EM3 - Speed control of DC motor and

sync motor at variable power factor


load
Vishal Raja 20110230

Armature control

Load armature voltage armature current torque rpm


load 0 440 1.05 1 1560
400 1.05 1 1423
360 1.02 0.9 1278
320 1.01 0.9 1147
load 1 440 2.89 5.7 1549
400 2.78 5.5 1417
360 2.66 5.2 1274
320 2.54 4.8 1135
load 2 440 4.64 10.2 1514
400 4.43 9.7 1401
360 4.24 9.2 1284
320 4.02 8.6 1144
load 3 440 6.36 14.5 1570
400 6.05 13.8 1416
360 5.73 13 1284
320 5.43 12.3 1138

Rpm vs armature voltage


Armature current vs armature voltage

Torque vs armature voltage


Learnings

● W (rads-1) = Vt/ (k*phi) - Ra * T/(k * phi)^2

● Speed increases linearly with armature voltage

● For same load connected to the generator, torque is almost constant

● Curve for Ia is similar to T since T = k * phi * Ia

Field control

Load field current armature current torque rpm


load 0 1.7 1.14 1.1 1651
1.6 1.14 1.1 1687
1.5 1.17 1.1 1727
1.4 1.22 1.1 1778
load 1 1.7 2.98 5.7 1619
1.6 3.06 5.8 1652
1.5 3.19 5.9 1697
1.4 3.28 6 1734
load 2 1.7 4.72 10.2 1606
1.6 4.87 10.8 1640
1.5 5.05 10.4 1680
1.4 5.25 10.6 1727
load 3 1.7 6.51 14.6 1603
1.6 6.71 14.8 1635
1.5 6.97 15 1673
1.4 7.27 15.2 1716

Armature current vs field current

Torque vs field current


Rpm vs field current

Learnings:

● W (rads-1) = Vt/ (k*phi) - Ra * T/(k * phi)^2

● As field current increases phi increases

● Torque is almost constant for a load

● Rpm decreases with increases in phi


● Ia = k * phi * T => Ia increases with phi

Sync motor at variable pf load

DC gen ex V field current armature current phase pf


V = 397 I = 2.16 0.6 0.6 147.6 0.9
0.55 0.85 131 0.65
0.7 0.694 142 0.79
0.75 0.954 124 0.56
0.64 0.567 167 0.97
V = 399 I = 1.42 0.55 1.521 156.1 0.912
0.6 1.4 169.7 0.9847
0.64 1.39 173.7 0.9941
0.7 1.48 159.3 0.934
0.75 1.632 147.9 0.846
V = 406 I = 0.72 0.61 0.984 172.6 0.99
0.6 1.011 166.4 0.97
0.7 1.08 154.7 0.9
0.5 1.396 134.9 0.708
0.75 1.283 139.7 0.7635
V = rated I = 0 0.6 0.6 147.6 0.9
0.55 0.85 131 0.654
0.7 0.694 142.5 0.79
0.75 0.954 124.5 0.567
0.64 0.567 167.4 0.97

Armature current vs field current


Pf vs field current

Learnings

● Ia * PF α If * sin(d)

● d is the angle between the stator and the roto fields in sync motor - is depends on the

loading
● When d is changed (load is changed), the pf also changes

● d also changes with change in field current

● Pf is max at d = 90 deg