Professional Documents
Culture Documents
IEEE Standard C37.118-2005 Synchrophasors For Power System
IEEE Standard C37.118-2005 Synchrophasors For Power System
within one of two accuracy classes, and conforming to the com- Frequency measurement accuracy (including rate of change
munication protocol for reporting measurements. A particular of frequency) is not specified in the standard. However, experi-
PMU may have additional capabilities (above and beyond those ence has shown that PMUs are among the best frequency trans-
required for compliance with the standard) in the realm of ac- ducers available, delivering accuracy of a few millihertz (typi-
curacy, communication, reporting rates, frequency range, noise cally 1–3 mHz) with a measurement window of a few cycles.
suppression, etc. These capabilities may be of interest to certain The standard does not specify PMU performance require-
applications and they are not considered to affect the compli- ments under transient conditions. This means that under nonsta-
ance requirement of the standard. tionary conditions such as a fast frequency ramp, various PMUs
1) Measurement Convention: Synchrophasor is defined as a will produce outputs that may differ despite their conformance
complex number representation of the fundamental frequency to either of the two accuracy classes of the standard. Refer to
component of a voltage or current, with an accompanying Section III of this paper for considerations regarding perfor-
time-tag defining the time instant for which the phasor mea- mance of PMUs under dynamic conditions.
surement is performed. The standard mandates the phase angle 3) Communications Protocol: The standard defines a pro-
convention as depicted in Fig. 1. The definition does not depend tocol for communicating synchrophasor measurements in real-
on position of the data window used to produce the phasor time from a PMU to a phasor data concentrator (PDC)—a device
estimate, and is unambiguous under offnominal frequencies. archiving and presenting the PMU data to various applications.
In fact, C37.118 does not refer to frequency when defining a This protocol can also be used for cascading PDCs when aggre-
synchrophasor. gating the data streams from different regions of the monitored
A conforming PMU must also provide a choice of reporting power system.
rates, from ten reports per second up to half the nominal system The protocol is “lightweight” in that it has only few mes-
frequency (25 or 30/s, respectively). The reporting times shall sage types with few options, is implemented in a single layer,
begin at the top of second (xx.000000 s) as defined by the time and splits the real-time data stream from occasional exchange
reference, and be evenly spaced through the second. of configuration information.
PMUs must also provide estimates of frequency and rate of If the PMU supports real-time data communication, confor-
change of frequency (df/dt), as part of the PMU output data mance to the standard requires that it support the five frame
stream. The standard does not specify how these estimates are types defined in the standard: Data frame (binary); two config-
to be calculated. uration frames (binary); header frame (ASCII); and command
2) Measurement Accuracy: The standard defines accuracy frame (binary).
as a vectorial difference between the measured (MEAS) and Once turned on by a start command, data frames are sent
expected (IDEAL) value of the phasor for the measurement at a continuously from the PMU to the host system. PMU numer-
given instant of time (k). This is defined as the total vector error ical outputs may be formatted either as a 16-b integer or 32-b
(TVE) floating-point numbers (IEEE Std. 754–1985). In addition to
synchrophasor and frequency measurements mandated by the
standard, other analog values (quantities such as power flows)
% (1) and digital status words (for example, breaker status) may op-
tionally be included in the data frame. The standard does not
specify how these other quantities are measured or time tagged.
TVE blends together three possible sources of error: magni- Configuration and header frames describe the PMU config-
tude, angle and timing. For example, if a given PMU synchro- uration. They are transmitted whenever requested by the host,
nized perfectly with the reference time and exhibits no angle which will usually occur at system startup or upon change of
error, 1% of error in magnitude will translate into 1% of TVE. PMU configuration. Configuration frames are a fixed binary
Without timing and magnitude errors, an angle error of 0.573 structure that is machine readable, which allows relatively auto-
corresponds to 1% of TVE. When all error is caused by inaccu- matic system configuration. Two configuration frames are used:
racy of time synchronization, 31.8 s at 50 Hz, and 26.5 s at 1) the first describes the full capabilities of a given PMU and 2)
60 Hz would cause 1% TVE. with the other, the capabilities are configured at a given time.
The standard allows for two levels of accuracy compliance: Header frames are unstructured text intended for human read-
Level 1 and Level 0. Both call for TVE below 1%, but Level 1 able information.
is more stringent by imposing more challenging test reference The command frame is sent by the host to the PMU to start or
conditions in terms of frequency range ( 5 Hz versus 0.5 Hz stop transmission, or request configuration data in the form of
for level 0, for example), magnitude range, signal distortions, configuration or header frames. Unused bits in these commands
etc. are reserved and may be used for further command information
The standard does not specify the method of measurement, in future revisions of the standard. A new extended frame com-
or other factors such as the sampling rate, algorithms, or syn- mand type is provided for user-defined functions such as PMU
chronization method. Instead, it mandates the same output—to configuration or remote controls.
