Saudi Electricity Company

Distribution Services Sector


SPECIFICATION FOR ELECTRONIC REVENUE Issue Date: 04/2023 Page: 49 of 93
CT AND CT-VT METER 40-SDMS-02A Rev. 9.5

Configuration features Default settings


Current date/ time, status information, Import
Active Power (+), Import Reactive Power (+),
Import Apparent Power (+), Import Reactive
LP recording
Power (QI), Export Reactive Power (QIV),
(at least fourteen (14) channels)
Export Active Power (-), Export Reactive
Power (-), Export Apparent Power
(-), import average power factor and export
average power factor.
CT Ratio 1
VT Ratio 1
The number of digits for the display
Active energy (kWh)
Reactive energy (kVarh) As per Table No.8 – Default Units to Display
Apparent energy (kVAh)
Maximum demand power (W)
Instantaneous values
(V, A, W, Var, VA, Hz)

11. MARKING OF METERS


11.1. Every meter shall be provided with a suitable size of name-plate inside the meter
cover if used. Information shall be bilingual (Arabic and English). These shall be
printed clearly, indelibly and readable from outside
11.2. Name-plate shall include the following information:
11.2.1. The Manufacturer's name or trademark and place of manufacturing
11.2.2. Designation and type
11.2.3. The number of phases and the number of wires for which the meter is
designed
11.2.4. Meter ID (Refer to Clause 6.12.3 of the CT and CTVT OBIS Codes
Specifications)
11.2.5. Year of manufacture
11.2.6. The reference voltage in the form of the nominal voltage of the system
or the secondary voltage of the instrument transformer to which the
meter is to be connected.
11.2.7. The rated current and the rated maximum current; for example: 1.5(6)
Amps
11.2.8. The reference frequency in Hertz, for example: 60 Hz
11.2.9. The meter constants in the form Imp/kWh, Imp/kVarh, Imp/kVAh