iNstallation manual
L-2484
DOMETIC TURBO DX AC INSTALLATION MANUAL
CONTENTS
Introduction 4
Installation
Installation Overview 5
Blower Rotation 5
Mounting Brackets 7
Condensate Drain 7
Ducting 7
Seawater System 10
3 ENGLISH
INTRODUCTION
This manual provides proper installation information on the Turbo air conditioning unit
(a/c unit). Improper installation procedures can result in unsatisfactory performance
and/or premature failure of these a/c units. Before proceeding please read this manual
completely. If there are any statements or procedures in this manual that you do not
understand, contact the Dometic Environmental Corporation Applications Department
for assistance. Phone 954-973-2477 (8 am - 5 pm US Eastern Time), Fax 954-979-
4414, or email sales@DometicEnviro.com. Please see the separate control operation
manuals for installation of digital or mechanical controls.
Turbo a/c units are covered under the existing Dometic Environmental Corpora-
tion (Dometic) warranty policy contained in the corresponding control manual.
In the interest of product improvement, Dometic’s specifications and design are
subject to change without prior notice.
ENGLISH 4
INSTALLATION
Very Important Safety Considerations: Never install your air conditioner in the bilge
or engine room areas. Ensure that the selected location is sealed from direct access to bilge
and/or engine room vapors. Do not terminate condensate drain line within three feet of any outlet
of engine or generator exhaust systems, nor in a compartment housing an engine or generator,
nor in a bilge, unless the drain is connected properly to a sealed condensate or shower sump
pump.
Safety Warning – The a/c unit should never be Caution - High compressor temperature is normal.
placed such that it can circulate carbon monoxide, Do not touch.
fuel vapors or other noxious fumes into the boat’s
living spaces. Do not install or operate a self-contained Prior To Installation
unit in the engine room or near an internal combustion Read these instructions completely and then plan
engine. Failure to follow this precaution could result in all connections which must be made to the a/c unit
serious injury or death. including ducting, condensate drain line, seawater
inlet and outlet hoses, electrical power connection,
Ignition Protection Warning - Self-contained location of control, and seawater pump placement, to
units do not meet federal requirements for ignition assure easy access for routing and future servicing.
protection. Do not install in spaces containing gaso-
line engines, tanks, LPG/CPG cylinders, regulators, Installation Overview
valves or fuel line fittings. Failure to comply may result See Figure 1 for an overview of a typical Turbo a/c
in injury or death. system installation.
The following is a summary of the labels on the unit: Placement of A/C Unit
IMPORTANT INSTALLATION NOTE: The Turbo
Danger - Electrical shock hazard. Disconnect condensate base pan is equipped with vibration isola-
voltage at main panel or power source before opening tors installed in the bottom of the pan. These isolators
any cover. Failure to comply may result in injury or are designed to dampen the vibration caused by the
death. operating a/c unit from transferring into the mounted
surface. Care must be taken when moving the a/c
Warning - This component does not meet federal unit across mounting surfaces as isolators can be
requirements for ignition protection. Do not install in damaged. Isolators will not normally pull out of pan,
spaces containing gasoline engines, tanks, LPG/CPG but can turn sideways if dragged and may break if
cylinders, regulators, valves or fuel line fittings. Failure excessive dragging occurs. Unit must be picked up
to comply may result in injury or death. after moving to allow isolator to reset into well or
vibration isolation will be ineffective.
Warning - To minimize the hazard of electrical shock
and personal injury, this component must be effec- The a/c unit must be mounted to a low flat level
tively grounded. Refer to the installation guidelines for surface, in bottom of locker, under a bunk or dinette
further information. seat, or in a similar location. Read the safety consider-
ations above and see Figure 1 before mounting unit.
5 ENGLISH
INSTALLATION
ENGLISH 6
INSTALLATION
Air Filters
FIGURE 2. Blower rotation
Air filters are necessary to remove air borne particu-
lates from the cabin air and to keep the evaporator coil
Mount unit with condenser/evaporator coil directly clean. One, and only one, air filter must be installed
behind return air grill or with at least 3" (76mm) of for each air conditioner unit. Install the air filter either
air circulation clearance if adjacent to a bulkhead or on the a/c unit or in the return air (RA) grill. The a/c unit
other obstructions. See Figure 3. Compressor should air filter mounts in the slots in front of the evaporator
be mounted away from return air grill if possible to coil (behind the condenser coil). Or, the return air filter
minimize sound level in cabin. attaches to the back of the RA grill. Clean the air filters
regularly per instructions in Owner’s Control Manual.
Mounting Brackets
Grills and Transition Boxes
The four mounting brackets provided should be
placed around edge of drain pan as equally spaced Install the supply air grill as high as possible in a loca-
as possible. Secure a/c unit to a flat level mounting tion that will provide uniform air distribution through-
surface. Brackets with vibration isolators and sleeves out the cabin; grill louvers should be directed upward.
are provided. Customer is to supply screw or bolts. The return air grill should be installed as low and close
See Figure 4. to the a/c unit as possible to insure direct uninterrupt-
ed airflow to the evaporator. The return air grill should
Condensate Drain have a minimum four inches 4"(101.6mm) of air circu-
lation clearance in front of it, free from any furniture or
For installation of the condensate drain please see other obstructions. See Figure 3.
