ADNOC GAS
HEAT LOAD CALCULATION
FOR SENIOR MESS HALL & SUBSTATION‐04
AGREEMENT NO: 4700018376
ELECTRICAL WORKS FOR SUBSTATION‐4 &
SENIOR MESS HALL AT AL MAHA CAMP
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
RECORDS OF REVISIONS
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
Contents
COMPLIANCE FOR ENGINEERS COMMENTS FOR REV‐00 ..................................................................... 4
1) INTRODUCTION ......................................................................................................................................... 6
2) BRIEF DESCRIPTION ABOUT THE PROJECT ................................................................................................ 6
3) SCOPE OF WORK ....................................................................................................................................... 6
a) PART A (SUB STATION‐4) ...................................................................................................................... 6
b) PART B (SENIOR MESS HALL) ................................................................................................................ 6
1)EXFLITRATION DETAILS (SENIOR MESS HALL & SUBSTATION‐04) ............................................................. 7
1.(a) ‐ EXFILTRATION DETAILS – KITCHEN HOOD SENIOR MESS HALL ...................................................... 8
2.(b) ‐ EXFILTRATION THROUGH DOORS SENIOR MESS HALL .................................................................. 8
3.(b) ‐ EXFILTRATION THROUGH DOORS SUBSTATION‐04 (SS‐4) ............................................................. 9
4. FRESH AIR CALCULATION ........................................................................................................................ 10
5. U VALUE CALCULATION .......................................................................................................................... 12
WALL LAYERS DETAILS (INSIDE TO OUTSIDE) .................................................................................. 13
ROOF DETAILS ................................................................................................................................. 13
DOOR DETAILS................................................................................................................................. 13
WINDOW DETAILS ........................................................................................................................... 13
6. HEAT DISSIPATION .................................................................................................................................. 15
7. AIR BALANCING ....................................................................................................................................... 21
8. HVAC EQUIPMENT SIZING ....................................................................................................................... 24
9. COMPUTER PRINTOUTS FOR HEAT LOAD CALCULATION FOR SENIOR MESS HALL & SUBSTATION‐04 . 26
1) SENIOR MESS HALL HEAT LOAD CALCUALTION .................................................................................. 27
