Client Schedule

Project Reference FE50745 Project Name ZNM Project, DW-4&5


Region/Approval Middle East - BS476

Date Created 13/04/2023 01:03:06 Date Last Changed 14/04/2023 02:43:21 Revision Number 1

Location

Site Address Site Contact Site Phone

Customer Eversendai Engineering LLC Design Code BS 5950

Customer Contact Ashok Kumar T

Project Description

Comments NOTE - The thicknesses quoted within this submission are third party certified under the Warringtonfire Certifire scheme which verifies
the DFT output accuracy of the FIRETEX Design Estimator software

Please note any assumptions (A) and any known comments (K)

1) General
i) Environment - C1/C2. (A)
ii) Floor Construction: Solid Slab. (A)
iii) This offer is based on the Total length (Qty x Length) provided in the BOQ. (A)
iv) Exposure considered as per the markup drawings provided. (A)
v) All items are considered as beams. (A)
vi) Fire protection of the connections (fittings/stiffeners etc) is not included in this offer, these should be coated with the same product and thickness as the parent member
and the paint volume should be included in your own additional calculation for wastage. (K)

120 min - PH 370-90

Reference Section Details Fire Protection Topcoat

Input Group Item Designation BC Cell Nett Exp / Use Data Type CT CT TCF Qty Length Area Hp/A DFT WFT Amount Item DFT Amount
# Area Source (°C) (m) (m²) (µ) (µ) (Litres) (µ) (Litres)
(m²)

1 Zone 1F Sketch-1 UKC 254x254x73 2 3S / B BEAM T18 620 1 59.8 73.7 130 1642 2189 161.3 0 0.00

2 Zone 1F Sketch-2 UKC 203x203x60 2 P/ B BEAM T18 620 1 70.3 30.2 55 853 1137 34.4 0 0.00

3 Zone 1F Sketch-3 UKA 100x100x8 2 3SA B BEAM T18 620 1 112.1 32.5 185 2174 2899 94.2 0 0.00
/
Page 1 of 6
Report generated by: Jijo John (J0G8FG3)

Client Schedule

Project Reference FE50745 Project Name ZNM Project, DW-4&5


Region/Approval Middle East - BS476

Date Created 13/04/2023 01:03:06 Date Last Changed 14/04/2023 02:43:21 Revision Number 1

120 min - PH 370-90

Reference Section Details Fire Protection Topcoat

Input Group Item Designation BC Cell Nett Exp / Use Data Type CT CT TCF Qty Length Area Hp/A DFT WFT Amount Item DFT Amount
# Area Source (°C) (m) (m²) (µ) (µ) (Litres) (µ) (Litres)
(m²)