Figure 4 and follow these instructions:
In no instance should a supply air discharge be
1. Remove the aft-most-facing drain pan slug (knock- directed towards a return air grill, as this will cause
out) from the drain pan. To do this, use the supplied the system to short cycle. Allow for adequate clear-
fitting by inserting the hose barb side into the drain ance behind the supply air grill(s) for the transition box
hole and, with one quick strike of a rubber mallet, and ducting connection. See Figure 5 for minimum
knock out the slug. Remove slug from pan. grill sizes.
7 ENGLISH
INSTALLATION
ENGLISH 8
INSTALLATION
9 ENGLISH
INSTALLATION
2. Slide the mylar duct hose around the mount ring • Insulated when located in high heat load areas (hull
until it bottoms out. side, mechanical compartments, etc.).
3. Screw 3 or 4 stainless steel sheet metal screws • Be properly protected against potential damage
through the duct hose into the transition ring. Make when routed through open areas.
sure to catch the wire in the duct hose with the heads
of the screws. Do not use band clamps, as the hose • Do not route ducting through engine room or any
will slide off. area where it may be exposed to dangerous vapors
or exhaust fumes.
4. Wrap duct tape around the ducting and ring joint to
prevent any air leaks. Seawater System
5. Pull the insulation back up over the mylar to the ring Several guidelines should be followed during the
and tape this joint. installation of the seawater system. If the circulation
pump is centrifugal and not self-priming, it must be
6. Remove excess ducting and use the same connec- mounted so that it is always at least one foot below
tion method at the supply air grill. the water line regardless of which tack the vessel is
on. Pump may be mounted horizontally or vertically,
Minimum Duct Diameter (in/mm) 4/102 5/127 6/152 6/152 7/178 7/178
Minimum Duct Area (sq in/cm) 12.6/81 19.6/126 28.3/183 28.3/183 38.5/248 38.5/248
Minimum R/A Grill (sq in/cm) 64/413 80/516 100/645 130/839 144/929 160/1032
Minimum S/A Grill (sq in/cm) 32/206 48/310 60/387 70/452 76/490 80/516
ENGLISH 10
INSTALLATION
however the discharge must always be above the from any foreign matter. Failure to install a seawater
inlet. Pump head should be rotated toward the direc- strainer will void the pump and unit warranty.
tion of water flow. See Figure 7.
The seawater system should be installed with an
Install the seawater scoop intake as far upward incline from the seawater scoop and seacock,
below the water line and as close to the keel through the strainer, to the inlet of the pump and
as possible in any application, but especial- then up to the inlet of the a/c unit’s condenser coil.
ly on a sailboat. The seawater scoop must The discharge from the a/c unit should then run to
remain in the water under all conditions or the seawater outlet thru-hull fitting which should be
air will get into the pump. Turn air condition- located where it can be visually checked for water
er off in rough seas. The seawater scoop intake flow and as close as practicable to the waterline to
must face forward and not be shared with any other reduce noise. All hose connections shall be secured
pump. by means of two double/reversed stainless steel hose
clamps. Use Teflon tape on all threaded connections.
A seawater strainer is mandatory between the shut
off valve (seacock) and the pump to protect the pump
11 ENGLISH
INSTALLATION
The following is a summary of the seawater system 5/8" (15.9mm) reinforced marine grade hose. Connect
installation: the discharge from the condenser coil to the over-
board discharge thru-hull fitting with 5/8" (15.9mm)
1. Install the seawater scoop thru-hull inlet as close to reinforced marine grade hose.
the keel and as far below the water line as possible,
facing forward. Bed the scoop with a marine sealant 7. Avoid loops, high spots or the use of 90° elbows
designed for underwater use. with seawater hose (each 90° elbow is equivalent to
2.5' (0.762M) of hose and a 90° elbow on the pump
2. Install a bronze, full flow seacock on the seawater outlet is equivalent to 20' (61M) of hose.
scoop thru-hull inlet.
8. Double clamp all hose connections with two stain-
3. Install a seawater strainer below the level of the less steel clamps, reversing the clamps.
pump with access to filter.
9. Use Teflon tape on all threaded connections.
4. Mount the pump above the strainer and at least
one foot below the waterline. 10. Connect all metallic parts in contact with seawater
to the vessel’s bonding system including the speed
5. Connect the seacock and strainer with an uphill run scoop inlet, strainer, pump and the air conditioner.
of reinforced marine grade hose. Failure to do so will void warranty.
ENGLISH 12
INSTALLATION
13 ENGLISH
INSTALLATION
ENGLISH 14
INSTALLATION
Installation Checklist & Final Inspection • Strainer mounted below pump with access to filter
(Review prior to and after installation.)
• Double/reversed stainless steel hose clamps on all
hose connections below the water line
Note: Refer to the separate operation manual for
installation and operation of controls.
• Teflon tape on all threaded connections
• Attached to solid level platform with hold down clips • Pump relay panel, if used, must have its own circuit
provided breaker sized for the pump (20 amp max)
• Condensate drain routed aft and down hill to a • All metal fittings should be bonded
sealed sump (not bilge)
15 ENGLISH
Dometic Environmental Corporation
2000 N. ANDREWS AVE. EXT. I POMPANO BEACH, FL 33069 USA I 954-973-2477 I FAX 954 979 4414
P.O. BOX 15299 I RICHMOND, VA 23227 USA I 804-746-1313 I FAX 804-746-7248
www.DometicEnviro.com I sales@DometicEnviro.com