED BY DETAIL DESIGN CONTRACTOR.

WRI
SERVICE : 24V DC MOUNTING : SURFACE/BRACKET-INVERTED

THE
BRANCHES : AS INDICATED LOCATION : OUTDOOR UNCLASSIFIED AREA (MAIN DECK-EAST)

THOUT
CIRCUIT CIRCUIT
CABLE BREAKER BREAKER CABLE
LOAD CKT CKT LOAD
LOAD DESCRIPTION NO. NO. LOAD DESCRIPTION

WI
(W) (SIZE) AF AT POLE POLE (SIZE) (W)
AT AF

NG
DRAWI
1 2 HELIDECK PERIMETER/
HELIDECK FLOOD 160 PC-0841 PC-0717

S
2 30 EXIT LIGHTS (34x15W)

THI
2
100 30 2 100 2
510
LIGHTS (4-40W) (50mm ) (50mm ) (LED)
3 4

FROM
(LED)

5 6

NED
OBTAI
SPARE 100 30 2 2 20 100 SPARE
7 8

BE
PART,SHALL
9 10
- 100 20 2 2 20 100 - REFERENCE DRAWINGS
SPARE SPARE
11 12 DWG. CONTROL FOR J.O.

E1L DIAGRAM HELIDECK LIGHTING 24V DC POWER SYSTEM

N
I
13 14

FULL,OR
LIGHTING LAYOUT MAIN DECK AA-037320
SPARE - 100 20 2 2 20 100 -
SPARE
15 CABLE AND CONDUIT SCHEDULE
16

N
I ON
SUB-TOTAL (W) 160 510 SUB-TOTAL (W)

REPRODUCTI
100AF
CONNECTED LOAD (W) 670 2P SOURCE OF POWER:24V DC BATTERY CHARGER BC-009
100AT
(MIN)

SAUDIARAMCO.NO
CONNECTED LOAD (A) 27.92
NOTE 2
+ -
DEMAND FACTOR (%) 100% CIRCUIT BREAKER INTERRUPTING CAPACITY:14KA @ 250VDC

GND BUS
DEMAND LOAD (W) 670 MINIMUM BUSBAR RATING: 100A
PC-0799

OF
27.92 FEEDER SIZE: 1-3/C 70mm 2 DSTA CABLE

PROPERTY
DEMAND LOAD (A) SCALE: NONE

REVISION VALIDATION

SOLE
THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

THE
30004827-0518-002

ARE
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

N
HEREI
ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

RAK RSS RAK RSS


05/15/18 05/15/18 05/15/18 05/15/18

NED
REV.NO. DATE REVISION DESCRIPTION

CONTAI
00 04/15/18 NEW STANDARD DRAWING

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
30004827

ON
CONSTRUCTION UNTIL CERTIFIED AND DATED

NFORMATI
SAUDI ARABIAN OIL COMPANY
DRAWING TYPE

PANEL SCHEDULE

I
STD

THE
AC LTG PANEL LP-001 (400/230V AC)

AND
ALL EQUIP, INSTRUMENT
STANDARDIZED 10-WELL PDM

NG
AND PIPING TAG

DRAWI
NUMBERS ARE PRECEDED
BY PREFIX NO.
STD. DWG SAUDI ARABIA
PLATFORM PREFIX NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

S
THI
XX 990 P AC-037321 008 00
Saudi Aramco 2635 ENG. (05/05)

RESTRICTED VECTOR CADD-05