within 1% of TVE—under a wide range of reference condi- The C37.118 protocol may be used with any communications
tions. This allows manufacturers to use different measurement medium or system, including serial ports (EIA—232 or—485,
methods while assuring conformance with the result under a for example) and Ethernet over wire or fiber optic cable. When
range of basic performance. used with a lower-level protocol such as TCP/IP or UDP/IP,
MARTIN et al.: EXPLORING THE IEEE STANDARD C37.118–2005 1807
IEEE C37.118 requires that the data frame as defined in the protocol are more completely specified, and several new data
standard be transmitted in its entirety, including the cyclic re- categories have been added. New annexes have been added to
dundancy check (CRC). Implementation over lower level pro- provide clarification and guidance. These changes are summa-
tocols is prescribed in the normative Annex I of the standard. It rized in this section.
states how the C37.118 message frames are to be mapped into
communication protocols, specifically RS-232 and IP protocol. A. Definition of a Synchrophasor
It also specifies default port numbers for IP protocol; 4712 for Instead of defining synchrophasor, 1344 introduced a con-
TCP and 4713 for UDP. vention for synchrophasor representation for a sinusoidal input
signal at the rated frequency of 60 or 50 Hz. According to the
D. Additional Guidance Provided in Annexes
previous standard, the synchrophasor angle is reported as zero
With the exception of Annex I, all annexes are “informative,” if the sample corresponding to the start of the data window used
which means they are not binding but guide the user in better in phasor calculation falls on the maximum of the signal wave-
understanding of the standard. Annex A presents a useful bib- form. This created an ambiguity under offnominal frequency
liography of documents relevant to the subject. Annex B clar- conditions. The standard did not mandate the position of the
ifies and illustrates the use of CRC generators and provides a window with respect to the absolute time reference, but pointed
sample algorithm for calculating the CRC. Annex C provides in one of its annexes (C.2—Alternate time-tagging) to three pos-
further information on time-tagging with examples related to sible solutions: time-tagging based one the first, middle or last
different computation codes. Annex D contains examples of all sample in the phasor calculation data window. With this ap-
message types with sample data. Annex E discusses sources of proach, although a phasor measurement could be defined un-
precise time synchronization for synchrophasor measurements. ambiguously at the rated frequency, at offnominal frequency the
Annex F details time communication formats and presents an convention for phasor representation was difficult to apply and
expanded IRIG-B format for improved time communication. interpret.
Annex G suggests sample benchmark for testing synchropha- In the new standard, definitions for both a phasor and
sors under transient conditions. Annex H explains the notion of synchrophasor are introduced and match the previous con-
TVE and gives examples of TVE calculations for various mag- vention for nominal frequency inputs. The ambiguity of the
nitude, phase and timing errors. phasor representation at offnominal frequency is completely
removed—the definition does not refer to frequency or position
E. System Integration of the data window, but rather to a time shift between the
The new standard includes a unit ID identifying the message waveform positive peak and the reporting instant expressed as
source or the destination for commands. These IDs are 16-b inte- a part of full cycle (rotation). All compliant PMUs will respond
gers. Assignment of values is left up to the user, so coordination the same to offnominal frequencies: the phasor angles will
is required when utility data is exchanged throughout an entire rotate at a rate that is the difference between the nominal and
grid. measured signal frequencies (e.g., a 61 Hz signal on a 60 Hz
The new standard does not require using any specific data system will appear to rotate at radians/s).
transmission method or protocol; this is left up to manufacturers The old standard did not have any accuracy requirement other
and users. It does specify how data messages are to be encapsu- than the sampling pulse accuracy (1 s). The new version uses
lated within a protocol, and gives examples for the IP protocol an aggregated measure, TVE, of magnitude, angle and timing
and RS232 serial communication. Within the IP protocol, TCP errors (1%).
or UDP can be used.
There are four bits set aside in the data frame to allow affixing B. Time-Tagging Specifications
a security suffix. This was done to allow future changes which By avoiding references to data window and frequency the
may be needed for evolving industry standards for substation new standard is more precise in stating what a synchrophasor
automation and corresponding protocols. measuring system should do under offnominal frequency condi-
tions. The time tag is defined by the measurement time and TVE
II. DIFFERENCES BETWEEN IEEE 1344 AND requirements rater than the data window and sample times.
C37.118 SYNCHROPHASOR STANDARDS The new standard states that the measured phasor should cor-
This section provides an overview of differences between the respond to the signal at the input terminals of the PMU. Thus,
new synchrophasor standard (IEEE Standard C37.118–2005 any phase or amplitude shift that occurs inside the PMU must
[2]) and the previous one (IEEE Standard 1344–1995 [1]). be compensated for and not reflected in the measured phasor.
