95-8527
Protect•IR® Multispectrum IR Flame Detector
X3301
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 13
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Optical Integrity (oi) . . . . . . . . . . . . . . . . . . . . . . 2 Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . 14
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3 oi Plate Removal and Replacement . . . . . . . . 14
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Periodic Checkout Procedure . . . . . . . . . . . . . . 15
Integral Wiring Compartment . . . . . . . . . . . . . . . 3 Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . 15
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . 18
Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 4
Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 5
ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 18
Protection Against Moisture Damage . . . . . . . . . 5
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . 5
Setting Device Network Addresses
APPENDIX A – FM APPROVAL AND
(EQP Model Only) . . . . . . . . . . . . . . . . . . . . 12
PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . . . 20
Protect•IR®
Multispectrum IR Flame Detector
X3301
Important
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X3301 includes the Automatic Optical Integrity
(oi ®) feature — a calibrated performance test that
is automatically performed once per minute to
verify complete detector operation capabilities. No
testing with an external test lamp is required.
A tricolor LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
DESCRIPTION fault conditions.
The X3301 Protect•IR® is a multispectrum infrared (IR)
Microprocessor controlled heated optics increase
flame detector. It provides unsurpassed detection of
resistance to moisture and ice.
fires from light to heavy hydrocarbon fuels combined
with the highest degree of false alarm rejection. The
The X3301 housing is available in copper-free aluminum
detector has Division and Zone explosion-proof
or stainless steel, with NEMA 4X and IP66 rating.
ratings and is suitable for use in indoor and outdoor
applications.
Outputs
The X3301 contains three IR sensors with their Relays
associated signal processing circuitry. The standard The standard detector is furnished with fire, fault and
output configuration includes fire, fault and auxiliary auxiliary relays. All three relays are rated 5 amperes
relays. Output options include: at 30 Vdc.
–– 0 to 20 mA output (in addition to the three relays)
The Fire Alarm relay has redundant terminals and
–– Pulse output for compatibility with existing controller normally open / normally closed contacts, normally
based systems (with fire and fault relays) de-energized operation, and latching or non-latching
–– Eagle Quantum Premier® (EQP) compatible model operation.
(no analog or relay outputs).
–– HART communication. The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
15.1 2 95-8527
The magnetic oi test is performed by placing a magnet General APPLICATION
by the marked location (mag oi) on the outside of Information
the detector. The manual oi test is accomplished by
connecting the oi lead (terminal 22) to power supply Response Characteristics
minus via an external switch. The magnet or switch Response is dependent on distance, type of fuel,
must be held in place for a minimum of 6 seconds temperature of the fuel, and time required for the fire to
to complete the test. Either of these test methods come to equilibrium. As with all fire tests, results must
activates the calibrated IR emitters. If the resulting be interpreted according to an individual application.
signal meets the test criteria, indicating that greater See Appendix A for fire test results.
than half of the detection range remains, the Alarm
relay changes state, the indicating LED changes to Important Application Considerations
red, and the 0-20 mA current output goes to 20 mA.
This condition remains until the magnet is removed or In applying any type of sensing device as a fire
the switch is released, regardless of whether the relays detector, it is important to know of any conditions that
are set for latching or non-latching operation. can prevent the device from responding to fire, and
also to know what other sources besides fire can cause
If less than half of the detection range remains, no the device to respond.
alarm is produced and a fault is generated. The fault
indication can be reset by momentarily applying the Welding
magnet or manual oi switch. Arc welding should not be performed within 40 feet of
the very high sensitivity detector, 10 feet of the medium
NOTE sensitivity detector, or 5 feet of the low sensitivity
Refer to Appendix A for FM verification of detector. It is recommended that the system be
Det-Tronics’ Optical Integrity o i function. bypassed during welding operations in situations where
the possibility of a false alarm cannot be tolerated.