(a)AHU‐1 & AHU‐2 COVERING AREAS ARE MENTIONED BELOW ........................................................... 27
(b) AHU‐3 (KITCHEN) COVERING AREAS ARE MENTIONED BELOW ........................................................ 27
2) SUBSTATION HEAT LOAD CALCUALTION ............................................................................................ 74
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
3) SCOPE OF WORK
Supply, Inspection, installation, testing & commissioning of electrical, telecom & HVAC system
pertaining to the senior mess hall in Al Maha Camp.
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
1)EXFLITRATION DETAILS (SENIOR MESS HALL & SUBSTATION-04)
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
EXFILTRATION IN DINING HALL AREA (SENIOR MESS HALL)
CRACK CRACK CRACK DIFF AIR AIR
WIDTH HEIGHT QTY IN
SL NO LOCATION DOOR LENGTH WIDTH AREA IN PRE. Δp FLOW FLOW
IN M IN M NOS
IN M IN M M3 (Pa) (M3/S) L/S
1 DINING (NE) DOOR (AD‐01) 2.20 1.80 1.00 8.00 0.003 0.02 15.00 0.08 77.15
2 DINING (NW) DOOR (AD‐02) 2.50 1.60 1.00 8.20 0.003 0.02 15.00 0.08 79.08
3 DINING (SE) DOOR (AD‐01) 2.20 1.00 1.00 6.40 0.003 0.02 15.00 0.06 61.72
TOTAL EXFILTRATION IN DINING HALL AREA (L/S) 217.95
EXFILTRATION IN KITCHEN AREA (SENIOR MESS HALL)
CRACK
CRACK CRACK
SL NO LOCATION DOOR WIDTH HEIGHT QTY WIDTH Δp (Pa) (M3/S) L/S
LENGTH AREA
IN M
1 ELE. ROOM DOOR (SD‐02) 3.00 2.00 1.00 10.00 0.003 0.03 1.00 0.02 24.90
2 POT STORAGE DOOR (SD‐03) 2.20 1.00 1.00 6.40 0.003 0.02 1.00 0.02 15.94
3 SOLID WASTE DOOR (SD‐03) 2.20 1.00 1.00 6.40 0.003 0.02 1.00 0.02 15.94
4 RECEIVING AREA DOOR (SD‐04) 2.20 1.60 1.00 7.60 0.003 0.02 1.00 0.02 18.92
TOTAL EXFILTRATION IN KITCHEN AREA (L/S) 75.70
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
EXFILTRATION IN SUBSTATION ‐04
CRACK CRACK DIFFERENTIAL AIR AIR
HEIGHT QTY IN CRACK
SL NO DOOR REF WIDTH IN M LENGTH WIDTH PRESSURE FLOW FLOW
IN M NOS AREA
IN M IN M Δp (Pa) (M3/S) L/S
1 SUBSTATION‐04 2.50 2.00 2.00 9.00 0.003 0.03 30.00 0.25 245.49
TOTAL EXFILTRATION IN SUBSTATION‐04 245.49
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
A B C D E F
MIN. FA
MINIMUM FRESH AIR REQUIREMENT BASED ON ASHRAE 62.1 &
ROOM SIZE REQUIREMENT BY
AGES SELECTED
ACH METHOD
ROOM EXFILT. EXTRACT FRESH AIR
Sl No. LOCATION / ROOM NAME
VOLUME TOTAL L/S TOTAL TOTAL VENT NO. OF AIR AIR MAX
NO OF LPS PER LPS PER TOTAL C/D/E/F
AREA HEIGHT FOR LPS PER AIR MAX OF AIR
PERSON PERSON AREA VENT AIR
PERSONS AREA (A&B) CHANGE
M2 M M3 Note 2* LPS ACH LPS LPS LPS LPS
1 Bakery & pastry area 53.5 3 160.5 2 3.8 7.6 0.9 48.15 48.15 1 44.58 237.47 237.47
2 Dry storage area 30.5 3 91.5 0.3 9.15 9.15 1 25.42 25.42
3 Chang. room-2 20 3 60 0.3 6 6 10 166.67 125 166.67
4 Toilet & Wash area 20 3 60 0.3 6 6 10 166.67 175 175.00
5 Chef's office 7.7 3 23.1 1 3.8 3.8 0.3 2.31 3.8 1 6.42 6.42
6 Chemical storage 4.4 3 13.2 0.3 1.32 1.32 1 3.67 3.67
7 Cold kitchen 23 3 69 1 3.8 3.8 0.6 13.8 13.8 1 19.17 19.17
8 Dining hall 902.3 5.8 5233.34 612 3.8 2325.6 0.9 812.07 2325.6 1 1453.71 217.95 2325.60
9 Electrical room 45.8 5.8 265.64 0.3 13.74 13.74 1 73.79 24.9 73.79
10 Vegetable prep.area 26.6 3 79.8 1 3.8 3.8 0.3 7.98 7.98 1 22.17 22.17
11 Poultry prep. area 18 3 54 1 3.8 3.8 0.3 5.4 5.4 10 150.00 150.00
