You are on page 1of 6

SR100 Series Service Regulators

Technical Bulletin
Model SR100 Series Regulator 05 Elster American Meter

Regulator Assembly Positions


180° Models
Valve Head Position “A” Valve Head Position “B”

2 2
1 3 1 3
4 4
Standard Standard
Vent Position Vent Position

Valve Head Position “C” Valve Head Position “D”

4 2 AC-250 Meter with SR113 Regulator


3 1 1 3
2 4 Example of Regulator
Standard Standard
Assembly Position
Vent Position Vent Position In the photo above the SR113 Regulator
shown has an 180 degree valve head in
90° Models Position "C" (Flow upward) with the vent in
position 2 (Looking down). This would be
Valve Head Position “A” Valve Head Position “B” assembly position C2.

Ordering Information
2 4 1 Model number
1 3 3 1 2 Size of inlet and outlet
4 3 Valve Head type
2
4 Inlet pressure, PSIG (bar)
Standard
Vent Position Standard 5 Outlet pressure, inches W.C.
Vent Position
(mbar) or PSIG (bar)
6 Spring Range
Valve Head Position “C” Valve Head Position “D” 7 Flow, SCFH (m3/h)
8 Kind and specific gravity of gas
9 Orifice size
2 2 10 Regulator assembly position
1 3 1 3 number
4 4
Standard Standard
Vent Position Vent Position

Shipping Weight
Offset Models 12.8 lbs/carton of four regulators

Valve Head Position “D”

1
4 2
3
Standard
Vent Position
Model SR100 Series Regulator 02 Elster American Meter

The compact, high capacity SR113 service regulator is designed for residential or light
commercial/industrial applications using various hydrocarbon or other
non-corrosive gases. 14
9
Features 13
11
• Outlet pressure ranges available in 3
6” to W.C. up to 2 PSIG
• Variety of interchangeable orifices 2
• Cast Iron Valve Body Sizes 3/4” 4
and 1”; available in 90 degree (right
5
angle), 180 degree (straight) and
offset configurations
• Capacities through 2500 SCFH
• Full capacity internal relief valve
• 3/4” or 1” NPT threaded vents
• Molded Diaphragm provides more
precise outlet pressure control 1
• All models conform to ANSI Code
B109.4 and CGA Service-type 15
Regulator Specification CAN/CGA
17 12
6.18-M95.
7 16 8

Advantages 10 6

• Wide capacity range provides the


1 Diaphragm Case - Precision die-cast 10 Orifice Valve - High strength,
ability to standardize on varying
aluminum with an exclusive seven- corrosion resistant aluminum.
applications
• Full lockup capability provides step advanced conversion coating, Standard Part
assurance that downstream single-coat polyester primer and Orifice Size Number

pressure will not build up during high solid polyurethane top coat. 5/16” 72494P022
no-flow situations 1/4” 72494P021
2 Valve Body - Cast grey iron,
• Full capacity relief provides safety 3/16” 72494P020
during abnormal overpressure undercoated, single coat polyester
occurrences primer and high solid polyurethane 1/8” x 3/16” 72494P030

• Compact design combined with high top coat. Threads meet ANSI/ASME
B1.20.1 or BS 21/EN 10226. 11 Pressure Adjustment Screw -
performance Reinforced nylon
Options 3 Pressure Spring - Steel, zinc plated 12 Relief Valve - Reinforced nylon
and chromate. Color coded for 13 Vent Screen - Stainless steel - All
• Vent Elbow
identification. models are designed with a
• Splashguard
• Pressure Taps
Outlet Pressure Color Code Part Number removable weather and bug-proof
• Offset Valve Body 6” to 8” W.C. Blue/Yellow 70017P138 stainless steel screen to resist freeze-
7” to 12” W.C. Blue/Red 70017P139
ups and to exclude foreign matter.
The vent is threaded ¾” or 1” NPT
13” to 16” W.C. Blue/White 70017P140
Applications 21” to 35” W.C. Blue/Org 70017P141
(BSP-TR threads available).