Communication Gas welding mandates system bypass, since the gas
torch is an actual fire. Arc welding rods can contain
The X3301 is furnished with an RS-485 interface for organic binder materials in the flux that burn during the
communicating status and other information with welding operation and are detectable by the X3301.
external devices. The RS-485 supports MODBUS Welding rods with clay binders do not burn and will not
protocol, with the detector configured as a slave be detected by the X3301. However, system bypass is
device. always recommended, since the material being welded
may be contaminated with organic substances (paint,
NOTE oil, etc.) that will burn and possibly trigger the X3301.
The EQP model uses LON/SLC communication.
RS-485 communication is not available on the Artificial Lighting
EQP model.
The X3301 should not be located within 3 feet of
Data logging artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
Data logging capability is also provided. Status
conditions such as normal, power down, general and EMI/RFI Interference
oi faults, pre-alarm, fire alarm, time and temperature
are recorded. Each event is time and date stamped, The X3301 is resistant to interference by EMI and RFI,
along with the temperature and input voltage. Event and is EMC Directive compliant. It will not respond to a
data is stored in non-volatile memory when the event 5 watt walkie-talkie at distances greater than 1 foot. Do
becomes active, and again when the status changes. not operate a walkie-talkie within 1 foot of the X3301.
Data is accessible using the RS-485 port or the EQP
controller. Non-Carbon Fires
The X3301 is a multiple spectrum IR device with
Integral wiring compartment detection limited to carbonaceous fuels. It should not
All external wiring to the device is connected within be used to detect fires from fuels that do not contain
the integral junction box. The screw terminals accept carbon, such as hydrogen, sulfur and burning metals.
wiring from 14 to 24 AWG. The detector is furnished with
four conduit entries, with either 3/4 inch NPT or 25 mm
threads.
15.1 3 95-8527
Important safety notes INSTALLATION
Warning note
Do not open the detector assembly in a hazardous The recommended lubricant for threads and
area when power is applied. The detector contains O-rings is a silicone free grease (part number
limited serviceable components and should never 005003-001) available from Detector Electronics.
be opened. Doing so could disturb critical optical Under no circumstances should a lubricant
alignment and calibration parameters, possibly containing silicone be used.
causing serious damage. This type of damage
could be undetected and could result in failure to Detector Positioning
see a fire and/or false alarm. Detectors should be positioned to provide the best
unobstructed view of the area to be protected.
Caution The following factors should also be taken into
The wiring procedures in this manual are intended consideration:
to ensure proper functioning of the device under • Identify all high risk fire ignition sources.
normal conditions. However, because of the
many variations in wiring codes and regulations, • Be sure that enough detectors are used to adequately
total compliance to these ordinances cannot be cover the hazardous area.
guaranteed. Be certain that all wiring complies • Be sure that the unit is easily accessible for cleaning
with the NEC as well as all local ordinances. If and other periodic servicing.
in doubt, consult the authority having jurisdiction
• Locate and position the detector so that the fire
before wiring the system. Installation must be
hazard(s) are within both the field of view and
done by a properly trained person.
detection range of the device. Refer to Appendix A
for specific information.
Caution
To prevent unwanted actuation or alarm, • The detector should be aimed downward at least 10
extinguishing devices must be disabled prior to to 20 degrees to allow lens openings to drain. See
performing system tests or maintenance. Figure 1. The detector should be positioned so
that its field of view does not cover areas outside
Caution the hazardous area. This will minimize the possibility
The multispectrum IR flame detectors are to be of false alarms caused by activities outside the area
installed in places where the risk of mechanical requiring protection.
damages is low. • For best performance, the detector should be
mounted on a rigid surface in a low vibration area.
Attention
Remove the protective cap from the front of the • Dense fog, rain or ice can absorb IR radiation and
detector before activating the system. reduce the sensitivity of the detector.
Attention
Observe precautions for handling electrostatic
sensitive devices.
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
INCORRECT
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT C1974
15.1 4 95-8527
• Although IR detectors are less affected by smoke It is also recommended to install at least one breather,
than other detectors, the X3301 should not be placed according to local codes, at upper locations to provide
where rising combustion products can obscure ventilation and allow water vapor to escape.
its vision. If smoke is expected before fire, smoke
Conduit raceways should be inclined so that water will
or other alternative detectors should be used in
flow to low points for drainage and will not collect inside
conjunction with the X3301. For indoor applications,
enclosures or on conduit seals. If this is not possible,
if dense smoke is expected to accumulate at the
install conduit drains above the seals to prevent the
onset of a fire, mount the detector on a side wall at
collection of water or install a drain loop below the
least a few feet (approximately 1 meter) down from
detector with a conduit drain at the lowest point of the
the ceiling.
loop.