12 Meat prep area 17.7 3 53.1 1 3.8 3.8 0.3 5.31 5.31 10 147.50 147.50
13 Fish prep. area 18 3 54 1 3.8 3.8 0.3 5.4 5.4 10 150.00 150.00
14 Pot wash&storage 22.6 3 67.8 0.3 6.78 6.78 1 18.83 346.43 346.43
15 Hot cooking area 111.8 3 335.4 6 3.8 22.8 0.6 67.08 67.08 1 93.17 696.32 696.32
16 Dish wash&storage area 36.4 3 109.2 1 3.8 3.8 0.3 10.92 10.92 1 30.33 433.31 433.31
17 Parcel room 20 3 60 0.3 6 6 1 16.67 16.67
18 Receiving area 25 3 75 0.3 7.5 7.5 1 20.83 18.92 20.83
19 Servery area 40 3 120 2 3.8 7.6 0.3 12 12 1 33.33 33.33
20 Solid waste 17.5 5.8 101.5 0.3 5.25 5.25 1 28.19 15.93 28.19
21 Vegetable wash area 16.1 3 48.3 1 3.8 3.8 0.3 4.83 4.83 1 13.42 13.42
22 Live Cooking area 34.5 3 103.5 2 3.8 7.6 0.6 20.7 20.7 1 28.75 500 500.00
23 Corridor 80 3 240 0.3 24 24 1 66.67 66.67
5658.03
EQUATION : ACH = (3.6*Airflow) / Volume (FROM ASHRAE 62.1)
NOTE : Exhaust Air considered as 80% of the fresh air delivering to the Zones
NOTE 2 : Total number of persons (20 persons) indicated in the whole kitchen area is presumed to be the same person(s) who will work in each area in the kitchen.
NOTE : Extract air for Meat preparation, Poultry preparation and Fish preparation shall be calculated based on 10 air changes per hour.
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
5. U VALUE CALCULATION
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
ROOF DETAILS
Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg K) (m²ꞏK)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.12064 0.0
Fascia Sheet 12.700 800.9 1.09 0.07890 10.2
Air space 0.000 0.0 0.00 0.16026 0.0
RSI-2.5 board insulation 50.800 32.0 0.92 2.44598 1.6
Built-up roofing 9.525 1121.3 1.47 0.05855 10.7
Outside surface resistance 0.000 0.0 0.00 0.05864 0.0
Totals 73.025 - 2.92297 22.5
DOOR DETAILS
Door U-Value 0.534 W/(m²ꞏK)
Glass U-Value 0.530 W/(m²ꞏK)
Glass Shade Coefficient 0.800
WINDOW DETAILS
amasood@adnoc.ae
99+ 90 of 91
Compose
Regards,
Mail
Anil
Inbox 372
Chat
Starred From: Ali Salem Al Zaabi (ADNOC Gas Processing - OHX) <asalzabi@adnoc.ae>
Sent: Wednesday, May 25, 2022 7:27 AM
Snoozed To: Anil Kumar Kurup (ADNOC Gas Processing - OHX) <akurup@adnoc.ae>
Spaces Cc: Mansoor Al Mansoori (ADNOC Gas Processing - OHX) <mansoor.a@adnoc.ae>; Arshad Masood (ADNOC Gas Processing - OHX) <amasood@adnoc.ae>
Sent
Subject: Data Input for Heat Load Calculation for Senior Kitchen
Drafts 36
Meet ADNOC Classification: Internal
More
Dear Mr. Anil,
Labels
Request your support to provide the available details of the followings (this in order to prepare for heat load calculation):-
1. Orientation of the building. ( Copy of location plan with Restaurant attached)
2. Details of wall ( Hollow block work cavity wall with insulation)
3. Details of door (External Aluminum Glazed doors and steel doors for service rooms & internal wooden doors)
4. Details of glass
5. U value /construction of wall : U<0.53W/m2K
6. U value /construction of door U<0.53W/m2K
7. U value /construction of glass U<0.53W/m2K
8. Details of the hoods ( Kitchen equipment under procurement. Apply Standard values)
9. Details of the heat dissipation from the kitchen equipment’s ( Kitchen equipment under procurement. Apply Standard values)
The following is the units and format for reference.