• Residential 1.8 - 2# White 70017P060 14 Vent Valve - Stainless steel with


• Light commercial Eletrogalvanized steel retainer.
4 Diaphragm Plate - Reinforced nylon
15 Relief Valve Spring - Steel, zinc
plated and yellow chromate.
5 Diaphragm - Nylon fabric reinforced Non-adjustable. Color coded for
Buna N. identification. Standard set point of
6 Seat Disc - Buna N; 60, 70 (std.) or 80 9” w.c. above outlet set pressure of
durometer rating. 7” w.c. Standard set point of 1.1 psig
above outlet set pressure of 2 psig.
7 Plunger Guide - Reinforced nylon
16 Lever Pin - Carbon steel, zinc plated
8 Lever - Stamped aluminum
9 Seal Plug - Reinforced nylon 17 Plunger -Reinforced nylon
Model SR100 Series Regulator 03 Elster American Meter

SR100 Series Service Regulators


Capacity 1” Outlet Valve Body, SCFH (m3/h) Regulator Relief Valve Performance
Set Pressure of 7” W.C. @ 50 SCFH Outlet Pressure Relative to Inlet Pressure*
Screened Vent – No Vent Pipe
Set Pressure 7” W.C.
Inlet Pressure
Outlet Pressure - Inches W.C. (mbar)
PSIG 1/8“x 3/16” 3/16” 1/4” 5/16”
90
(bar) Orifice Orifice Orifice Orifice (224)
5 250 400 550 475 80
(199)
(0.34) (7.08) (11.33) (15.57) (13.45)
70
10 350 700 1100 1500 (174)
(0.69) (9.91) (19.82) (31.15) (42.48) 60
15 450 900 1700 2100 (149) 2 PSIG

(1.03) (12.74) (25.49) (48.14) (59.47) 50


(124)
20 500 1100 2000 2500
40
(1.38) (14.16) (31.15) (56.63) (70.79) (100)
30 650 1500 2500 2500 30
(75) 1 PSIG
(2.07) (18.41) (42.48) (70.79) (70.79)
20
40 800 1800 2500 2500 (50)
(2.76) (22.65) (50.97) (70.79) (70.79) 10
60 1100 2400 2500 2500 (25)

(4.14) (31.15) (67.96) (70.79) (70.79) 0


0 10 20 30 40 50 60 70 80 90 100 110 120 130
(.7) (1.4) (2.1) (2.8) (3.4) (4.1) (4.8) (5.5) (6.2) (6.9) (7.6) (8.3) (9.0)
0.60 Specific Gravity Gas at 60ºF and 14.7 PSIA (15.6oC and 1.01 bar)
Inlet Pressure - PSIG (bar)
Outlet pressure variance not to exceed +2/-1” W.C. from set pressure
5/16” 1/4” 3/16” 1/8” x 3/16”
*Failure by disconnecting linkage between the diaphragm and valve mechanism.

Capacity 1” Outlet Valve Body, SCFH (m3/h) Regulator Relief Valve Performance
Set Pressure of 2 PSIG @ 50 SCFH Outlet Pressure Relative to Inlet Pressure*
Screened Vent – No Vent Pipe
Inlet Pressure Set Pressure 2 PSIG
PSIG 1/8“x 3/16” 3/16” 1/4” 5/16”
(bar) Orifice Orifice Orifice Orifice Outlet Pressure - PSIG (bar)
10
5 175 150 300 250 (.69)
(0.34) (4.96) (4.25) (8.50) (7.08) 9
(.62)
10 300 275 400 425
8
(0.69) (8.50) (7.79) (11.33) (12.03) (.55)
15 375 350 600 550 7
(.48)
(1.03) (10.62) (9.91) (16.99) (15.57) 6
20 450 450 700 750 (.41)
(1.38) (12.74) (12.74) (19.82) (21.24) 5
(.34)
30 550 600 950 1000 4
(2.07) (15.57) (16.99) (26.90) (28.32) (.28)
3
40 750 800 1300 1400 (.21)
(2.76) (21.24) (22.65) (36.81) (39.64) 2
60 1000 1300 1900 2100 (.14)
1
(4.14) (28.32) (36.81) (53.80) (59.47) (.07)

0.60 Specific Gravity Gas at 60ºF and 14.7 PSIA (15.6oC and 1.01 bar) 0 10 20 30 40 50 60 70 80 90 100 110 120 130
Outlet pressure variance not to exceed 10% from set pressure (.7) (1.4) (2.1) (2.8) (3.4) (4.1) (4.8) (5.5) (6.2) (6.9) (7.6) (8.3) (9.0)
Inlet Pressure - PSIG (bar)

5/16” 1/4” 3/16” 1/8” x 3/16”

*Failure by disconnecting linkage between the diaphragm and valve mechanism.