• If possible, fire tests should be conducted to verify
correct detector positioning and coverage. Conduit seals are not required for compliance with
explosion-proof installation requirements, but are highly
• For ATEX installations, the X3301 detector housing
recommended to prevent water ingress in outdoor
must be electrically connected to earth ground.
applications. Units with M25 thread must use an IP66
washer to prevent water ingress.
Wiring Procedure
Wire Size and Type
oi PLATE
15.1 5 95-8527
Relay and 0-20 mA Output Models EOL Resistors (Not Used with EQP Model)
Follow the instructions below to install the X3301. To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
1. Make field connections following local ordinances by EOL resistors, observe the following guidelines
and guidelines in this manual. when installing the resistors.
–– Figure 4 shows the wiring terminal strip located 1. Required EOL resistor power rating must be 5
inside the detector’s integral junction box. watts minimum.
–– Figure 5 shows the wiring terminal identification for note
the X3301 detector. EOL resistors must be ceramic, wirewound
–– Figure 6 shows an EOL resistor installed within the type, rated 5 watts minimum, with actual power
integral wiring compartment of the detector (refer to dissipation not to exceed 2.5 watts. This applies
“EOL Resistors” for details). to ATEX/IEC installations only.
–– Figures 7 and 8 provide examples of typical 2. Resistor leads should be cut to a length of
installations with a X3301 wired to a fire alarm approximately 1 1/2 inches (40 mm).
panel.
3. Bend the leads and install the EOL resistor as
–– If the detector is equipped with a 0 to 20 mA output, shown in Figure 6.
refer to Figures 9 through 12.
4. Maintain a 3/8 inch (10 mm) minimum gap between
2. Check all field wiring to be sure that the proper the resistor body and the terminal block or any
connections have been made. other neighboring parts.
Important NOTE
Do not test any wiring connected to the detector The EOL resistor can only be used within the
with a meg-ohmmeter. Disconnect wiring at flameproof terminal compartment. Unused
the detector before checking system wiring for apertures shall be closed with suitable blanking
continuity. elements.
4.0
(10.2)
4X ø0.42 3.0 13.1
(1.1) (7.6) (33.4)
4.0
(10.2)
10.6
(27.0)
E2069
15.1 6 95-8527
Figure 4—X3301 Terminal Block
19 18 17 16 15 14 13 12 11
B2126
BULKHEAD
15.1 7 95-8527
X3301 DETECTOR
FIRE ALARM PANEL
9 4-20 mA + 19 4-20 mA – SPARE 29
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
X3301 DETECTOR
FIRE ALARM PANEL
9 4-20 mA + 19 4-20 mA – SPARE 29
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
15.1 8 95-8527
X3301 IR DETECTOR X3301 IR DETECTOR
PLC PLC
600 Ω MAX 9 4-20 mA + 19 4-20 mA – SPARE 29 600 Ω MAX 9 4-20 mA + 19 4-20 mA – SPARE 29
AT 24 VDC AT 24 VDC
+ 8 4-20 mA + REF 18 4-20 mA – REF SPARE 28 + 8 4-20 mA + REF 18 4-20 mA – REF SPARE 28
– 7 COM FIRE COM FIRE 17 COM AUX 27 – 7 COM FIRE COM FIRE 17 COM AUX 27
4 TO 20 mA 6 N.O. FIRE N.O. FIRE 16 N.O. AUX 26 4 TO 20 mA 6 N.O. FIRE N.O. FIRE 16 N.O. AUX 26
5 N.C. FIRE N.C. FIRE 15 N.C. AUX 25 5 N.C. FIRE N.C. FIRE 15 N.C. AUX 25
+ +
24 VDC 24 VDC
4 COM FAULT COM FAULT 14 RS-485 A 24 4 COM FAULT COM FAULT 14 RS-485 A 24
– –
