You are on page 1of 16

Original Paper

Indoor and Built


Environment
Indoor and Built Environment
0(0) 1–16

An investigation of the cooling ! The Author(s) 2019


Article reuse guidelines:

performance of air-conditioning sagepub.com/journals-


permissions
DOI: 10.1177/1420326X19891645
systems in seven Chinese hub journals.sagepub.com/home/ibe

airport terminals

Xiaochen Liu1, Xiaohua Liu1,2, Tao Zhang1 and


Lingshan Li1

Abstract
Airport terminals are key infrastructures with rapid development currently, where the air-conditioning
(AC) systems aim to guarantee the normal operation. This research investigated the AC systems in
seven Chinese hub airport terminals by a large-scale on-site measurement. The average annual
electricity consumption was 177 kWh/(m2  year), in which 30–60% was consumed by AC systems.
The terminal device of AC systems is one of the key components restricting the cooling performance.
The commonly used terminal devices (i.e. air handling units) accounted for 40–74% of the AC electricity
consumption. As an alternative, the AC system combining radiant floor and displacement ventilation
could save 34% of the AC electricity consumption in one investigated airport terminal. Furthermore, the
designed cooling capacities were 132–176 W/m2, while the measured values were only 43–90 W/m2.
Thus, the AC systems, especially the terminal devices, should have the ability to adjust cooling capacity
over a wide range to cope with this prevailing situation of low load rates. This study is beneficial for the
design and operation of AC systems in airport terminals.

Keywords
Airport terminal, Air-conditioning system, Cooling performance, Energy consumption, On-site measurement
Accepted: 9 November 2019

Introduction
energy consumption, the indoor environment in airport
The civil aviation industry has maintained a rapid terminals is always less than satisfactory.8,9 Therefore,
development throughout the world in recent years. how to improve both indoor environment and energy
More than 4 billion passengers chose to travel by air efficiency is an urgent topic in the design and operation
in 2017, in which China had the highest growth rate of of the air-conditioning systems in airport terminals.
14% in top-ten countries or groups.1 As critical infra- Airport terminals are public buildings with special
structures for civil aviation, airport terminals are functions to meet the requirements for civil aviation;3
experiencing rapid development in China. More than
70 new airport terminals are to be built and more than 1
Department of Building Science, Tsinghua University, Beijing,
100 airport terminals are to be retrofitted in the 13th
China
five-year plan period (2016–2020).2 Previous research 2
Beijing Key Laboratory of Indoor Air Quality Evaluation and
indicates that the energy consumption of airport termi- Control, Tsinghua University, Beijing, China
nals is usually higher than that of common civil build-
Corresponding author:
ings,3,4 and 40–80% of the energy is consumed Tao Zhang, Department of Building Science, Tsinghua
by heating, ventilation and air-conditioning (HVAC) University, Beijing 100084, China.
systems.5–7 Even though with such a high level of Email: zt2015@mail.tsinghua.edu.cn
2 Indoor and Built Environment 0(0)

besides, they are generally designed to be large space Moreover, the control method of air-conditioning sys-
buildings with high ceilings and large areas of glazing tems is also important in actual operation. Fan et al.22
envelopes.6 These characteristics differentiate them presented an exergy analysis method to evaluate the
from common types of buildings (such as offices and operation performance of the HVAC system in an air-
residences), especially for the indoor environment. port of Haikou, China, which could give directions for
Researchers have investigated the indoor environment optimal control. Huang et al.23 proposed a hybrid
in airport terminals over the world and analysed the model predictive control (HMPC) scheme for energy
main reasons leading to thermal discomfort in summer, and cost savings in Adelaide Airport T1, Australia,
including high globe temperature caused by high- by which a considerable amount of energy has been
temperature envelopes, overheating/overcooling caused saved without violating thermal comfort. Although
by air-conditioning systems, and high humidity caused many researchers have studied novel technologies and
by air infiltration.6,8–11 To create a satisfactory indoor forms of air-conditioning systems in airport terminals
environment, terminal devices of an air-conditioning over the world, there is still a lack of long-time and
system are significant in large spaces of airport termi- large-scale on-site measurements to reveal the actual
nals, which determine the airflow distribution and influ- operation situations of air-conditioning systems in cur-
ence the cooling load. Jet ventilation with nozzle outlets rent airport terminals and analyse common problems,
is commonly used in airport terminals6 and other large especially in China with such a rapid development of
space buildings, such as a stadium12 and a railway sta- airport terminals.
tion.13 Moreover, various types of new terminal devices In this study, comprehensive on-site measurements
were proposed and used in large spaces of airport ter- from 2013 to 2018 were summarised to investigate the
minals to improve the cooling performance, such as the performance of air-conditioning systems in seven
displacement ventilation in the new terminal of Madrid Chinese hub airport terminals. The results were ana-
Airport14 and the radiant floor supplemented by dis- lysed in detail to determine the key issues restricting the
placement ventilation in New Bangkok Airport15 and performance and possible solutions were also pro-
Xi’an Xianyang International Airport.16 Previous posed. The present analysis would be beneficial to the
research mainly focused on the indoor environment in construction and operation of air-conditioning systems
the occupant zones of airport terminals; however, the in airport terminals.
indoor environment of the entire large spaces with var-
ious types of terminal devices has not been investigated
and compared in detail, which is closely related to the Basic information of measurements
cooling load of air-conditioning systems. The cooling performance in airport terminals was
Furthermore, energy efficiency is the other significant determined by the indoor environment in terminal
aspect to evaluate the cooling performance of air- buildings and the energy performance of key devices
conditioning systems in airport terminals. The energy in air-conditioning systems. On-site measurements
efficiency of devices in air-conditioning systems or a were performed in seven Chinese hub airport terminals
cooling plant as a whole is usually defined as an to give a comprehensive view of the cooling perfor-
output–input ratio which refers to the ratio of cooling mance. Besides, the design parameters and measure-
capacity and electric power consumption, such as coeffi- ment results of some other Chinese airport terminals
cient of performance (COP) of a chiller and energy effi- in literature were also collected for comparison.
ciency ratio of a cooling plant (EER).17,18 These indexes
have been widely used to evaluate the energy perfor- Air-conditioning systems in the measured
mance of air-conditioning systems, such as benchmark-
airports
ing energy performance for cooling in large commercial
buildings.19 Based on these indexes, new forms of air- Table 1 shows the seven terminals of three Chinese hub
conditioning systems have been designed to improve airports (A, B and C) for the on-site measurements.
the energy performance of airport terminals. Sun For example, A1, A2 and A3 are three different termi-
et al.20 proposed to integrate the chilled water system nals in the same airport, but they were constructed in
of Hong Kong International Airport into neighbouring different years, resulting in various forms of architec-
buildings, which improved the energy efficiency of the tural spaces and air-conditioning systems. Figure 1
cooling plant in partial load conditions. Zhang et al.21 illustrates the outdoor temperatures for HVAC designs
utilised thermal energy storage (TES) equipment in the in the top 20 Chinese airports.24 Although these air-
building cooling heating and power (BCHP) system of ports are located in various climate zones of China,
Qingdao International Airport, and then optimised the their design/extreme outdoor temperatures in summer
strategy to operate electrical chillers, TES equipment are quite similar compared with those in winter.
and absorption chillers in various load conditions. Thus, the on-site measurements in the selected airport
Liu et al.