Model SR100 Series Regulator 04 Elster American Meter

SR100
Service Regulator Dimensions
C
F Model SR113 - 90°
Inlet Outlet A B C D E F
3/4" 3/4" 1-1/2" 7-1/8" 5-3/8" 4-7/16" 2" 2-13/16"
D 38.10mm 180.98mm 136.53mm 112.73mm 50.80mm 71.45mm
3/4" 1" 1-1/2” 7-1/8” 5-3/8" 4-7/16" 2" 2-13/16"
38.10mm 180.98mm 136.53mm 112.73mm 50.80mm 71.45mm
1" 1" 1-1/2" 7-1/8” 5-3/8" 4-7/16" 2" 2-13/16"
E 38.10mm 180.98mm 136.53mm 112.73mm 50.80mm 71.45mm

A B

C
F Model SR113- 180°
Inlet Outlet A B C D E F
3/4" 3/4" 1" 7-1/8" 5-3/8" 4-7/16" 2" 2-13/16"
D 25.40mm 180.98mm 136.53mm 112.73mm 50.80mm 71.45mm
3/4" 1" 1” 7-1/8” 5-3/8" 4-7/16" 2" 2-13/16"
25.40mm 180.98mm 136.53mm 112.73mm 50.80mm 71.45mm
1" 1" 1" 7-1/8” 5-3/8" 4-7/16" 2" 2-13/16"
E 25.40mm 180.98mm 136.53mm 112.73mm 50.80mm 71.45mm

A B

C
F
Model SR113 - Offset
Inlet Outlet A B C D E F

D 3/4" 3/4" 1" 8-9/16" 5-3/8" 4-7/16" 2" 2-13/16"


25.40mm 217.49mm 136.53mm 112.73mm 50.80mm 71.45mm
3/4" 1" 1” 8-9/16” 5-3/8" 4-7/16" 2" 2-13/16"
25.40mm 217.49mm 136.53mm 112.73mm 50.80mm 71.45mm

E 1" 1" 1" 8-9/16” 5-3/8" 4-7/16" 2" 2-13/16"


25.40mm 217.49mm 136.53mm 112.73mm 50.80mm 71.45mm

A B

Regulator Pressure Rating


125 PSIG (8.6 bar) = Maximum recommended inlet pressure for normal service.
Maximum recommended pressure may vary with orifice size.

175 PSIG (12 bar) = Maximum inlet pressure for abnormal or emergency service, without causing damage to regulator case.
2 PSIG (138 mbar) = Maximum outlet pressure for normal service.
10 PSIG (689 mbar) = Maximum outlet pressure which can be contained by pressure carrying components (no flange leakage to
atmosphere except for normal relief action). If regulator is subjected to these conditions, it should be removed from service.
50 PSIG (3.5 bar) = Maximum outlet pressure for abnormal service without damage to internal components. If regulator is subjected to
these conditions, it should be removed from service.
About Elster Group
A world leader in advanced metering
infrastructure, integrated metering, and
utilization solutions to the gas, electricity
and water industries. Elster’s metering
and system solutions reflect over 170
years of knowledge and experience
in measuring precious resources
and energy.

Elster provides solutions and advanced


technologies to help utilities more easily,
efficiently and reliably obtain and use
advanced metering intelligence to
improve customer service, enhance
operational efficiency, and increase
revenues. Elster’s AMI solutions enable
utilities to cost-effectively generate,
deliver, manage, and conserve the life-
essential resources of gas, electricity, and
water.

Elster has a staff of over 7,500 serving


customers globally in North America,
Central America, South America, Europe,
Asia, Africa and the Middle East.

ISO 9001:2000

Certification No. 006697

Elster American Meter


2221 Industrial Road
Nebraska City, NE
68410
USA

T +1 402 873 8200


F +1 402 873 7616

www.elster-americanmeter.com

Elster Canadian Meter

T +1 905 634 4895


F +1 905 634 6705

www.elster-canandianmeter.com

© 2009 Elster American Meter. All right reserved

EAM-TB8100-EN-P - July 2009