3 N.O. FAULT N.O. FAULT 13 RS-485 B 23 3 N.O. FAULT N.O. FAULT 13 RS-485 B 23
Oi TEST1 Oi TEST1
Figure 9—X3301 Detector Wired for Non-Isolated 0 to 20 mA Current Figure 10—X3301 Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sourcing) Output (Sinking)
24 VDC 24 VDC
– + X3301 IR DETECTOR + – X3301 IR DETECTOR
PLC PLC
600 Ω MAX 9 4-20 mA + 19 4-20 mA – SPARE 29 600 Ω MAX 9 4-20 mA + 19 4-20 mA – SPARE 29
AT 24 VDC AT 24 VDC
+ 8 4-20 mA + REF 18 4-20 mA – REF SPARE 28 + 8 4-20 mA + REF 18 4-20 mA – REF SPARE 28
– 7 COM FIRE COM FIRE 17 COM AUX 27 – 7 COM FIRE COM FIRE 17 COM AUX 27
4 TO 20 mA 6 N.O. FIRE 16 N.O. AUX 26 4 TO 20 mA 6 N.O. FIRE N.O. FIRE 16 N.O. AUX 26
N.O. FIRE
5 N.C. FIRE N.C. FIRE 15 N.C. AUX 25 5 N.C. FIRE N.C. FIRE 15 N.C. AUX 25
+ +
24 VDC 24 VDC
4 COM FAULT COM FAULT 14 RS-485 A 24 4 COM FAULT COM FAULT 14 RS-485 A 24
– –
3 N.O. FAULT N.O. FAULT 13 RS-485 B 23 3 N.O. FAULT N.O. FAULT 13 RS-485 B 23
Oi TEST1 Oi TEST1
Figure 11—X3301 Detector Wired for Isolated 0 to 20 mA Figure 12—X3301 Detector Wired for Isolated 0 to 20 mA
Current Output (Sourcing) Current Output (Sinking)
15.1 9 95-8527
EQP Model 5. Check all field wiring to be sure that the proper
1. Connect external wires to the appropriate terminals connections have been made.
inside the device junction box. (See Figure 13 for 6. Replace the device cover.
terminal identification.) 7. Make the final sighting adjustments and ensure that
2. Connect the shield of the power cable to “earth the mounting bracket hardware is tight.
ground” at the power source.
NOTE
3. Connect shields for the LON cable as indicated. See Refer to the Eagle Quantum Premier system
Figure 14. manual 95-8533 for information regarding power
NOTE and network communication cable requirements.
DO NOT ground any shields at the detector housing.
COM 1 A 5 15 COM 2 A
COM 1 B 4 14 COM 2 B
24 VDC + 2 12 24 VDC +
24 VDC – 1 11 24 VDC –
A2089
15.1 10 95-8527
15.1
+ +
– –
– POWER –
+ DISTRIBUTION +
+
–
+ – + –
CONTROLLER EQP3700DCIO EQP2100PSM EQPX3301 EQPX3301 EQPX3301 EQPX3301
P1 P1
6 SHIELD 3 4 SHIELD 9 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3
52 B 49 5 B 2 11 B 3 14 B 4 14 B 4 14 B 4 14 B 4
53 A 50 4 A 1 10 A 2 15 A 5 15 A 5 15 A 5 15 A 5
P6
BUS BAR P3
C 45 A2207
C 1 N
FAULT NO 46 P4 P3
B 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3
B IN–/OUT+ B + –
CH 1
CH 5
GND 5 57 GND GND 54 24 VDC 4 H
C COMMON C SUPPLY
RXD 2 58 RxD B 55
11
TXD 3 59 TxD A 56 A + SUPPLY A
DB-9 H N
P2 P3
CONNECTION B IN–/OUT+ B AC LINE
CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1– 5– 14 C COMMON C
+ –
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2– 6– 16 BATTERY
B IN–/OUT+ B
CH 3
CH 7
9 3+ 7+ 17
10 3– 7– 18 C COMMON C
11 4+
DIGITAL INPUTS
8+ 19
A + SUPPLY A
12 4– 8– 20
B IN–/OUT+ B
CH 4
CH 8
P4 P5
21 C C 33 C COMMON C
22 NO NO 34
RELAY 5
RELAY 1
23 NC NC 35
24 C C 36
25 NO NO 37
RELAY 6
RELAY 2
26 NC NC 38
27 C C 39
28 NO NO 40
RELAY 7
RELAY 3
29 NC NC 41
30 C C 42
31 NO NO 43
RELAY 4
RELAY 8
32 NC NC 44
95-8527
Figure 14—A Typical EQP System
ADDRESS SWITCHES SENSOR MODULE
REMOVED FROM HOUSING
A2191
Setting Field Device Addresses After setting address switches, record the address
Selection of the node address is done by setting rocker number and device type.