4 Zone 1F Sketch-3 UKA 100x100x10 2 3SA B BEAM T18 620 1 263.1 76.2 150 1840 2453 187.0 0 0.00
/

5 DW-5 Sketch-3 UKA 100x100x10 2 3SA B BEAM T18 620 1 103.0 29.8 150 1840 2453 73.2 0 0.00
/

6 DW-5 Sketch-3 UKA 100x100x8 2 3SA B BEAM T18 620 1 107.3 31.1 185 2174 2899 90.1 0 0.00
/

7 DW-5 Sketch-4 UKC 203x203x71 2 P/ B BEAM T18 620 1 35.8 27.2 85 1166 1555 42.4 0 0.00

8 DW-5 Sketch-4 UKC 254x254x73 2 P/ B BEAM T18 620 1 142.1 125.2 95 1272 1696 212.3 0 0.00

9 DW-5 Sketch-2 UKC 203x203x71 2 P/ B BEAM T18 620 1 15.2 6.7 50 804 1072 7.1 0 0.00

10 DW-5 Sketch-2 UKC 254x254x73 2 P/ B BEAM T18 620 1 133.1 70.4 55 853 1137 80.1 0 0.00

11 DW-5 Sketch-5 SPEC UKC254x254x73 2 P/ COLUMN T18 550 1 19.0 29.1 135 3043 4057 118.1 0 0.00

12 DW-5 Sketch-6 SPEC MU210A 2 P/ BEAM T18 620 1 6.7 5.1 50 804 1072 5.5 0 0.00

13 DW-4 Sketch-1 UKB 356x171x57 2 3S / B BEAM T18 620 1 46.2 55.4 165 1983 2644 146.4 0 0.00

14 DW-4 Sketch-1 UKB 533x165x74 2 3S / B BEAM T18 620 1 13.2 19.9 160 1936 2581 51.5 0 0.00

15 DW-4 Sketch-7 UKC 203x203x46 2 4S / B COLUMN T18 550 1 3.8 4.6 205 3914 5219 23.9 0 0.00

16 DW-4 Sketch-4 UKC 254x254x73 2 P/ B BEAM T18 620 1 489.8 431.5 95 1272 1696 731.9 0 0.00

17 DW-4 Sketch-2 UKC 254x254x89 2 P/ B BEAM T18 620 1 6.9 3.7 50 804 1072 3.9 0 0.00

18 DW-4 Sketch-2 UKC 254x254x107 2 P/ B BEAM T18 620 1 28.0 15.3 40 705 940 14.4 0 0.00

19 DW-4 Sketch-2 UKC 254x254x132 2 P/ B BEAM T18 620 1 5.0 2.8 35 656 875 2.5 0 0.00

Page 2 of 6
Report generated by: Jijo John (J0G8FG3)

Client Schedule

Project Reference FE50745 Project Name ZNM Project, DW-4&5


Region/Approval Middle East - BS476

Date Created 13/04/2023 01:03:06 Date Last Changed 14/04/2023 02:43:21 Revision Number 1

120 min - PH 370-90

Reference Section Details Fire Protection Topcoat

Input Group Item Designation BC Cell Nett Exp / Use Data Type CT CT TCF Qty Length Area Hp/A DFT WFT Amount Item DFT Amount
# Area Source (°C) (m) (m²) (µ) (µ) (Litres) (µ) (Litres)
(m²)

20 DW-4 Sketch-8 UKPFC 260x75x28 2 P/ B BEAM T18 620 1 23.1 10.0 125 1589 2119 21.2 0 0.00

21 DW-4 Sketch-8 UKPFC 150x75x18 2 P/ B BEAM T18 620 1 13.1 4.2 140 1745 2327 9.8 0 0.00

22 DW-4 Sketch-8 UKPFC 260x75x28 2 P/ B BEAM T18 620 1 76.8 33.3 125 1589 2119 70.7 0 0.00

23 DW-4 Sketch-3 UKA 100x100x8 2 3SA B BEAM T18 620 1 193.9 56.2 185 2174 2899 162.9 0 0.00
/

Theoretical Properties

Product Coated Area Amount Number of Units EPD CO₂e Topcoat Coated Area (m²) Amount Number of Units EPD CO₂e Total
(m²) (Litres) Total kg (Litres) kg
PH 370-90 1,174.17 2,344.44 118 x 20.00 L 6,986.43 Total Coated 0.00 0.00 Overall N/A

Total Coated 1,174.17 2,344.44 Overall 6,986.43 Total Area (m²)

Total Area (m²) 1,174.17

Total Nett Area 1174.17 2344.44 Total Nett Area (m²) 0.00 0.00
(m²) Covered Covered

Total Cellular 0.00 0.00 Total Cellular Nett 0.00 0.00


Nett Area (m²) Area (m²)

Total Gross 4 1949.66


Sided (m²)
Page 3 of 6
Legal Waiver
DISCLAIMER
FIRETEX Design Estimator™ (“the Software”) is the sole property of Sherwin Williams UK Limited (“Sherwin-Williams”) and has been developed with the intention of allowing the user to obtain
guidance as to the volumes and thicknesses of paints required for any particular construction project.

Sherwin-Williams has exercised reasonable skill and care to ensure that, when correctly installed and used in accordance with the instructions provided, the Software should produce accurate
guidance as to the thicknesses and volumes of paints required as verified by the Software's Third Party Verification Certificates (see Verification section below) However, users must
carefully check and verify the results and reliance on the Software is at user's own risk.

The use of Sherwin-William’s “Plug-ins” to derive thicknesses and volumes of paints and/or adjust steel member properties within an associated BIM model is at user’s own risk and users must
carefully check and verify the results.

Please note in particular that, unless alternatively specified, quoted Dry Film Thicknesses (“DFT”) and therefore forecast paint volumes, are based upon accepted industry standard
practices derived from a number of sources, depending on the particular country, market and design code, and the user should take care to verify (and if necessary adjust) the DFTs and
limiting temperatures which it wishes to apply according to its required specification.

The DFTs for cellular beams and fire engineered sections are calculated based upon either limiting temperatures supplied by a third party, upon calculations by Sherwin-Williams or upon data
supplied from Sherwin-Williams’ product specific cell beam testing and assessments. DFTs for these limiting temperatures will be based upon Sherwin-Williams’ own Multi Temperature
Analysis product data. Default values for the limiting temperature of cellular beams specified in the Software may have been derived using a third party supplied calculation module embedded
within the Software and again should be verified (and if necessary, adjusted) by the user according to its required specification. Notwithstanding that the Software may suggest certain default
values for DFT, limiting temperatures or other variables, it remains at all times the responsibility of the user to verify and if necessary alter such values.