Table 1. Information of airport terminals investigated in this research.

Airport terminal A1 A2 A3 B1 B2 C2 C3

Passengers in 2017 (million) 95.8 49.8 41.9


Climate zone Cold Hot Summer-Cold Winter Cold
Constructed year 1980/2004 1999 2008 2001 2012 2003 2012
On-site measurement year 2018 2018 2014 & 2018 2017 2017 2013 & 2017 2013 & 2017
Floor area (thousand m2) 60 336 986 130 330 84 244
Indoor height (m)
Check-in hall 5–8 16–26 9–27 10–25 14–26 8–19 1827
Departure hall 5–6 6–16 10–18 6–14 6–15 8–15 711
Terminal devices in large spaces AHU þ AHU þ AHU þ AHU þ AHU þ AHU þ HLDP þ DV;
of airport terminala jet nozzle jet nozzle jet nozzle jet nozzle jet nozzle jet nozzle RF þ dry FCU
Distance between energy centre 1.0–1.2 0.6–1.0 0.5–2.5 0.9–1.1 0.3–0.5 0.2–0.4 0.81.0
and airport terminal (km)
Cold source in energy centre CC CC CC SACþCC CCþDFAC CCþice storage CCþice storage
Photo of terminal building

AHU: Air handling unit; CC:centrifugal chiller; DFAC: direct fired absorption chiller; SAC: steam absorption chiller; HLDP: heat pump-driven liquid desiccant processor; DV: displacement
ventilation; RF: radiant floor; FCU: fan coil unit.
a
Air-conditioning systems in other areas of the airport (i.e. offices, air bridges, data centres) were not included.
3
4 Indoor and Built Environment 0(0)

Figure 1. Design and extreme outdoor temperatures for the HVAC systems at the top 20 airports in China.24

Figure 2. Schematic diagram of air-conditioning systems in airports.

terminals can reveal the typical cooling condition in air-conditioning systems with the radiant floor (RF)
Chinese hub airport terminals. A district cooling/heat- and displacement ventilation (DV), as shown in
ing system is commonly adopted in an airport area, as Figure 3(c), have been introduced into large spaces of
illustrated in Figure 2, which consists of terminal devi- airport terminals, which can further decrease the air-
ces in an airport terminal, a distribution system and an conditioning controlled space to be about 2 m high.
energy centre. The cold sources of air-conditioning systems are
In airport terminals, occupants’ activities almost usually located in the energy centre (i.e. cooling
occur in the space within about 2 m above the floor, plant), as shown in Figure 2. Centrifugal chillers are
while airport terminals are usually designed to be large often utilised as cold sources, which are supplemented
space buildings. The maximal indoor height of the by absorption chillers in some airports, such as B2.
check-in halls in these measured airport terminals can Besides, the ice storage technology is also applied in
reach 27 m, and that of the departure halls is 18 m (A3 some airport terminals like C2 and C3, which aims to
in Table 1). There are three commonly used forms of optimise the installed cooling capacity of district cool-
terminal devices in large spaces of these airport termi- ing systems. The energy centres are typically located
nals, as shown in Figure 3. The airport terminals, 0.3–2.0 km away from their respective airport termi-
which were constructed in the early years, usually nals. Therefore, multistage pumps are generally
adopted the entire space air-conditioning systems, as designed in the distribution system to supply chilled
shown in Figure 3(a), which means the entire indoor water from the energy centre to the airport terminal.
space is cooled. To reduce the air-conditioning con- Figure 4 illustrates the design parameters of typical
trolled space for energy saving, the stratified air- cooling plants in the measured airport terminals and
conditioning systems, as shown in Figure 3(b), are some other Chinese airport (i.e. D to J).27–33 The
most widely used nowadays in airport terminals. The chilled water with a temperature difference of 5 K
jet nozzles are installed in the side walls (such as check- (i.e. 7  C supply and 12  C return) is commonly
in counters), and the air-conditioning controlled space adopted, especially in those airport terminals built in
is 4–6 m high. Moreover, the occupant zone early years. However, to reduce the energy
Liu et al. 5

Figure 3. Typical terminal devices of HVAC systems in large spaces of airport terminals: (a) entire space air-conditioning (jet
ventilation), (b) stratified air-conditioning (jet ventilation) and (c) occupant zone air-conditioning (RF þ DV).