switches on an 8 switch “DIP Switch Assembly” within
the detector’s housing. Refer to Figure 15 for switch
location.
ON
WARNING
1 2 3 4 5 6 7 8
The network address switches are located within
BINARY
the detector housing. Disassembly of the detector VALUE 1 2 4 8 16 32 64 128
15.1 12 95-8527
STARTUP PROCEDURE Table 3—Current Level Output Troubleshooting Guide
15.1 13 95-8527
MAINTENANCE LOOSEN TWO CAPTIVE SCREWS
IMPORTANT
Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
GRASP VISOR AND
REMOVE oi PLATE
Warning
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that B2106
15.1 14 95-8527
Refer to the Inspector Monitor manual, 95-8581, for FEATURES
instructions regarding oi plate replacement and oi
system recalibration. • Long detection range to carbonaceous fires.
• Unequaled false alarm rejection.
X3301 Reflector Plates
• Responds to a fire in the presence of modulated
X3301 models are supplied with either a black or a blackbody radiation (i.e. heaters, ovens, turbines)
stainless steel reflector plate. These plates are not without false alarm.
interchangeable. Order the replacement that matches
• Microprocessor controlled heated optics for
the reflector plate on your X3301 detector.
increased resistance to moisture and ice.
Associated MANUALS
List of X3301 related manuals:
TITLE FORM NUMBER
Pulse 95-8528
EQP 95-8533
SIL 2 (Safety) 95-8582
HART Addendum 95-8577
Automotive Addendum 95-8534
Hangar 95-8548
15.1 15 95-8527
SPECIFICATIONS CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a maximum
OPERATING VOLTAGE— loop resistance of 500 ohms from 18 to 19.9 Vdc and 600
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). ohms from 20 to 30 Vdc.
Maximum ripple is 2 volts peak-to-peak.
LON Output—
POWER CONSUMPTION— Digital communication, transformer isolated (78.5 kbps).
Without heater: 4 watts at 24 Vdc nominal;
5.2 watts at 24 Vdc in alarm. TEMPERATURE RANGE—
4.5 watts at 30 Vdc nominal; Operating: –40°F to +167°F (–40°C to +75°C).
6.5 watts at 30 Vdc in alarm. Storage: –67°F to +185°F (–55°C to +85°C).
Heater only: 8 watts maximum. Hazardous location ratings from –55°C to +125°C.
Total power: 17 watts at 30 Vdc with EOL resistor installed
and heater on maximum. HUMIDITY RANGE—
EOL resistor must be ceramic, wirewound type, rated 0 to 95% relative humidity, can withstand 100%
5 watts minimum, with actual power dissipation not to condensing humidity for short periods of time.
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8577. CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
POWER UP TIME— the highest sensitivity lying along the central axis.
Fault indication clears after 0.5 second; device is ready Unlike conventional detectors, the X3301 provides full
to indicate an alarm condition after 30 seconds. coverage at a minimum of 70% of the maximum detection
distance.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc: Perfect cone of vision for methane fire detection — 100
The Fire Alarm relay has redundant terminals and feet on and off axis on “very high” setting.
normally open / normally closed contacts, normally
de-energized operation, and latching or non- Refer to Appendix A for FM Approved cone of vision
latching operation. data.