These standards follow a consistent approach to the subject,
C. Communications Protocol
but differ in a number of details. Synchrophasor measurement
in IEEE 1344 was defined in terms of waveform sampling, The old and new standards differ moderately in the area of
timing, and the basic phasor definition. Data communication in data communications. In particular:
1344 was incompletely specified, and much was left up to the 1) Message Framework: The same four message types are
manufacturer and the user. used in C37.118 as were used in 1344: data, configuration,
C37.118 covers the same basic elements as 1344, but the syn- header, and command. Several fields have been added, such as
chrophasor is defined unambiguously, various parameters of the sync and frame size words, to simplify decoding.
1808 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 4, OCTOBER 2008
A. State Estimation
State estimation is a process that determines the state of the Fig. 5. Power-voltage (PV) curve.
power system to allow the system operator to make better deci-
sions aimed at maintaining power system security in the face of
various contingencies. Improvement in the accuracy of the state be directly calculated with linear equations (“indirectly mea-
estimation of the power system network is one of the most im- sured”). These buses are therefore defined as “observable” to
mediate benefits of PMU application. bus S, the PMU location [3].
The state estimation technology currently in use evolved in Similarly the placement of PMUs at busses J and G define
the 1960s. It uses measurements that do not require a common regions X and Y where the state is accurately measured either
reference: power system active power and reactive power flow directly or indirectly. The remaining buses E, N, L and Q are
measurements, voltage magnitude, etc., collected over a fairly not considered “measurable” with the current PMU placement.
long interval, to estimate the power system state. The process The number of adjacent busses that are not measurable (directly
combines the measurements with the network model to find or via calculations with linear equations) defines the “depth of
the variables of interest by solving nonlinear equations by nonobservability” for a system with partial PMU coverage. It is
numerical iterations. The process may take several minutes optimum to place the PMUs in such a way to maintain a uniform
or longer to converge to a solution, is prone to errors in the depth of “nonobservability.” For this configuration the depth of
network parameters, and often diverges during those evolving nonobservability is one and state voltage and current quantities
disturbances when a good state estimation is needed most. The at the unobservable busses can be estimated by linear interpola-
industry is constantly developing methods to improve state tion with reasonable accuracy.
estimation accuracy. Power system state-vector determination from PMU mea-
The application of a sufficient number of time-tag synchro- surements offers the most precise method yet for obtaining real-
nized PMUs across the system will improve state estimation so- time static and dynamic information about the condition of the
lutions to the point that the process becomes one of state mea- network [4].
surement. Consider the placement of PMUs at busses G, J and
S on the power system shown in Fig. 4. B. Voltage Instability
The PMU at bus S measures the voltage phasor (amplitude Visual tracking of the system proximity to an insecure voltage
and angle), , and current phasors , and . condition with a power-voltage (PV) curve may be done using
Having these phasor quantities and an accurate system model, synchrophasor data. Fig. 5 shows a typical PV curve developed
the voltage phasors at the remote busses M, P, R, and T can from transmission corridor and load impedance data [5]. The
1810 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 4, OCTOBER 2008
While usually considered for indicating power flow, phase angle paper is not a substitute for the actual standard, which is the ulti-
can also indicate topology changes that require control actions. mate authority as to what constitutes compliance. The main dif-
This approach is used in another demonstration SIPS control ferences between the old and the new standards have also been
scheme [12]. pointed out. The paper also provides a preliminary discussion of
PMU responses to electrical and electromechanical transients.
G. System Oscillation and Small Signal Analysis This paper discussed several prospective applications for the
System oscillations can be monitored and analyzed using PMU technology with significant benefits for system operation
phasors reported at an adequate rate (see Section III-C). For and integrity.
example, a 30/s reporting rate (15 Hz Nyquist rate) allows a The Working Group hopes that this standard will serve the
filtered measurement bandwidth of 4–8 Hz, covering most sig- industry well for years to come.
nificant system oscillations. Prony or Eigen analysis can be used
REFERENCES
to determine the system oscillation modes from the measured
[1] IEEE Standard for Synchrophasors for Power Systems, IEEE Std.
data. Comparison of mode values indicates unit participation, 1344-1995 (R2001).
and modal damping [13], [14]. This information can be used [2] IEEE Standard for Synchrophasors for Power Systems, IEEE Std. C37.
to assure system security, locate and resolve control problems, 118–2005 (Revision of IEEE Std. 1344–1995).