Figure 4. Design parameters of typical cooling plants in Chinese airport terminals: (a) chilled water temperature and
(b) cooling capacity.

consumption of chilled water distribution systems, the On-site measurement method


design temperature difference of supply and return
The time of on-site measurements in the seven airport
chilled water increases to be 6–13 K in some airports,
such as C2 and C3. Furthermore, the design cooling terminals (shown in Table 1) was June, July and
capacity per air-conditioning controlled area in these August of 2013, 2014, 2017 and 2018, which can rep-
airports ranges from 122 W/m2 to 231 W/m2 with an resent the typical situation in summer. The on-site
average value of 169 W/m2, as shown in Figure 4(b), measurements were carried out simultaneously in the
which indicates a high level of cooling demand in air- cooling plant and the terminal building of each airport
port terminals. terminal to investigate the indoor environment in these
6 Indoor and Built Environment 0(0)

terminal buildings and the energy performance of key Qc


WTFcwp ¼ (3)
devices in their air-conditioning systems. Pcwp
The indoor environmental parameters, including air
temperature, relative humidity, air velocity and CO2 Qc
WTFct ¼ (4)
concentration, were measured in each of the airport ter- Pct
minals. For occupant zones, the indoor environmental
sensors were located 1.5 m above the floor in typical where P is the power consumption; the subscripts chw,
areas of each airport terminal, including check-in hall, cwp, ct and gl refer to chilled water pumps, cooling
departure hall, arrival hall, security check area, baggage waters pump, cooling towers and glycol pumps, respec-
claim area, restaurant and shop. Besides, a series of tively (W); Qe and Qc is the cooling capacity in evapo-
sensors was hung in the centre of each check-in hall to rators and condensers of chillers (W).
measure the air temperature and relative humidity at The energy performance of AHU was evaluated by
different heights of large airport hall spaces. The previ- air transport factor (ATF),18 as shown in equation (5)
ous research in airport terminal B26 has described the
QAHU
measurement method and locations of all sensors in ATF ¼ (5)
detail, which is also applied to other airport terminals PAHU
in the current research.
The key devices in air-conditioning systems include where QAHU is the cooling capacity of AHUs (W) and
chillers, air-conditioning water pumps, cooling towers PAHU is the power consumption of AHUs (W).
and air handling units (AHUs). The measurement Moreover, the energy performance of the cooling
methods of these devices are described in the online plant as a whole was evaluated by energy efficiency
Appendix in detail. The energy performance of these ratio (EER),18,19 which is defined to be the ratio of
devices can all be equally compared using the output– the cooling capacity to the power consumption in a
input ratio, which refers to the ratio of the cooling cooling plant, as equation (6).
capacity to the electric power consumption. To be spe-
Qe
cific, the energy performance of chillers can be evalu- EER ¼ (6)
ated by the coefficient of performance (COP), which is Pch þ Pchw þ Pcwp þ Pct þ Pgl
defined as equation (1).
All the parameters mentioned above were measured
Qe continuously at 10-min intervals during each period of
COP ¼ (1)
Pch the on-site measurement. The measurement devices and
their accuracies are shown in Table 2. The air tempera-
where Qe is the cooling capacity of evaporators of chillers ture and relative humidity were measured using a com-
(W) and Pch is the power consumption of chillers (W). bined resistance temperature detector (Pt RTD) and a
Similarly, the transport factors of other key devices lithium chloride relative humidity sensor (LiCl RHS), by
can be defined as dimensionless ratios according to which the humidity ratio of air was also determined (rel-
COP of chillers to indicate their energy performance. ative accuracy within 10%). Besides, the energy con-
The water transport factors (WTF)18,19 of air- sumption data and the electric power of the devices in
conditioning water pumps and cooling towers are the air-conditioning systems (such as chillers, pumps,
defined as equations (2) to (4). cooling towers, and AHUs) were all obtained from the
building automation system of each airport terminal.
Qe The outdoor meteorological parameters were collected
WTFchw ¼ (2)
Pchw þ Pgl from the weather stations in these airports.

Table 2. Specifications of the measurement devices.

Parameter Device Accuracy Operational range



Air/water temperature Pt PTD 0.2 C 20 to 80 C
Air relative humidity LiCl RHS 3% 10–90%
Air velocity Hot wire anemometer 0.03 m/s 0–10 m/s
CO2 concentration CO2 concentration data logger 50 ppm 0–5000 ppm
Water flow rate Ultrasonic flow meter 1% 0–3  106 m3/h
Liu et al. 7

Indoor environment in large spaces psychrometric chart. The measured data were compared
with the Chinese thermal comfort standard,24 which
Thermal environment and indoor air quality are two
requires the indoor environment to be controlled
essential factors of the indoor environment in airport
within 24–27  C and 40–70%. As shown in Figure 5,
terminals; thus, in this section, the on-site measurement the requirement of temperature could be basically met
results of indoor temperature, humidity and CO2 con- except for over-heating sometimes in the restaurants and
centration are presented. shops, and over-cooling sometimes in the departure halls
and the arrival halls in these airports. Besides, the
Temperature and humidity indoor humidity was not strictly controlled in these air-
port terminals. Airport terminal A1, A2, A3 and B2
The indoor thermal environment in the airport were too humid while some parts of airport terminals
terminals indicates the controlling performance of C2 and C3 were over-dehumidified. The performance of
air-conditioning systems. Figure 5 illustrates the dehumidification in airport terminals in summer is relat-
indoor temperature and humidity in the typical occu- ed to the temperature of chilled water, which were ana-
pant zones of the measured airport terminals. The atmo- lysed and discussed in the ‘Discussion’ section.
spheric pressures at airport B (95.75 kPa) and C Figures 6 and 7 illustrate the vertical distribution of
(95.71 kPa) were very close; thus, the data of airport air temperature and humidity ratio in large spaces of the
terminals B2, C2 and C3 were plotted in the same check-in halls, respectively. The air temperature and

Figure 5. Air temperature and humidity in occupant zones of airport terminals: (a) A1, A2 and A3 (atmospheric pressure:
99.99 kPa), and (b) B2, C2 and C3 (atmospheric pressure: 95.73 kPa).