4.7
(11.9)
10.0 4.8
B2067
(25.4) (12.2)
15.1 16 95-8527
ENCLOSURE MATERIAL— CERTIFICATION—
Copper-free aluminum (painted) or 316 stainless steel.
FM ®
Vibration— APPROVED
VdS
A
R
PA
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire. For complete approval details, refer to the appropriate
Screw terminal required torque range is 3.5–4.4 in.-lbs. Appendix:
(0.4-0.5 N·m).
14 AWG (2.08 mm2) or 16 AWG (1.31 mm2) shielded Appendix A - FM
cable is recommended. Appendix B - CSA
Important: 18 Vdc minimum must be available at the Appendix C - ATEX/CE
detector. For ambient temperatures below –10°C and Appendix D - IECEx
above +60°C use field wiring suitable for both minimum Appendix E - VdS
and maximum ambient temperature. Appendix F - Offshore
Appendix G - Additional approvals.
Thread SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
WARRANTY PERIOD—
5 years.
15.1 17 95-8527
Replacement parts ORDERING INFORMATION
The detector is not designed to be repaired in the field. When ordering, please specify:
If a problem should develop, refer to the Troubleshooting X3301 IR Flame Detector
section. If it is determined that the problem is caused by Refer to the X3301 Model Matrix for details
an electronic defect, the device must be returned to the
factory for repair. Q9033 mount is required:
Q9033A for aluminum detectors only.
Q9033B for aluminum and stainless steel detectors.
DEVICE REPAIR AND RETURN
X-Series Flame Detector Accessories
Prior to returning devices, contact the nearest local
Part Number Description
Detector Electronics office so that a Return Material
000511-029 Converter RS485 to RS232
Identification (RMI) number can be assigned. A 103881-001 Converter RS485 to USB
written statement describing the malfunction must 007819-001 W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
accompany the returned device or component to W6300B1003 USB Inspector Connector
007819-002
assist and expedite finding the root cause of the (Inspector Monitor software included)
009207-001 Flame Inspector Monitor CD
failure. 103922-001 Model 475 HART Communicator
102740-002 Magnet
Pack the unit properly. Always use sufficient packing 008082-001 Magnet and Adapter for Extension Pole
007739-001 Magnet and Extension Pole
material. Where applicable, use an antistatic bag as oi Replacement kit for X3301 (5 Black reflector plates)
009208-001
protection from electrostatic discharge. with Inspector Connector and Monitor
010831-001 oi Replacement kit for X3301 (5 Stainless Steel reflector plates)
with Inspector Connector and Monitor
note 009208-003 oi Replacement kit for X3302 (5 Black reflector plates)
with Inspector Connector and Monitor
Det-Tronics reserves the right to apply a service oi Replacement kit for X3302 (5 Stainless Steel reflector plates)
010831-002
charge for repairing returned product damaged as with Inspector Connector and Monitor
a result of improper packaging. 009208-002 oi Replacement kit for X52/X22/X98 (5 reflector plates)
with Inspector Connector and Monitor
007307-001 Replacement oi reflector plate for X3301 with Black plate
(requires inspector connector to calibrate)
Return all equipment transportation prepaid to the factory Replacement oi reflector plate for X3301 with Stainless Steel
010830-001
in Minneapolis. plate (requires inspector connector to calibrate)
007307-003 Replacement oi reflector plate for X3302 with Black plate
(requires inspector connector to calibrate)
NOTE 010830-002 Replacement oi reflector plate for X3302 with Stainless Steel
plate (requires inspector connector to calibrate)