https://mail.google.com/mail/u/0/?ogbl#search/amasood%40adnoc.ae/FMfcgzGsmqzvBbwGJkwSbkvLMrBhmQjs 1/1
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
6. HEAT DISSIPATION
HEAT DISSIPATION DETAILS FOR KICHEN APPLIANCES / EQUIPMENTS
A ‐ RECEIVING AREA
C ‐ GARBAGE ROOM
D ‐ VEGETABLE WASH AREA
E ‐ VEGETABLE PREP. AREA
VEGETABLE PREPARATION MACHINES ‐ CL
7 E.13 1 2.7 2.7 1.62 1620
55E+1927 Disc
ICE MACHINE ‐ AIR COOLED DICE CUBE‐150
10 E.17 1 1.2 1.2 0.72 720 7506
KG/24 HR
VERTICAL CUTTER MIXER ‐ ROBOT COUPE
12 E.25 1 2.7 2.7 1.62 1620
R5A Plus‐1500
F ‐ POULTRY PREP. AREA
BONE SAW‐ BLADE LENGTH 1550 MMX16
29 G.19 1 1 1 0.6 600
MM
H ‐ FISH PREP. AREA
I‐POT WASH AREA
P ‐ LIVE COOKING
2 WELL ELECTRIC PASTA COOKER‐40+40
45 J.15 1 20 20 COMING UNDER HOOD AREA
LTRS
S/S ISLAND TYPE DOUBLE SKIN HOOD‐
49 J.21 1 0.08 0.08 COMING UNDER HOOD AREA
LIGHTING
9852
ELECTRIC BOILING PAN INDIRECT HEATING
50 J.25 2 21.5 43 COMING UNDER HOOD AREA
150 LTRS
Q ‐ PARCEL ROOM
S/S COLD BAIN MARIE WITH NEUTRAL
119 Q.04 1 1 1 0.6 600
COMPARTMENT + SLIDING DOORS
S/S HOTBAIN MARIE WITH NEUTRAL
120 Q.05 1 3 3 1.8 1800
COMPARTMENT + SLIDING DOORS
6000
S/S HEATED CUPBOARD WITH SLIDING
121 Q.06 1 3 3 1.8 1800
DOORS
S/S UPRIGHT HOT CABINET WITH HINGED
122 Q.07 1 3 3 1.8 1800
DOORS
S ‐ DAILY CHILLER ROOM
63 K.07 FREESTANDING DOUGH SHEETER 1 5 5 3
82 K.37 DOUGH DIVIDER ‐ FREESTANDING 1 5 5 3
L ‐ DISH WASH AREA
S/S HOT CUPBOARD WITH 2 MID SHELF &
87 N.06 2 1.6 3.2 1.92 1920
SLIDING DOORS +RSB
S/S 6 WELL HOT BAIN MARIE WITH TRAY
88 N.10 SLIDE, SNEEZE GUARD &HOT 3 4 12 7.2 7200
CUPBOARD BOELOW
S/S COLD BAIN MARIE WITH TRAY SLIDE,
89 N.11 SNEEZE GUARD &COLD CABINET 2 1.5 3 1.8 1800
12402
BELOW
90 N.12 2 DOOR UPRIGHT REFRIGERATOR 2 0.57 1.14 0.684 684
DINING AREA
O ‐ COLD KITCHEN
7. AIR BALANCING
AIR BALANCING FOR SENIOR MESS HALL AREA
Supply Air Flow Return Air Flow Exfiltration In Exhaust Air In
Sl No Zone Name Fresh Air in L/s
in (L/s) in L/s L/s L/s
1 BAKERY & PASTRY AREA 3350 3112.53 237.47 237.47 0
2 B‐DRY STORAGE AREA 239 213.58 25.42 22.878
3 CHANG. ROOM‐2 237 237.00 260.7
4 CHEF'S OFFICE 42 35.58 6.42 5.778
5 CHEMICAL STORAGE 74 70.33 3.67 81.4
6 COLD KITCHEN 890 870.83 19.17 17.253
7 CORRIDOR 300 233.33 66.67 60.003
8 ELECTRICAL ROOM 326 252.21 73.79 24.9 0
9 E‐VEGETABLE PREP.AREA 831 808.83 22.17 19.953
10 F‐POULTRY PREP. AREA 286 136 150 165