Figure 6. Vertical distribution of air temperature in the check-in halls of airport terminals: (a) A2, (b) B2, (c) C2 and (d) C3.
8 Indoor and Built Environment 0(0)

Figure 7. Vertical distribution of humidity ratio in the check-in halls of airport terminals: (a) A2, (b) B2, (c) C2 and (d) C3.

Figure 8. CO2 concentrations in the occupant zones of the airport terminals.

humidity were measured and recorded when the outdoor been explained in our previous research, that was due to
temperature was close to their respective design values the dominant buoyancy-driven flow of air infiltration in
during the on-site measurement. The light blue areas in the large space of an airport terminal.6 The research had
these figures indicate air-conditioning controlled spaces confirmed that the outdoor air infiltrates through the
in each check-in hall, which have been illustrated previ- walkway doors and skylights at the top and flows out
ously in Figure 3. Each of the large space has a non- through the opening gates on different floors in the
uniform indoor environment in the vertical direction, space cooling condition. Besides, the air temperature
which shows obvious thermal and humidity stratifica- at the upper space would be even higher than the out-
tions. The air temperature and humidity were relatively door air temperature, which had resulted from the solar
uniform in the air-conditioning controlled spaces in the irradiation on the roofs in the daytime and some heat
airport terminals A2, B2 and C2, where the jet ventila- sources (such as lights) in the upper spaces.
tion with nozzle outlets were applied in all these places.
As for airport terminal C3 in Figures 6(d) and 7(d), the
CO2 concentration
radiant floor and displacement ventilation, which direct-
ly produced cooling of the bottom of the indoor space, Figure 8 illustrates the CO2 concentrations in the typ-
had created obvious thermal and humidity stratifica- ical occupant zones of the measured airport terminals
tions even in the occupant zones. Furthermore, the air during the operation time, which indicates the freshness
temperature and the humidity at the upper space were of indoor air. The average values of CO2 concentration
all higher than those in the occupant zones and close to in the measured airport terminals were 563–688 ppm.
their respective outdoor values. These distributions had During the majority of the time, CO2 concentrations
Liu et al. 9

were below the upper limit (1000 ppm) stipulated by the As shown in Table 1, centrifugal chillers are the
Chinese standard, GB50736–2012.24 Those data most widely used type of chillers in the measured air-
exceeding the standard were measured in the security port terminals. The COPs of the centrifugal chillers in
check areas which have high occupant densities. The the measured airport terminals are all listed in Table 3.
common situation of low CO2 concentrations reflects The COP in the chilled water condition ranges from 3
the introduction of excessive outdoor air in these air- to 7. Furthermore, the COP is closely related to the
port terminals. These on-site investigations showed operating condition of chillers, especially the tempera-
that the opening of the mechanical fresh air valves in ture of chilled water in evaporators and the tempera-
the AHUs almost maintained at a low level (0–15%). ture of cooling water in condensers. Figure 11
Thus, there was a considerable amount of unorganised illustrates the influence of the chilled water temperature
outdoor air infiltrating into the airport terminals, and cooling water temperature on centrifugal chillers’
which was also confirmed in the case study.6 COP in airport terminals A1, A2, B2, C2 and C3.
The outlet temperature of chilled water was about
Energy performance of 6–14  C and the inlet temperature of cooling water
air-conditioning systems was about 25–34  C. An operating condition with
higher chilled water temperature and lower cooling
Figure 9 illustrates the electricity consumption in the water temperature could increase the COP of centrifu-
measured airport terminals. The average annual elec- gal chillers. However, the designed temperature of
tricity consumption per floor area was 177 kWh/ supply chilled water was about 3–7  C, as shown in
(m2  year), which was 2.2 times the value of commercial Table 1, which determined the cooling and dehumidi-
office buildings in China.34 About 30–60% of the total fication ability of terminal devices in airport terminal
electricity was consumed by air-conditioning systems in buildings. Therefore, although a higher chilled water
these airports (i.e. the equipment in cooling plants and temperature has the potential to improve the perfor-
the terminal devices in airport terminals). Thus, the mance of centrifugal chillers, it may burden the termi-
energy performances of cooling plants (i.e. chillers, nal devices in airport terminal buildings and influence
air-conditioning water pumps and cooling towers) the indoor thermal environment, which were further
and terminal devices in large spaces of airport terminals analysed and discussed in the ‘Discussion’ section.
were determined and evaluated during a typical week in As for the ice storage systems (such as in C2 and
the cooling season (Figure 10). C3), the COP of the chillers is only about 2–4 in the ice
storage condition, as shown in Table 3. The outlet tem-
Key devices in cooling plants perature of glycol (as the refrigerating medium) ranges
The task of a cooling plant is to supply chilled water to from 4.9  C to 0.1  C in the chillers of C2 and C3.
its corresponding airport terminal; therefore, the chill- Thus, there is a lower evaporation temperature of chill-
ers, as the cold source of air-conditioning systems, have ers in the ice storage condition than that in the chilled
an essential influence on the energy performance of water condition, which leads to a lower COP.
cooling plants. However, the ice storage system has advantages in

Figure 9. Annual electricity consumption in typical airports: (a) total electricity consumption and (b) electricity consumption
of air-conditioning systems.
10 Indoor and Built Environment 0(0)

Figure 10. The outdoor temperature and total cooling capacity per air-conditioning controlled area in the measured air-
ports: (a) A1, (b) A2, (c) A3, (d) B2, (e) C2 and (f) C3.

Table 3. Energy efficiency performance of main devices in air-conditioning systems of studied airports.