It is highly recommended that a complete spare
007307-002 Replacement oi reflector plate for X52/X22/X98
be kept on hand for field replacement to ensure (requires inspector connector to calibrate)
continuous protection. 007240-001 Q1116A1001, Air Shield (AL)
007818-001 Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
007818-002 Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
009177-001 Q1120A1001 Paint shield mounting ring (AL)
010857-001 Q1130A1001 Flange Mount Assembly for X3301 & X3302
009199-001 Q1198A1001 Dual Air Shield/Flange Mount (X9800 only)/(AL)
006097-001 Q1201 Laser
102871-001 Laser Battery, 3V Lithium (laser)
007255-001 Q1201C1001 X-Series Laser Holder (AL/Plastic)
007338-001 Q2000A1001 X-Series Weather Shield (AL)
007338-010 Q2033A10R X3301/X3302 FOV Limiter 10° (AL)
007338-020 Q2033A20R X3301/X3302 FOV Limiter 20° (AL)
007338-030 Q2033A30R X3301/X3302 FOV Limiter 30° (AL)
007912-010 Spare Restrictor Plate 10° (AL)
007912-020 Spare Restrictor Plate 20° (AL)
007912-030 Spare Restrictor Plate 30° (AL)
Q9033B Stainless Steel Swivel Mount Assembly is for
007290-001 aluminum and stainless steel detectors
Q9033A Aluminum Swivel Mount Assembly is for aluminum
007290-002 detectors only
011385-001 Q9033 Collar Attachment
101197-001 Stop Plug, 3/4 NPT, AL
101197-004 Stop Plug, 3/4 NPT, SS
103517-001 Stop Plug, AL, IP66, Ex d e, M25
101197-003 Stop Plug, SS, IP66, Ex d e, M25
010816-001 Stop Plug, 20PK, 3/4NPT, AL
010817-001 Stop Plug, 20PK, 3/4NPT, SS
010818-001 Stop Plug, 20PK, M25, AL
010819-001 Stop Plug, 20PK, M25, SS
103363-001 14 mm Hex Wrench (Steel)
103406-001 Screwdriver
107427-040 O-ring - Rear Cover (Viton)
005003-001 1 oz grease for detectors (non-silicon)
001680-001 Window cleaner (6 pack)
15.1 18 95-8527
X3301 MODEL MATRIX
MODEL DESCRIPTION
X3301 Multispectrum IR Flame Detector
TYPE MATERIAL
A Aluminum
S Stainless Steel (316)
TYPE THREAD TYPE
4M 4 PORT, METRIC M25
4N 4 PORT, 3/4" NPT
TYPE OUTPUTS
11 Relay
13 Relay and 4-20 mA
14 Eagle Quantum Premier (EQP)
15 Relay and Pulse
16 Addressable Module Only (Third Party Type)*
21 Relay-Automotive
22 EQP Automotive
23 HART, Relay and 4-20 mA
TYPE APPROVALS
A FM/CSA
T SIL/FM/CSA/ATEX/CE/IECEx
W FM/CSA/ULC**/ATEX/CE/IECEx
TYPE CLASSIFICATION
1 Division/Zone Ex d e
2 Division/Zone Ex d
*The Addressable Module Only (Type 16) is not FM approved.
**ULC approval applies to output types 11, 13, 15, 21, and 23.
15.1 19 95-8527
APPENDIX A
FM Approval and Performance Report
• Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA/Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
The Optical Integrity test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual,
is the approved external optical test method for this detector to verify end-to-end detector function. This test replaces
the function and need of a traditional external test lamp.
15.1 20 95-8527
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel Size Distance feet (m) Average Response Time (seconds)***
n-Heptane 1 x 1 foot 210 (64)* 11
n-Heptane** 1 x 1 foot 210 (64)* 6
n-Heptane 1 x 1 foot 100 (30.5) 3
n-Heptane 6 in. x 6 in. 80 (24.4) 3
Isopropanol 6 in. x 6 in. 70 (21.3) 4
Diesel** 1 x 1 foot 150 (45.7)* 14
Ethanol 1 x 1 foot 210 (64) 11
Methanol 6 in. x 6 in. 40 (12.2) 3
Methanol 1 x 1 foot 150 (45.7)* 18
Methanol** 1 x 1 foot 150 (45.7)* 7
Methane 30 inch plume 100 (30.5) 3
JP-5** 1 x 1 foot 150 (45.7)* 2
JP-5** 2 x 2 feet 210 (64)* 4
JP-5** 2 x 2 feet 100 (30.5) 2
Office Paper 0.5 lb. 19" x 19" x 8" 100 (30.5) 4
Corrugated Panel 18" x 36" 100 (30.5) 8
* Outdoor test condition.
