The document provides default setting values for meters delivered to the Saudi Electricity Company. Unless otherwise specified, the meters will be configured with the default settings in Table No.9, which include standard Saudi time, time-of-use tariff periods, automatic monthly reset of energy on bill (EOB) readings, 30-minute maximum demand integration time with 5-minute sub intervals, and channels to record load profiles. The default CT and VT ratios are set to 1, and digits displayed are as specified in Table No.7.
Original Description:
Original Title
Pages from 40-SDMS-02A- CT-CTVT Meter Specifications Rev.9_ Sep-19
The document provides default setting values for meters delivered to the Saudi Electricity Company. Unless otherwise specified, the meters will be configured with the default settings in Table No.9, which include standard Saudi time, time-of-use tariff periods, automatic monthly reset of energy on bill (EOB) readings, 30-minute maximum demand integration time with 5-minute sub intervals, and channels to record load profiles. The default CT and VT ratios are set to 1, and digits displayed are as specified in Table No.7.
The document provides default setting values for meters delivered to the Saudi Electricity Company. Unless otherwise specified, the meters will be configured with the default settings in Table No.9, which include standard Saudi time, time-of-use tariff periods, automatic monthly reset of energy on bill (EOB) readings, 30-minute maximum demand integration time with 5-minute sub intervals, and channels to record load profiles. The default CT and VT ratios are set to 1, and digits displayed are as specified in Table No.7.
Saudi Electricity Company الشركة السعودية للكهرباء
SEC DISTRIBUTION MATERIALS 40-SDMS-02A
SPECIFICATION DATE: September 2019
10. DEFAULT SETTINGS
All the meters delivered to COMPANY shall have the default setting values easily configurable. Unless differently specified by COMPANY request, the default settings shall comply with the values in Table No.9. Table No.9 Default settings Configuration features Default settings Clock (DD:MM:YYYY, HH:MM:SS) KSA Standard time (GMT + 3.00) Time of Use (TOU) Setting (#1: Sat ~ Thu, #2: Fri) Tariff 1 (TOU 1) #1: From 12:00 ~ 17:00 #1: From 08:00 ~ 12:00 and 17:00 ~ 24:00 Tariff 2 (TOU 2) #2: From 09:00 ~ 21:00 #1: From 00:00 ~ 08:00 Tariff 3 (TOU 3) #2: From 00:00 ~ 09:00 and 21:00 ~ 24:00 Tariff 4 (TOU 4) Not applied TOU 5 ~ 8 or more Not applied Automatic EOB reset time & date At 00h 00m on the first day of every month Maximum demand Integration method Sliding window Integration time 30 minutes (Default) Sub interval 5 minutes (Default) Import Active Power (+), Import Reactive Power (+), Import Apparent Power (+), Import Reactive Power (QI), Export Reactive LP recording Power (QIV), Export Active Power (-), Export (at least twelve (12) channels) Reactive Power (-), Export Apparent Power (-), import average power factor and export average power factor. CT ratio 1 VT ratio 1 The number of digits for the display Active energy (kWh) Reactive energy (kVarh) Apparent energy (kVAh) As per Table No.7 – Default Units to Display Maximum demand power (W) Instantaneous values (V, A, W, Var, VA, Hz)