Professional Documents
Culture Documents
kV=11)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
500 500
300 300
RL_103_EM_001 - N
100
OC1 100
ABB
REF 615
50
CT Ratio 20:1 50
Group 1
30
IEC Normal Inverse
Pickup = 0.1 (0.01 - 5 xCT Sec) 30
RMU_103_EM_001
Time Dial = 0.05
3x = 0.315 s, 5x = 0.214 s, 8x = 0.165 s
Inst = 1 (1 - 40 xCT Sec)
Time Delay = 0.02 s
10 10
5 5 CB13
Seconds
Seconds
3 3
1 1 RL_103_EM_001
±
.5 .5 R
.3 .3
160 kVA
103_TR_001
.1 .1
.05 .05
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 0.1 RMU_103_EM_001 (Nom. kV=11, Plot Ref. kV=11) ETAP Star 21.0.2C