A1þA2 A3 B2 C2 C3 D27 E28 F29

Tout( C) 20–34 25–36 23–36 24–40 24–37 28–33 28–37 28–36


COPa 5.5–6.4 5.4–5.6 4.8–5.3 ice: 2.7–3.8 ice: 2.9–4.0 4.3–4.9 4.7–5.9 4.2–5.5
water: 3.0–4.9 water: 4.0–5.5
WTFchw 44–56 53–55 45 36–42 63 19–57 / /
WTFcwp 53–64 54–57 43 26–27 32 34–50 / 53–73
WTFct 119–131 120–140 150–250 61–71 119 191–240 / 52–110
EER 4.6–4.9 4.2–4.4 3.9–4.2 1.7–2.9 2.0–2.7 3.0–3.5 / /
ATF 2.3–6.3 6.7–14.9 4.9–20.8 3.8–16.6 10.6–22.0 / / /
a
It refers to COP of centrifugal chillers and the performance of absorption chillers is not included here.

Figure 11. COP of centrifugal chillers in the chilled water condition in the measured airports: (a) A1 and A2, (b) B2, (c) C2
and (d) C3.
Liu et al. 11

shifting power consumption at peak hours during the airport terminals. Since chillers account for about
daytime to the nighttime and reducing the total 70–90% of the total electricity consumption in cooling
installed capacity of chillers. plants of measured airport terminals, the improvement
Since there is always a long distance between the of the cooling efficiency of chillers is significant for
cooling plant to the airport terminal building, the dis- energy saving in the cooling plants of airports.
tribution system of the air-conditioning system also
needs to be investigated in detail. The WTF of key Terminal devices in large spaces
devices in the measured airport terminals are also
As shown in Table 1, AHUs with jet nozzles are the
listed in Table 3. The WTF of chilled water pumps
(chw) and cooling water pumps (cwp) were all about most commonly adopted terminal devices in large
20–70, which means the energy consumption propor- spaces of the measured airport terminals. The perfor-
tions of these two parts are similar. Besides, according mance parameters of AHUs in airport terminals A1,
to the recommended standard,18,19 the minimum limit A2, A3 and B2 are illustrated in Figure 12, which takes
values of WTFchw and WTFcwp are 35 and 30 respec- the volume flow rate of air as the X-axis. The design
tively, which means the air-conditioning water pumps overpressure of supply air (Dp) was about 400–900 Pa,
in the measured airport terminals almost worked in which had resulted in the high electricity consumption
good conditions. The WTF of cooling towers (ct) of fans in AHUs. The designed ATF almost ranged
ranged from 50 to 250, which was obviously higher from 5 to 30 while the measured ATF was lower
than those of the air-conditioning water pumps. (2–20); and the ATF in the recommended standard
Furthermore, all the WTF of key devices in the distri- given by GB/T 17981–200718 is 8. The physical mean-
bution systems were higher than the COP of chillers. ings of chillers’ COP and AHUs’ ATF are quite similar,
Thus, the distribution system would have less influence but the ATF was close to or even lower than the COP
on the total energy consumption of the cooling plant in our on-site measurements, as shown in Table 3.
than the chillers. Therefore, the energy efficiencies of chillers and
Furthermore, the EERs of the cooling plants in the AHUs are equally important for the energy conserva-
measured airport terminals are also listed in Table 3. tion of air-conditioning systems in airports.
The EER of these cooling plants ranges from 1.7 to 4.9. Furthermore, the temperature of chilled water from
Concerning the recommended cooling plant efficiency the cooling plant can influence the performance of
in the literature,35 the EER higher than 4.25 is at a AHUs. Figure 13 illustrates the temperature of chilled
good level, while those lower than 3.5 need to be water or glycol in various locations of the HVAC dis-
improved. Airport terminals A1 and A2 shared a cool- tribution systems. First of all, large temperature differ-
ing plant, and their cooling plant efficiency was at a ences between outlet chilled water of chillers and inlet
good level, because they supplied high-temperature chilled water of AHUs generally existed in the mea-
chilled water (10.3–15.6  C). Besides, airport terminals sured airport terminals. The chilled water mixing
C2 and C3 were all installed with ice storage systems (such as bypass water from non-working chillers and
and had low COP of chillers, which led to an obvious the balance pipe of the distribution system) raised the
lower EER of cooling plants than other measured chilled water temperature from chiller and decreased

Figure 12. Performance parameters of AHUs in airport terminals: (a) A1, A2 & A3, and (b) B2.
12 Indoor and Built Environment 0(0)

Figure 13. The temperature of chilled water (glycol) in various locations of air-conditioning distribution systems.

