Professional Documents
Culture Documents
٠٠ (HFC-٢٢٧ea HEDS)
UL: EX٢٧٨٧٨ / Component of FM Approved System
Consolidated Report
Customer Information
Company Name:
Address:
Phone:
Contact:
Title:
Project Data
Project Name:
Designer:
Number:
Account:
Location:
Description:
Enclosure Report
Page: ١ of ١٢
Consolidated Report
Minimum: ٧.٠٠ % Total Volume: ٥٣.٦٦ m ³
Min. Agent Required: ٢٩.٥١ kg
Adjusted Agent Required: ٢٩.٥١ kg
Page: ٢ of ١٢
Consolidated Report
Parts Report
Pipe &
Fittings Type Diameter Length Elbows (٩٠) Elbows (٤٥) Tees Unions
٤٠T ١٥A ٥.١٥ m ٢ ٠ ٠ ٠
٤٠T ٢٥A ٤.٤٥ m ٣ ٠ ١ ٠
Other
Objects Name Quantity Part Number
٥٠ mm Flexible Hose ١ SHG٠٠٥٠FH
Page: ٣ of ١٢
Consolidated Report
Percent Agent Before First Tee: ٨.٨%
Dead Volume: ٠.٠% (٠.٠٠ kg)
Enclosure Number: ١
Enclosure Name: ROOM VPID
Minimum Design Concentration: ٧.٠٠%
Adjusted Design Concentration: ٧.٠٠%
Predicted Concentration: ٦.٥٣%
Maximum Expected Agent Concentration: ٦.٥٣% (At ٢٠.٠ C)
Enclosure Number: ٢
Enclosure Name: TRENCH VOID
Minimum Design Concentration: ٧.٠٠%
Adjusted Design Concentration: ٨.٤٧%
Predicted Concentration: ١٢.٩٨%
Maximum Expected Agent Concentration: ١٢.٩٨% (At ٢٠.٠ C)
Page: ٤ of ١٢
Consolidated Report
Minimum Adjusted Predicted Average
Agent Agent Agent Nozzle
Nozzle Required Required Delivered Pressure
Page: ٥ of ١٢
Consolidated Report