11 G‐MEAT PREP AREA 355 207.5 147.5 162.25
12 H‐FISH PREP. AREA 166 16 150 165
13 I‐POT WASH&STORAGE 346.43 0 346.43 346.43 0
14 J‐HOT COOKING AREA 1350 653.68 696.32 696.32 0
15 L‐DISH WASH&STORAGE AREA 479 45.69 433.31 433.31 0
16 Q‐PARCEL ROOM 180 163.33 16.67 15.003
17 RECEIVING AREA 286 265.17 20.83 18.92 0
18 SOLID WASTE 169 0 28.19 15.93 140.81
19 TOILET & WASH AREA 175 0 175 192.5
20 VEGETABLE WASH AREA 136 122.58 13.42 12.078
21 Dining hall 10035 7709.4 2325.6 217.95 1896.885
22 Servery area 1260 1226.67 33.33 29.997
23 Live Cooking Area 774 274 500 500 0
1. Exhaust air thru Fresh Air Handling Unit shall be 90% of the Fresh Air to maintain slightly positive pressure in the space.
2. Fresh (Outdoor) air ventilation = Supply Air, refer to HAP calcs
3. Exhaust air flow rate from canopy hood from Kitchen equipment vendor
4. Treated fresh air flow rate to Kitchen hood is assumed as 90% of exhaust air
5. Supply air shall be based from the HAP calculations
6. For Changing room Supply Air ‐237 L/s (166.67+70.33) & Exhaust 110% of Supply Air
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
From Exfiltration calculation the air needs to make up inside the substation to
maintain the 30 Pa will be 245.79 L/s
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
Dining Hall,
Servery Area & Combined details for
2 AHU - 2 & 3 2 12125.00 9210.07 2858.93 23.50 17.30 12.70 12.10 204.00 158.00 500
Live Cooking AHU-2&3
Area
Senior Mess
3 FAHU 1 5728.38 3247.48 5658.03 51.10 28.60 20.20 18.30 261.00 209.00 500 Hall (Kitchen &
Dining)
1 Duty & 1
4 PACKAGE UNIT 1 3674.00 3428.21 245.79 26.00 18.30 14.30 13.60 57.70 51.60 250 Substation-04 Stand by
AGREEMENT NO: 4700018376 ELECTRICAL WORKS FOR
SUBSTATION-4 & SENIOR MESS HALL AT ALA MAHA CAMP
AT AL MAHA CAMP
For Senior Mess Hall consist of 3 no’s of AHU’s and 1 no. of FAHU is allocated as
HVAC equipment. In which chilled water from existing line is going to serve to cool the
building with the above mentioned equipment’s. As per Tender document the previous year peak
data’s only one chiller is working. And the chiller water from the existing line is enough to
provide cooling in Senior mess hall area.
Considering Senior Mess Hall 2 no’s of AHU’s is Serving for Dining Hall Area and 1
no. of AHU is serving in Kitchen area. And FAHU serving in both areas for Ventilation and
pressurization purpose.