the cooling and dehumidification ability of AHUs. The with centrifugal chillers plus the jet ventilation with
inlet chilled water temperature of AHUs in airport ter- nozzles outlets in large spaces of the airport terminal
minals A1 and A2 were 11.6–16.4  C and 12.9–16.5  C, building (A1, A2, B2, D and K), in which the terminal
respectively, while the design values were all 7  C, as devices contributed 40–74% of the total electricity con-
shown in Figure 4, which can explain the high humidity sumed by air-conditioning systems. Therefore, there is
level of the indoor environment in these airport termi- a need for a further consideration on the energy per-
nals, as previously shown in Figure 5. Besides, formance of terminal devices.
although the high temperature chilled water could ben- First of all, as was mentioned before, there is a
efit the COP of chillers, it reduced the cooling and trade-off between the energy performance of cold sour-
dehumidification ability of AHUs, which resulted in ces (chillers) and terminal devices (AHUs). For exam-
extremely low ATF of 2.3–6.3. Therefore, there is a ple, the cooling plant of airport terminal A1 and A2
trade-off between the COP of chillers and ATF of supplied high temperature chilled water, and the elec-
AHUs, which is determined by the chilled water tricity consumption of terminal devices is 57 kWh/
temperature. (m2yr), which is much higher than that of the cooling
plant (20 kWh/(m2yr)). As for B1, B2, C2, D, G and K,
the electricity consumption of terminal devices is
Discussion only 22–44 kWh/(m2year). Therefore, the chilled
Based on the on-site measurement of the indoor envi- water temperature in conventional air-conditioning
ronment and the energy performance of air- systems of airport terminals should not be set too
conditioning systems, the typical operation situation high. This would probably improve the performance
of air-conditioning systems in airport terminals can of chillers, but at the expense of the energy perfor-
be concluded, and some key issues need to be discussed mance of terminal devices (Figure 12) and even the
further in order to improve the energy efficiency. indoor thermal environment (Figure 5).
Furthermore, new types of terminal devices, such as
High energy consumption of terminal radiant floor and displacement ventilation, have
lower energy consumption than the conventional
devices in airport terminals
type (jet ventilation with nozzle outlets). As shown in
Chillers are commonly believed to consume the largest Figure 9(b), the electricity consumption of terminal
proportion of electricity in air-conditioning systems. devices in airport terminal C3 was only 9 kWh/
However, the terminal devices in airport terminals (m2year), which saved 34% of the air-conditioning
sometimes have higher electricity consumption than electricity consumption compared with the average
those of chillers. Figure 9(b) illustrates the composition value. There are several reasons for this energy-saving
of electricity consumed by air-conditioning systems in potential. First, the radiant floor and displacement ven-
measured airport terminals and the airport terminals tilation system only controlled the occupant zones,
D,27 G30 and K7 from the literature. Except for airport which could significantly reduce the air-conditioning
terminal B1 which was predominantly cooled by controlled space in airport terminals, as shown in
absorption chillers, chillers accounted for 21–47% of Figures 3 and 6. Besides, previous research36 also
the electricity consumption while terminal devices pointed out that radiant floors could achieve outstand-
accounted for 20–74%. The most widely adopted ing performance, especially in operating cooling loads
type of air-conditioning system is the cooling plant caused by solar irradiation and high-temperature
Liu et al. 13

envelopes, which are intensive in large spaces with glaz- Discrepancy of capacities between cold
ing envelopes in airport terminals. Moreover, the essen- sources and terminal devices
tial difference between these two terminal devices is the
flow medium to transport cooling capacity. Radiant In the design process of air-conditioning systems, the
floors use high-temperature chilled water to transport cooling loads of terminal devices in each area of an air-
cooling capacity directly to the indoor space. On the port terminal were calculated respectively with the con-
other hand, the air in AHUs is cooled and dehumidified sideration of the worst condition (i.e. the most crowed,
hottest, the most intense solar radiation). Then, these
by the chilled water first and then supplied to the
designed cooling capacities were directly summed up
indoor space. Therefore, a similar definition of water
to obtain the designed cooling capacity of the cold
transport factor of radiant floors (WTFRF), as shown in
source in the cooling plant. Figure 10 illustrates the mea-
equation (7), can be used to perform a comparison of
sured and designed cooling capacity of a typical week in
energy performance with the ATF of AHUs.
the cooling plants of airport terminals A1, A2, A3, B2,
QRF qw Gw cp;w  DTw qw cp;w  DTw  gw C2 and C3. The designed cooling capacity per air-
WTFRF ¼ ¼ Gw  Dpw
¼ conditioning controlled area ranged from 132 W/m2 to
PRF Dpw
g w 176 W/m2, while the average values in the operation time
(7) were only 43–90 W/m2. When the outdoor temperature
reached the design value, the actual cooling capacities
where QRF is the cooling capacity of radiant floors; were only 56–69% of their respective design capacity;
PRF is the power consumption of cycling pumps in even when outdoor temperature exceeded the design,
radiant floor systems; qw is the water density; Gw is the maximal cooling capacity values were only
the water flow rate; cp,w is the specific heat capacity 61–75% of their respective design capacity. These results
of water; DTw is the temperature difference of supply demonstrate that the measured cooling plants all oper-
and return water; Dpw is the pressure difference of ated in the partial load condition. Thus, the current
the cycling pump in radiant floor systems; gw is the design method mentioned above could have exaggerated
efficiency of water pumps. the designed cooling capacity of the cold source.
Because radiant floors only operate the sensible heat From the perspective of terminal devices in the air-
in airport terminals (avoiding condensation on their port terminal, Figure 14 compares the measured and
surfaces), the ATF in equation (6) is transformed into designed cooling capacity of AHUs in typical areas of
equation (8) under the dry condition for a fair compar- the airport terminal B2. The data were collected when
ison with WTFRF. the outdoor air temperature was 35.5  C, which
exceeded the design value of 33.1  C. The ratios of mea-
QAHU qa Ga cp;a  DTa qa cp;a  DTa  ga sured and designed cooling capacities of AHUs ranged
ATF ¼ ¼ Ga Dpa
¼ (8) from 46% to 91%. Thus, the actual cooling capacities of
PAHU g
Dpa
a AHUs vary over a wide range instead of always being
the design capacities of the worst condition. The varia-
where the subscripts a refer to air; Dpa is the pressure tion of AHUs’ cooling capacities mainly had resulted
difference of the fan in AHUs and ga is the efficiency from the occupancy rates in an airport terminal, as
of the fan. was analysed in the previous research.37 An airport ter-
The parameters in equations (7) and (8) are listed minal is not always fully occupied as it is in the design
in Table 4, which were based on the design parame- condition. Therefore, the uneven occupant distribution
ters of airport terminal C3.16 WTFRF is about 3–15 both in time and space would cause dramatic variation
times of ATF, which means water has a higher trans- in the actual demand for cooling load.
port capacity than air. Therefore, radiant floors have The on-site measurement results indicate a signifi-
a high potential to reduce the energy consumption of cant discrepancy of capacities between cold sources
terminal devices to operate the sensible heat in airport and terminal devices. The terminal devices operate
terminals. according to their respective cooling demands in

Table 4. Performance comparison of sensible heat handling devices transported by air (AHU) and water (radiant floor).

