You are on page 1of 2

TITAN 130

Gas Turbine Generator Set


Power Generation

General Specifications
Titan™ 130 Gas Turbine
• Industrial, Single-Shaft • NEMA Class F Insulation – On-Crank/On-Line
• Class B Temperature Rise* – Portable Cleaning Tank*
• 14 Stage Axial Compressor
– Variable Inlet Guide Vanes and Stators • Continuous Duty Rating Voltages: • Package Power
– Pressure Ratio: 19.1:1 – 3300, 6600, 11 000 (50Hz) – 120VDC Battery/Charger System
– Inlet Airflow: 55.4 kg/sec (122 lb/sec) – 4160, 6900, 12 470, 13 200, 13 800 (60Hz) • Turbotronic™ On-Skid Gas Turbine and
– Vertically Split Case Package Generator Control System Features
– Combination Generator Control Module
• Combustion Chamber, Annular-Type • Mechanical Construction
with Load Share, Auto Synchronization,
– 21 Conventional Fuel Injectors – Steel Base Frame with Drip Pans
Voltage Control
– 14 Lean-Premixed, Dry Low – 316L Stainless Steel Piping
– Standard Display with Discrete Event Log,
Emissions SoLoNOx™ Injectors – Compression Type Tube Fittings
Strip Chart, Historical Trend,
– Single Torch Ignitor System • Start System Maintenance Screen
• Power Turbine – Direct Drive AC Motor with VFD Control – Vibration and Temperature Monitoring
– 3-Stage Reaction • Package Electrical Certification – English Display Text and Labels
– Clockwise Rotation – NEC, CSA Class 1, Group D, Div.2 – Spanish, Portuguese, German, French
• Bearings • Fuel System or Simplified Chinese Display Text
– 3 Radial Journal: Tilt-Pad – Natural Gas – Auxiliary and Remote Display/Control
– 1 Thrust, Active: Tilt-Pad – Diesel* Terminals*
– 1 Thrust, Inactive: Fixed Tapered Land – Dual (Natural Gas and Diesel)* – Turbine Performance Map*
• Coatings – Low BTU Gas* – KW Import Control*
– Compressor: Inorganic Aluminum • Integrated Lube Oil System – KVAR/Power Factor Control*
– Turbine and Nozzle Blades: Platinum – Turbine-Driven Lube Pump – ControlNet Redundant Media, Ethernet
Aluminide (Stages 1 and 2) – AC Motor Driven Pre/Post Lube Pump or Modbus RS232C/422/485 Supervisory
– DC Motor Driven Backup Lube Pump Interface*
• Vibration Transducer Type
– Air to Oil Cooler – Heat Recovery Application Interface*
– Proximity Probes, 2 per Radial Bearing/
– Water to Oil Cooler* – Multi-Unit Applications: Load Shed Control,
2 per Thrust Bearing
– Integral Lube Oil Tank Import/Export or kW/KVAR Control Panels*
Main Reduction Drive – Lube Oil Tank Heater – InSight System™ Equipment Health
• Epicyclic Type – Lube Oil Filter Management*
– 1500 or 1800 rpm (50 or 60 Hz) – Duplex Lube Oil Filter* – Printer/Logger*
– Vibration monitoring: Acceleration – Oil Tank Vent Separator with • Electrical System Options
Transducer Flame Arrestor – Neutral Grounding Resistor
Generator • Air Inlet and Exhaust Systems or Transformer*
– Carbon Steel – Switchgear and Generator Protective
• 4 Pole, 3 Phase, 6 Wire, Wye Connected,
– Stainless Steel* Relay*
Synchronous with Permanent Magnet
– Barrier Type Filters – Motor Control Center with Automatic
Generator Exciter
– Self-Cleaning Filters Transfer Switch*
• Available Construction Types:
– Inlet and Exhaust Silencers • Documentation
– Open Drip-Proof Construction
– Inlet Evaporative Cooler* – Drawings
– CACA/TEAAC (Closed Air, Cooling Air/
– Inlet Chiller Coils* – Quality Control Data Book
Totally Enclosed, Air to Air Cooling)*
• Enclosure – Inspection and Test Plan
– CACW/TEWAC (Closed Air, Cooling
– Complete Package – Test Reports
Water/Totally Enclosed, Water to Air
– Driver Only* – O&M Manuals
Cooling)*
– Fire Detection and CO2 Suppression • Factory Testing of Turbine
• Sleeve Bearings
System • Factory Testing of Package Systems
• Vibration Monitoring; Velocity Transducers
• Turbine Compressor Cleaning Systems – Non-Dynamic
• Vibration Monitoring; Displacement – Dynamic
Transducers*

* Option
TITAN 130
Gas Turbine Generator Set
Power Generation

Performance
Available Power*
Output Power 16 530 kWe
18,500 11.0
Heat Rate 10 160 kJ/kWe-hr
(10,430)
(9630 Btu/kWe-hr)

HEAT RATE, MJ/kW-hr (Btu/kWe-hr)


Exhaust Flow 202 510 kg/hr Output Power
(446,460 lbs/hr) 17,125 10.7

OUTPUT POWER, kWe


(10,140)
Exhaust Temperature 490°C
(910°F)

Application Performance 15,750 10.4


Steam (Unfired) 29.2 tonnes/hr (9860)
(64,490 lb/hr)
Steam (Fired) 134.1 tonnes/hr
1536°C (2800°F) (295,730 lb/hr) 14,375 10.1
(9570)
Chilling (Absorp.) 25 240 kW
Heat Rate
(7170 refrigeration tons)
9.8
Nominal rating – per ISO 13,000 (9290)
At 15°C (59°F), sea level -30.0 -15.0 0.0 15.0 30.0 45.0
No inlet/exhaust losses (-22) (5) (32) (59) (86) (113)
Relative humidity 60%
INLET AIR TEMPERATURE, °C (°F)
Natural gas fuel with DS130GSPG-002M
LHV = 35 MJ/Nm3 (940 Btu/scf)
No accessory losses * SoLoNOx
Engine efficiency: 35.4%
(measured at generator terminals)

Enclosure Access and Maintenance Space


4.6 m
4572 mm 14.2mm
14021 m
(15’
(15’0”)
0”) (46’0”)
(46’ 6”)

MINIMUM SPACE CLEARANCE


REQUIRED FOR ENCLOSURE
3 mmm
3048 GENERATOR ACCESS DOORS AND
(10’
(10’ 0”) MAINTENANCE ROUTINE OPERATION
AND MAINTENANCE

MINIMUM CLEARANCE REQUIRED 3.2 mm


3048 m
FOR ENGINE REMOVAL (10’ 5”)
(9’11”)

8611
8.6 mm
m
(28’ 3”)
(28’ 2”)
Package Height: 3.9 m (12’ 9”) DS130PG-003C
Package Weight: 87 510 kg (192,925 lb)

Dry weight, unenclosed height

Solar Turbines Incorporated


P.O. Box 85376
FOR MORE INFORMATION 
San Diego, CA 92186-5376 Telephone: (+1) 619-544-5352
Caterpillar is a trademark of Caterpillar Inc. Solar, Titan, SoLoNOx and Turbotronic are E-mail: infocorp@solarturbines.com
trademarks of Solar Turbines Incorporated. Specifications subject to change without notice.
© 2020 Solar Turbines Incorporated. All rights reserved. Internet: www.solarturbines.com
DS130PG/0120/EO