Dining hall
Live cooking area
Servery area
Design Parameters:
24
Temperature ( °C )
22
20
18
16
14
12
10
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 1 1 1 1 1 1 1 1 1 1 1 1
Tuesday 1 1 1 1 1 1 1 1 1 1 1 1
Wednesday 1 1 1 1 1 1 1 1 1 1 1 1
Thursday 1 1 1 1 1 1 1 1 1 1 1 1
Friday 1 1 1 1 1 1 1 1 1 1 1 1
Saturday 1 1 1 1 1 1 1 1 1 1 1 1
Sunday 1 1 1 1 1 1 1 1 1 1 1 1
Holiday 1 1 1 1 1 1 1 1 1 1 1 1
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
O = Occupied; U = Unoccupied
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 1 1 1 1 1 1 1 1 1 1 1 1
Tuesday 1 1 1 1 1 1 1 1 1 1 1 1
Wednesday 1 1 1 1 1 1 1 1 1 1 1 1
Thursday 1 1 1 1 1 1 1 1 1 1 1 1
Friday 1 1 1 1 1 1 1 1 1 1 1 1
Saturday 1 1 1 1 1 1 1 1 1 1 1 1
Sunday 1 1 1 1 1 1 1 1 1 1 1 1
Holiday 1 1 1 1 1 1 1 1 1 1 1 1
Wall Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 0.535 W/(m²ꞏK)
Roof Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 0.342 W/(m²ꞏK)
WINDOW-AW-01-(1.8 M X 1.5 M)
Window Details:
Detailed Input No
Height 1.80 m
Width 1.50 m
Overall U-Value 0.530 W/(m²ꞏK)
Overall Shade Coefficient 0.800
WINDOW-AW-04-(1.5M X 0.6M)
Window Details:
Detailed Input No
Height 1.50 m
Width 0.60 m
Overall U-Value 0.530 W/(m²ꞏK)
Overall Shade Coefficient 0.800
Window Details:
Detailed Input No
Height 0.60 m
Width 0.40 m
Overall U-Value 0.530 W/(m²ꞏK)
Overall Shade Coefficient 0.800
Door Details:
Gross Area 4.0 m²
Door U-Value 0.534 W/(m²ꞏK)
Glass Details:
Glass Area 4.0 m²
Glass U-Value 1.200 W/(m²ꞏK)
Glass Shade Coefficient 0.800
Glass Shaded All Day? No
Door Details:
Gross Area 4.0 m²
Door U-Value 0.530 W/(m²ꞏK)
Glass Details:
Glass Area 4.0 m²
Glass U-Value 0.530 W/(m²ꞏK)
Glass Shade Coefficient 0.800
Glass Shaded All Day? No
Door Details:
Gross Area 6.0 m²
Door U-Value 0.534 W/(m²ꞏK)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 0.534 W/(m²ꞏK)
Glass Shade Coefficient 0.500
Glass Shaded All Day? No
Door Details:
Gross Area 2.2 m²
Door U-Value 0.534 W/(m²ꞏK)
Glass Details:
Glass Area 2.2 m²
Glass U-Value 0.534 W/(m²ꞏK)
Glass Shade Coefficient 0.800
Glass Shaded All Day? No
DOOR-SD-04(2.2M X 1.6M)
Door Details:
Gross Area 3.5 m²
Door U-Value 0.534 W/(m²ꞏK)
Glass Details:
Glass Area 3.5 m²
Glass U-Value 0.534 W/(m²ꞏK)
Glass Shade Coefficient 0.800
Glass Shaded All Day? No
1. General Details:
Floor Area 53.5 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 800.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 27.7 4 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 53.5 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 53.5 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 30.5 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 720.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 17.6 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 30.5 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 30.5 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
CHANG. ROOM-2
1. General Details:
Floor Area 39.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 320.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.1 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 23.6 0 0 0
SE 25.4 4 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 39.0 0 0
5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 39.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
CHEF'S OFFICE
1. General Details:
Floor Area 7.7 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 50.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 7.7 0 0
5. Infiltration:
Design Cooling 0.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 7.7 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
CHEMICAL STORAGE
1. General Details:
Floor Area 4.4 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.00 W/m² Activity Level User defined
Ballast Multiplier 1.25 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 14.0 2 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.4 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 4.4 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
COLD KITCHEN
1. General Details:
Floor Area 23.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 750.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 23.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
CORRIDOR
1. General Details:
Floor Area 89.0 m²
Avg. Ceiling Height 5.8 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 400.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 6.3 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 89.0 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 89.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
DINING HALL
1. General Details:
Floor Area 902.3 m²
Avg. Ceiling Height 6.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 612.0 People
Wattage 6900.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 313.0 6 0 1
NW 134.0 2 0 1
SE 167.0 3 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 902.3 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 902.3 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
ELECTRICAL ROOM
1. General Details:
Floor Area 45.8 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 400.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 33.3 0 0 0
SW 28.2 0 0 1
NE 4.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 45.8 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 45.8 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