[3] R. F. Nuqui and A. G. Phadke, “Phasor measurement unit placement
and validate system models. In addition, a low level probing techniques for complete and incomplete observability,” IEEE Trans.
signal can be used to excite particular oscillation modes [15]. Power Del., vol. 20, no. 4, pp. 2381–2388, Oct. 2005.
This can provide operational security to be sure critical modes [4] A. G. Phadke, J. S. Thorp, and K. Karimi, “State estimation with phasor
are damped. Synchronized phasors provide the high-accuracy measurements,” IEEE Trans. Power Syst., vol. PWRD-1, no. 1, pp.
233–241, Feb. 1986.
and low noise measurements required for these applications. [5] M. Larsson, C. Rehtanz, and J. Bertsch, “Real-time voltage stability
assessment for transmission corridors,” presented at the IFAC Power
Plants and Power Systems Control Conf., Seoul, Korea, 2003.
V. OTHER SYNCHROPHASOR STANDARDS [6] V. Centeno, J. De La Ree, A. G. Phadke, G. Michel, J. Murphy, and
R. Burnett, “Adaptive out-of-step relaying using phasor measurement
techniques,” IEEE Comput. Appl. Power, vol. 6, no. 4, pp. 12–17, Oct.
A. Synchrophasor Standard in China 1993.
[7] C.-S. Chen, C.-W. Liu, and J.-A. Jaing, “A new adaptive PMU based
Research on synchrophasor technology in the People’s Re- protection scheme for transposed/un-transposed parallel transmission
public of China started in 1994. However, it was not until 2002 lines,” IEEE Trans. Power Del., vol. 17, no. 2, pp. 395–404, Apr. 2002.
that PMU and wide area monitoring systems (WAMS) gained [8] M. Weibel, W. Sattinger, P. Rothermann, U. Steinegger, M. Zima, and
G. Biedenbach, “Overhead line temperature monitoring pilot project,”
wide acceptance and application development started. The com- in CIGRE General Session, Paris, France, Aug. 27–Sep. 1, 2006, pp.
mercial PMU/WAMS systems are manufactured according to B2–311.
“The Technological Specification of Power System Real-time [9] E. Price, “Practical considerations for implementing wide area moni-
toring, protection and control systems,” presented at the 59th Annu.
Dynamic Monitoring Systems.” The specification, based on an Conf. Protective Engineers, College Station, TX, Apr. 2006, Texas
early draft of C37.118, standardizes the general architecture, A&M Univ.
basic functions, communication interfaces and other related is- [10] C. W. Taylor, D. C. Erickson, K. E. Martin, R. W. Wilson, and V.
Venkatasubramanian, “WACS—Wide-area stability and voltage con-
sues of PMU/WAMS [16]. trol system: R&D and online demonstration,” in Proc. IEEE, May 2005,
vol. 93, no. 5, pp. 892–906.
B. IEC Synchrophasor Standard [11] D. Hu and V. Venkatasubramanian, “New wide-area algorithms for
detecting angle instability using synchrophasors,” presented at the
IEEE Standard C37.118 is expected to become an interna- Western Protective Relay Conf., Spokane, WA, Oct. 2006.
[12] E. Martinez, N. Juarez, A. Guzman, G. Zweigle, and J. Leon, “Using
tional standard. At this time there is no attempt to create a com- synchronized phase angle difference for wide-area protection and con-
peting standard, but rather to use the IEEE version under the trol,” presented at the Western Protective Relay Conf., Spokane, WA,
“dual logo agreement” between IEEE and IEC. This encourages Oct. 2006.
[13] P. Kundar, G. J. Rogers, and M. Klein, “A fundamental study of inter-
development, creates a global application space for the manu- area oscillations in power systems,” IEEE Trans. Power Syst., vol. 6,
facturers, will lead to improved cost and performance, and allow no. 3, pp. 914–921, Aug. 1994.
faster maturity rate for the PMU technology. [14] K. E. Martin, “Phasor measurements in the WECC,” presented at the
IEEE T&D Show, Panel on Phasor Measurements—Systems Applica-
tions, Dallas, TX, May 2006.
[15] J. F. Hauer and M. J. Besir, “Interim report of WSCC summer 2000
VI. CONCLUSION staged system tests and validation studies” Oct. 2000, WECC Modeling
Working Group.
This paper has described the principal features of the revised [16] X. Xie and Y. Xin, “WAMS applications in Chinese power system,”
synchrophasor standard. The reader must remember that the IEEE Power Energy Mag., vol. 4, no. 1, pp. 54–63, Jan./Feb. 2006.