Results from the Software and /or the “Plug-ins” referred to above are provided for general guidance only and are without any warranty of any kind express or implied.

Without prejudice to the generality of the foregoing, Sherwin-Williams accepts no liability whatsoever for any losses incurred by inaccurate or unreliable results received from the Software and
which is due to the input by the user of inaccurate, estimated or erroneous data, or by a failure by the user to verify/amend any default or other values which may appear in the Software.

All supplied take-off quantities are based on theoretical figures only and contractor's norms should be included for the calculation of wastage, coatback and other losses.

Contractors must satisfy themselves on the accuracy of the area.

The information contained in this schedule has been produced under the terms of the FDE software license and must not be passed to any third party without written permission from the
licensee or Sherwin-Williams.

Page 4 of 6
Technical Notes

PGE denotes an estimated plate girder (built-up I section) section factor has been used where sufficient data regarding web and flange thicknesses cannot be provided.

FAB denotes a section that has been fabricated from two separate tees, cut from rolled I sections and re-welded to form a fabricated I section profile.

The void above the top flange of a steel beam, where a Trapezoidal metal decking profile has been specified, MAY require fire stopping, please consult the issuer if in doubt.

The DFT for the members regarded and analysed as “Secondary Element ” are calculated as per ASFP's technical guidance.

Please note that the DFTs given in this document MAY have been derived using fire engineering principles (Performance Based Design).

All products in the applied fire protection system must be stored, used (including surface preparation, application and drying) in strict accordance with the product’s data sheet and/or other
written guidance from Sherwin-Williams. The products must not be altered (unless specifically allowed in the data sheet instructions, e.g. thinning) or used after the “use by” date or shelf life
expiry (unless an extension is given in writing).

Sherwin Williams EPD's incorporate modules A1-A5, B1-B7, C1-C4 in accordance with ISO 21930:2017. Therefore, the Life Cycle Assessment (LCA) used for all products is Cradle to Grave ,
it assumes the average life of the building will be 60 years and the coatings are specified accordingly.

Concrete filled hollows - The FIRETEX thickness has been calculated using an approach based on published research (Edwards) which modifies the section factor of the concrete filled hollow
column.

Special Sections (SPEC) - The FIRETEX thickness has been derived from a combination of certified test data, section factor calculation and determined geometry based on a specialist
judgement on how the specific element of construction is utilised.

Verification

The FIRETEX Design Estimator software has been subject to a validation process by Warrington Certification Ltd., and it has been certificated (under WCL certificate reference 648 and 649)
as providing accurate predictions of the fire protection performance of the range of FIRETEX Intumescent Coating covered within the scope of the certification all of which are the subject of
CERTIFIRE product conformity certification or European Technical Assessment (ETA).

The critical temperature of composite beams with web openings is calculated by a module developed by Warrington Certification Ltd. in accordance with SCI RT1356 and it has been
independently verified by Manchester University, UK. The extension to analyse non-composite beams has been developed based on SCI RT1356 and the principles are also independently
verified by Manchester University. The Fire Engineering module that calculates the critical temperature of steel columns and braces has been verified by Manchester University and
Warrington Certification Ltd. independently.

The certification provides for an ongoing review and maintenance of the software as the range of products covered change or as their certificated scope changes. Full up-to-date details of the
scope of the certification can be found on the WCL website at www.warringtoncertification.com.

Page 5 of 6
Key
Exp = Exposure
3S = 3-Sided, 4S = 4-Sided, 3SA = 3-sided A, 3SB = 3-Sided B, P = Partial Exposure, F = Full, MSA = Mid-Span A, MSB = Mid-Span B, EdA = Edge A, EdB = Edge B (A & B represents the
different orientations)
Use = Section Use
B = Beam, EB = Edge Beam, C = Column, Br = Fully Loaded Brace, S = Secondary
BC = Building Category
TCF = Trapezoidal Composite Floor with unfilled voids
CT = Critcal (or Limiting) Temperature
PSD = Project Specific Design
T16/T18 refers to the Critical/Limiting Temperature tables for UK use taken from the ASFP Yellow book
EPD CO2e = Environmental Product Declaration CO2 equivalence
N/A = Not Available

FM 828 ISO9001, ISO14001

Page 6 of 6

You might also like