E-VEGETABLE PREP.AREA
1. General Details:
Floor Area 26.6 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 750.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 26.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 26.6 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 540.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.1 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 18.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 17.7 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 360.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.7 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 17.7 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 18.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 10.00 W/m² Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 18.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
I-POT WASH&STORAGE
1. General Details:
Floor Area 22.6 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 300.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 23.2 2 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 22.6 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 22.6 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 111.8 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 850.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 29.5 4 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 111.8 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 111.8 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 36.4 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 400.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 36.4 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 36.4 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 34.5 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 300.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 18.1 0 0 0
NW 25.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 34.5 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 34.5 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
Q-PARCEL ROOM
1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.00 W/m² Activity Level User defined
Ballast Multiplier 1.25 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 42.3 2 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 20.0 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 20.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
RECEIVING AREA
1. General Details:
Floor Area 25.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 300.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.1 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 18.4 1 0 0
NW 50.3 0 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 25.0 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 25.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
SERVERY AREA
1. General Details:
Floor Area 40.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 300.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 40.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 40.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
SOLID WASTE
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.00 W/m² Activity Level User defined
Ballast Multiplier 1.25 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 37.4 0 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 20.0 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 390.0 Watts Activity Level User defined
Ballast Multiplier 1.25 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.1 W/person
Schedule ALL SCHEDULE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 20.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 20.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 16.1 m²
Avg. Ceiling Height 4.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 10.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 80.0 W/person
Schedule ALL SCHEDULE Latent 60.0 W/person
Schedule ALL SCHEDULE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 34.3 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 16.1 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 16.1 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Air System Name AHU-DINING HALL
Equipment Type Chilled Water AHU
Air System Type Single Zone CAV
Number of zones 1
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
DINING HALL x1
LIVE COOKING AREA x1
SERVERY AREA x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 25.0 21.1 18.3 0.83 100 0.0 0.0
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 0 %
5. Equipment Data
No equipment data required for this system.
1. General Details:
Air System Name KITCHEN AHU
Equipment Type Chilled Water AHU
Air System Type Single Zone CAV
Number of zones 1
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
BAKERY & PASTRY AREA x1
B-DRY STORAGE AREA x1
CHANG. ROOM-2 x1
CHEF'S OFFICE x1
CHEMICAL STORAGE x1
COLD KITCHEN x1
CORRIDOR x1
ELECTRICAL ROOM x1
E-VEGETABLE PREP.AREA x1
F-POULTRY PREP. AREA x1
G-MEAT PREP AREA x1
H-FISH PREP. AREA x1
I-POT WASH&STORAGE x1
J-HOT COOKING AREA x1
L-DISH WASH&STORAGE AREA x1
Q-PARCEL ROOM x1
RECEIVING AREA x1
SOLID WASTE x1
TOILET & WASH AREA x1
VEGETABLE WASH AREA x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 23.0 21.1 18.3 0.83 100 0.0 0.0
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 0 %
5. Equipment Data
No equipment data required for this system.
