GENERATOR SIZING CALCULATION

Sr. No. Description Load(KW) Classification of Load Generator during load

Required Short
Starting Amps
Legally Pump Ckt Outage with
Optional Routine Outage Pump NEMA (I(A) = 1000 × Source Normal Power Outage with
Emergency Required Amps @ Starting KVA Amps(Considerin Eqp. In Notes
Standby Outage with FLS Motor HP Code G S(kVA) / (√3 × VL- Impedance Source FLA Factor FA and Pump
Standby 480 V g volatage drop Operation
L(V) )
of 15%)
1 2 3 4 5 6 7 8 9 10 11
1*3 For 3 Phase 5/0.15 6*7
1 Egress Lighting 100 100 100 100 100 100

2 Fire Alarm 50 50 50 50 50 50

3 Smoke Control 200 200 200 200 200


Load @ Fire Pump
4 Fire Pump 125 125 150 180 6.3 944 1135 7566 0.17 1286 0.8 855 855
Starting
5 Computer Room 400 400 400 400

6 Elevator 100 100 100 100 100 100

7 Garage Exhaust 100 100 100 100 100 100


Walk-in
8 25 25 25 25
Refrigerator

Total Connected
load(in Amps) =
Total 1100 375 300 425 775 550 1015
675 KW except
optional standby
Total Combination of load with
Combination of
fire pump except optional 8581 0.17 1459 0.8 970
load with fire pump
Standby load

Total Connected
load(in Amps) = 1654
1100 KW

Total Load 9220 0.17 1567 0.8 1042 Total of all load

Reserve Capacity(25%) 261 KW

Generator Size 100% Power 1303 KW

SUMMARY

Reserve
Sr. No. Description Generator KW total Capacity
Capacity KW

1 During Staring of Fire pump 855

2 During Staring of Fire pump with other FLS loads 970

3 All loads are connected 1042 261 1303