Supply/ Return DT ( C) q (kg/m3) cp (kJ/kgK) Dp (kPa) g (–) Performance

Aira 20 C/26 C 6 1.187 1.028 0.4–1.0 60% ATF ¼ 5–11


Water 16 C/19 C 3 998.7 4.194 100–200 60% WTFRF ¼ 38–75
a
xa ¼ 12.6 g/kg.
14 Indoor and Built Environment 0(0)

Figure 14. Comparison between the measured and designed cooling capacity of AHUs in airport terminal B2. (when
measured cooling capacity from the cooling plant was 120 W/m2 with outdoor air of 35.5  C).

various areas of the airport terminal and achieve their consumed by AHUs accounted for 40–74% of the
design capacities at different time. However, the output total electricity consumption of air-conditioning
capacity from the cooling plant is relatively constant systems. Therefore, energy-saving technologies
and lower than each maximal capacity of terminal devi- should be considered for terminal devices of air-
ces in the airport terminal. Therefore, the cooling conditioning systems in airport terminals.
capacity of each terminal device should have the ability 2. Temperatures in occupant zones were basically con-
to be adjusted over a wide range in order to match the trolled within 24–26 C. The relative humidities in
varying cooling demand. Furthermore, the designed some airport terminals were consistently higher than
cooling capacity of the cooling plant is supposed to 70% due to high-temperature chilled water supplied
be reconsidered to cope with the prevailing situation by chillers and chilled water mixed in the distribution
of a low load rate. A partial load coefficient could be system. The average CO2 concentrations were 563–
applied to reduce the designed cooling capacity of the 688 ppm, which indicated a considerable amount of
cooling plant appropriately. Otherwise, chillers and unorganised air infiltration. The thermal stratification
distribution systems should also have the ability to be commonly existed in large spaces in airport terminals;
adjusted and should be operated with high energy effi- these are closely related to the terminal devices of air-
ciency even at a low load rate. Thus, the research into conditioning systems.
feasible strategies to cope with this discrepancy of 3. The energy performance of air-conditioning systems
capacities is still needed in the further. in airport terminals can be improved by reducing the
total cooling demand and increasing the energy effi-
ciency. The occupant zone air-conditioning system
Conclusion (i.e. radiant floor þ displacement ventilation) is
Airport terminals have a higher level of energy adopted in airport terminal C3. The air-
consumption than common buildings, in which the conditioning controlled height could be reduced
air-conditioning systems account for the largest propor- from 4 – 6 m to about 2 m, and the radiant floor
tion. Large-scale on-site measurements were performed has a higher transport efficiency that the common-
to investigate energy consumption and indoor environ- ly-used air handling unit. Thus, this system could
ment in typical Chinese hub airports. This paper aims to save 34% of the air-conditioning electricity
analyse and compare air-conditioning systems in these consumption.
airport terminals, with an emphasis on the cooling 4. There was a significant discrepancy in the capacities
performance and their key restrictions. The conclusions between cold sources and terminal devices. In the
are summarised as follow: cooling plants, the designed cooling capacities were
132–176 W/m2, while the average measured values
1. The average annual electricity consumption in the were only 43–90 W/m2, and this was because each
measured airport terminals was 177 kWh/(m2year), terminal device in the airport terminal could
in which the air-conditioning systems consumed achieve its design capacity at different time.
30–60%. The measured COP of centrifugal chillers Therefore, the cooling capacity of each terminal
was 2.7–6.4 in chilled water condition, while the device should have the ability to be adjusted over
ATF of AHUs was 2.3–22.0. The electricity a wide range to match the varying cooling demand.
Liu et al. 15