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
DINING HALL 1 120.1 Jul 1400 9977 10.3 902.3 11.06
LIVE COOKING AREA 1 9.2 Jul 1400 766 0.6 34.5 22.21
SERVERY AREA 1 15.2 Jul 1400 1260 0.2 40.0 31.50
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 L/s
0.016
0.012
4
5 0.010
1 23
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
BAKERY & PASTRY AREA 1 40.3 Sep 1500 3350 0.5 53.5 62.61
B-DRY STORAGE AREA 1 2.9 Jul 1400 239 0.3 30.5 7.83
CHANG. ROOM-2 1 2.9 Jul 1500 237 0.6 39.0 6.08
CHEF'S OFFICE 1 0.4 Jul 1400 35 0.0 7.7 4.55
CHEMICAL STORAGE 1 0.9 Sep 1600 74 0.1 4.4 16.83
COLD KITCHEN 1 10.7 Jul 1400 890 0.1 23.0 38.68
CORRIDOR 1 3.6 Jul 1400 300 0.5 89.0 3.37
ELECTRICAL ROOM 1 3.9 Aug 1500 326 0.8 45.8 7.11
E-VEGETABLE PREP.AREA 1 10.0 Jul 1400 831 0.1 26.6 31.23
F-POULTRY PREP. AREA 1 3.4 Jul 1400 286 0.1 18.0 15.89
G-MEAT PREP AREA 1 4.3 Jul 1400 355 0.1 17.7 20.08
H-FISH PREP. AREA 1 2.0 Jul 1400 166 0.1 18.0 9.25
I-POT WASH&STORAGE 1 2.7 Sep 1600 227 0.3 22.6 10.04
J-HOT COOKING AREA 1 16.2 Aug 1500 1350 0.9 111.8 12.07
L-DISH WASH&STORAGE AREA 1 5.8 Jul 1400 479 0.2 36.4 13.17
Q-PARCEL ROOM 1 8.2 Jul 1500 682 0.5 20.0 34.11
RECEIVING AREA 1 3.4 Jul 1700 280 0.7 25.0 11.18
SOLID WASTE 1 2.0 Sep 1600 166 0.4 17.5 9.48
TOILET & WASH AREA 1 1.4 Jul 1400 113 0.1 20.0 5.63
VEGETABLE WASH AREA 1 1.6 Jul 1400 137 0.4 16.1 8.49
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 L/s
0.016
0.012
0.010
1 23 4
5
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
0.012
1 24
0.010
65 3
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
EXTERNAL WALL-SUBSTATION
Wall Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 0.535 W/(m²ꞏK)
SUBSTATION ROOF
Roof Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 0.685 W/(m²ꞏK)
DOOR-01 (SS-4)
Door Details:
Gross Area 5.5 m²
Door U-Value 1.200 W/(m²ꞏK)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 3.293 W/(m²ꞏK)
Glass Shade Coefficient 0.880
Glass Shaded All Day? No
SUBSTATION -4 (SS-4)
1. General Details:
Floor Area 227.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 312.5 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 245.5 L/s
OA Requirement 2 0.00 L/(sꞏm²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 50.00 W/m² Activity Level User defined
Ballast Multiplier 1.25 Sensible 0.0 W/person
Schedule ALL SCHEDULE Latent 0.0 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 31.0 0 0 1
NW 92.0 0 0 0
SE 92.0 0 0 0
SW 31.0 0 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 227.0 0 0
5. Infiltration:
Design Cooling 0.35 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 227.0 m²
Total Floor U-Value 0.568 W/(m²ꞏK)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²ꞏK)/W
7. Partitions:
(No partition data).
1. General Details:
Air System Name PACKAGE UNIT
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
SUBSTATION -4 (SS-4) x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.9 26.7 21.1 18.3 0.83 100 0.0 0.0
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return
Safety Factors:
Cooling Sensible 0 %
Cooling Latent 0 %
Heating 0 %
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 57.7 kW
Design OAT 35.0 °C
Equipment Sizing Auto-Sized
Capacity Oversizing Factor 0 %
ARI Performance Rating 3.224 EER
DX System Configuration 1-stage compression, 1 circuit
Conventional Cutoff OAT 12.8 °C
Low Temperature Operation Used
Low Temperature Cutoff OAT -17.8 °C
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
SUBSTATION -4 (SS-4) 1 40.9 Jul 1400 3600 4.7 227.0 15.86
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 246 L/s
0.012
2
34 6 0.010
7
5
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35 40 45 50
Temperature ( °C )
0.012
0.010
0.008
0.006
1 2 6 7 34
0.004
8 5
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )