EES 10/03/2016 10:48:39 Page 1


EES Ver. 6.883: #434: For use only by Kwangil Kim of Samsung Electronics Co.

Calculate
Supply conditions
3
qva = 1814400 [m /h]
Ts = 33.1 [°C]
RHs = 80.9 [%]
Building cotations
H= 4.0 [m]
L= 168.0 [m]
P= 100.0 [m]
-1
a= 27 [h ]
Textile industries 25 – 29
Manufacturing industries 18 – 22
Plastic materials industries 30 – 35
Paintshops 25 – 30
Foundries 25 – 30
Workshops 22 – 25
Ovens 20 – 25
Ambiant conditions
Restaurants 18 - 22
Pa= 1.013 [bar]
Bars and cafés 18 - 22
Te= 45.0 [°C] Wineries 18 - 22
RHe= 35.0 [%] Wine bars 30 – 40
Discos and pubs 25 – 29
sat= 80.0 [%]
Cinemas and theaters 14 – 18

pump flow
qvp = 32.64 [L/s]

p= 80.0 [%]


qve = 2612 [L/s]

Unit Settings: [kJ]/[C]/[bar]/[kg]/[degrees]


p = 80.0 [%] sat = 80.0 [%] H = 4.0 [m]
he = 100.4 [kJ/kg] L = 168.0 [m] P = 100.0 [m]
Pa = 1.013 [bar] qma = 536.491 [kg/s] qme = 2.612 [kg/s]
qva = 1814400 [m3/h] qve = 2612 [L/s] qvp = 32.64 [L/s]
s = 1.064 [kg/m ] RHe = 35.0 [%] RHs = 80.9 [%]
3

re = 21.33 [g/kaas] rs = 26.2 [g/kaas] rsat = 27.41 [g/kaas]


a = 27 [h ] Te = 45.0 [°C] Ts = 33.1 [°C]
-1

Tsat = 30.12 [C] V = 67200 [m3]