Besides, the designed cooling capacity of the cool- 5. Alba SO and Manana M. Energy research in airports: a
ing plant is supposed to cope with the common review. Energies 2016; 9: 349.
situation of a low load rate. 6. Liu X, Lin L, Liu X, Zhang T, Rong X, Yang L and
Xiong D. Evaluation of air infiltration in a hub airport
Authors’ contribution terminal: on-site measurement and numerical simulation.
Build Environ 2018; 143: 163–177.
XL conducted the on-site measurements, analysed the data and 7. Zhao H. A field study on energy consumption and indoor
drafted the article. XL and TZ supervised the measurements, environment quality of terminals in China. Master Thesis,
reviewed the manuscript and provided comments for revision of Tsinghua University, Beijing, 2015.
the article. LL participated in the on-site measurements and 8. Wang Z, Zhao H, Lin B, Zhu Y, Ouyang Q and Yu J.
analysed the data of the airport terminals A1 and A2. Investigation of indoor environment quality of Chinese
large-hub airport terminal buildings through longitudinal
Acknowledgements field measurement and subjective survey. Build Environ
The authors would like to thank Lin Lin for participating in the 2015; 94: 593–605.
on-site measurements. The airport staff are gratefully acknowl- 9. Pichatwatana K, Wang F, Roaf S and Anunnathapong
edged for their kind help during the on-site measurement. M. An integrative approach for indoor environment
quality assessment of large glazed air-conditioned airport
Declaration of conflicting interests terminal in the tropics. Energy Build 2017; 148: 37–55.
10. Kotopouleas A and Nikolopoulou M. Evaluation of
The author(s) declared no potential conflicts of interest with
comfort conditions in airport terminal buildings. Build
respect to the research, authorship, and/or publication of
Environ 2018; 130: 162–178.
this article. 11. Kotopouleas A and Nikolopoulou M. Thermal comfort
conditions in airport terminals: indoor or transition
Funding spaces? Build Environ 2016; 99: 184–199.
The author(s) disclosed receipt of the following financial sup- 12. Huang C, Zou Z, Li M, Wang X, Li W, Huang W, Yang
port for the research, authorship, and/or publication of this J and Xiao X. Measurements of indoor thermal environ-
ment and energy analysis in a large space building in
article: The research described in this paper was supported
typical seasons. Build Environ 2007; 42: 1869–1877.
by the National Key Research Program of China (Grant No.
13. Wang B, Yu J, Ye H, Liu Y, Guo H and Tian L. Study
2018YFC0705001) and National Natural Science Foundation on present situation and optimization strategy of infiltra-
of China (Grant Nos 51878369, 51638010 and 51521005). tion air in a train station in winter. Procedia Eng 2017;
205: 2517–2523.
ORCID iD 14. Gil-Lopez T, Galvez-Huerta MA, O’Donohoe PG,
Tao Zhang https://orcid.org/0000-0001-5367-9537 Castejon-Navas J and Dieguez-Elizondo PM. Analysis
of the influence of the return position in the vertical tem-
Supplementary material perature gradient in displacement ventilation systems for
large halls. Energy Build 2017; 140: 371–379.
The method for the measurement of the key devices in the air-
15. Simmonds P, Holst S, Reuss S and Gaw W. Using radi-
conditioning system is given in the online supplementary
ant cooled floors to condition large spaces and maintain
material.
comfort conditions. ASHRAE Trans 2000; 106: 695–701.
16. Zhang T, Liu X, Zhang L, Jiang J, Zhou M and Jiang Y.
References Performance analysis of the air-conditioning system in
1. International Civil Aviation Organization (ICAO). Xi’an Xianyang International Airport. Energy Build
Annual Report 2017: air transport statistics, 2013; 59: 11–20.
https://www.icao.int/annual-report-2017/Pages/the-worl 17. Engineers RAC. ASHRAE handbook-HVAC systems and
d-of-air-transport-in-2017-statistical-results.aspx equipment. Atlanta, GA: American Society of Heating,
(accessed 5 September 2019). Refrigerating and Air-Conditioning Engineers Inc., 2016.
2. Civil Aviation Administration of China, National 18. GB/T 17981-2007. Economic operation of air conditioning
Development and Reform Commission, Ministry of systems. Beijing: The Standardization Administration of
Transport. 13th Five-year Plan of Civil Aviation, China, 2007.
http://www.caac.gov.cn (accessed 5 September 2019). 19. Li H and Li X. Benchmarking energy performance for
3. Liu X, Li L, Liu X, Zhang T, Rong X, Yang L and Xiong cooling in large commercial buildings. Energy Build 2018;
D. Field investigation on characteristics of passenger flow 176: 179–193.
in a Chinese hub airport terminal. Build Environ 2018; 20. Sun Y, Wang S, Cui B and Yim M. Energy performance
133: 51–61. enhancement of Hong Kong International Airport
4. Balaras CA, Dascalaki E, Gaglia A and Droutsa K. through chilled water system integration and control
Energy conservation potential, HVAC installations and optimization. Appl Therm Eng 2013; 60: 303–315.
operational issues in Hellenic airports. Energy Build 2003; 21. Zhang Y, Si P, Feng Y, Rong X, Wang X and Zhang Y.
35: 1105–1120. Operation strategy optimization of BCHP system with
16 Indoor and Built Environment 0(0)

thermal energy storage: a case study for airport terminal 29. Yun Z, Mao L, Zhou Z, Wei D and Xue X. Energy-
in Qingdao, China. Energy Build 2017; 154: 465–478. saving retrofit of air-conditioning cooling water system
22. Fan B, Jin X, Fang X and Du Z. The method of evalu- in terminal building of Guilin Liangjiang International
ating operation performance of HVAC system based on Airport. Build Sci 2007; 23: 104–107.
exergy analysis. Energy Build 2014; 77: 332–342. 30. Shen L, LY and Ma W. Air-conditioning system and
23. Huang H, Chen L and Hu E. A new model predictive energy design for Terminal 2 of Nanjing Lukou
control scheme for energy and cost savings in commercial International Airport. J HVAC 2017; 47: 66–72.
buildings: an airport terminal building case study. Build 31. Liao H. Application of hydronic balancing technology in
Environ 2015; 89: 203–216. the HVAC system of Chongqing Jiangbei International
24. GB50736–2012. Design code for ventilation and air condi- Airport. Refrigerat Air-Condition 2007; 21: 76–79.
tioning of civil buildings. Beijing: The Standardization 32. Yu L. Operation of the chilled water system for Terminal
Administration of China, 2012. 2 of Hongqiao International Airport. Refrigerat Air-
25. Takahashi T, Murakami S, Kato S, Ooka R, Deguchi K, Condition 2010; 10: 81–84.
Ikezawa H and Sugiyama T. Field experiment on indoor 33. Zheng W. Measures for energy saving of the air-
climate of passenger terminal building of Kansai conditioning system in New Baiyun International
International Airport (Part1): thermal environment Airport. Refrigeration 2008; 103: 53–56.
under full-cooling condition and air flow visualization. 34. Building Energy Research Center of Tsinghua University.
In: Annual Meeting the Society of Heating, Air- Annual report on China building energy efficiency. China
conditioning and Sanitary Engineers of Japan (SHASE), Building Industry Press, Beijing, China, 2018.
Hiroshima, 2-4 October 1995, 1493–1496. 35. Hartman T. All-variable speed centrifugal chiller plants.
26. CPG Consultants Pte Ltd. M&E systems for Changi Ashrae J. 2001; 43: 43–53.
Airport Terminal 3. The Singapore Engineer 2007; 239: 36. Zhao K, Liu X and Jiang Y. Application of radiant floor
24–29. cooling in large space buildings-A review. Renew Sustain
27. Liang M. Field Study and simulation of indoor thermal Energy Rev 2016; 55: 1083–1096.
environment in an airport terminal in winter. Bachelor 37. Liu X, Li L, Liu X and Zhang T. Analysis of passenger
Thesis, Tsinghua University, Beijing, 2017. flow and its influences on HVAC systems: An agent
28. Liu D, Liu C and Hu Z. Performance test analysis of based simulation in a Chinese hub airport terminal.
water chillers in the energy center of Pudong Build Environ 2019; 154: 55–67.
International Airport. J Hvac. 2002; 32: 101–103.

You might also like