** Pre-burn from ignition.
*** Add 2 seconds for EQP Model.
Medium Sensitivity
Fuel Size Distance feet (m) Average Response Time (seconds)***
n-Heptane 1 x 1 foot 100 (30.5) 12
n-Heptane 1 x 1 foot 50 (15.2) 2
Diesel** 1 x 1 foot 70 (21.3) 4
Ethanol 1 x 1 foot 85 (25.9) 13
Methanol 1 x 1 foot 70 (21.3) 10
Methane 30 inch plume 65 (19.8) 3
Methane 30 inch plume 55 (16.8) 2
JP-5** 2 x 2 feet 100 (30.5) 3
Office Paper 0.5 lb. 19" x 19" x 8" 50 (15.2) 6
Corrugated Panel 18" x 36" 50 (15.2) 2
** Pre-burn from ignition.
*** Add 2 seconds for EQP Model.
Low Sensitivity
Fuel Size Distance feet (m) Average Response Time (seconds)***
n-Heptane 1 x 1 foot 50 (15.2) 10
Methanol 1 x 1 foot 20 (6.1) 10
Methane 32 inch plume 15 (4.6) 9
*** Add 2 seconds for EQP Model.
15.1 21 95-8527
FM Approval and Performance Report – Continued
Medium Sensitivity
Distance Distance Average Response Time
False Alarm Source Fire Source
feet (m) feet (m) (seconds)***
Sunlight, direct, modulated, reflected — 6-inch propane 6 (1.8) <4
Vibration* N/A N/A N/A N/A
Radio frequency interference 1 (0.3) 6-inch propane 6 (1.8) <1
Arc welding, #7014 10 (3) 1 x 1 foot n-Heptane 40 (12.2) 4
6 kw heater, modulated 60 (18.3) 1 x 1 foot n-Heptane 60 (18.3) 2
6 kw heater, unmodulated 10 (3) 1 x 1 foot n-Heptane 60 (18.3) 2
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 1
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 1
500 w shielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 60 (18.3) 1
500 w unshielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 60 (18.3) 1
1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 60 (18.3) 6
Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 2
* Fire was verified with very high sensitivity only.
*** Add 2 seconds for EQP Model.
15.1 22 95-8527
FM Approval and Performance Report – Continued
Low Sensitivity
Distance Distance Average Response Time
False Alarm Source Fire Source
feet (m) feet (m) (seconds)***
Sunlight, direct, unmodulated, reflected* — 1 x 1 foot n-Heptane 35 (10.7) < 13
Sunlight, direct, modulated, reflected* — 1 x 1 foot n-Heptane 15 (4.6) < 14
Arc welding, steady, #7014 5 (1.5) 1 x 1 foot n-Heptane 50 (15.2) 11
Arc welding, modulated, #7014 5 (1.5) 1 x 1 foot n-Heptane 30 (9.1) 10
70 w sodium vapor, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 16
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 18
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 18
500 w shielded quartz halogen lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 12
500 w shielded quartz halogen lamp, modulated 10 (3) 1 x 1 foot n-Heptane 50 (15.2) 11
1500 w electric radiant heater, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 12
1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 30 (9.1) 11
Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 14
* Outdoor test conditions.
*** Add 2 seconds for EQP Model.
15.1 23 95-8527
FM Approval and Performance Report – Continued
Medium Sensitivity
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 10 (3) No alarm No alarm
6 kw heater 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm
Low Sensitivity
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration — No alarm No alarm
Radio frequency interference N/A No alarm N/A
Arc welding 5 (1.5) No alarm No alarm
6 kw heater 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm
15.1 24 95-8527
FM Approval and Performance Report – Continued
FIELD of view
Very High Sensitivity
Avg. Horiz. Avg. Vert.
Distance Horizontal Vertical
Fuel Size Response Time Response Time
feet (m) (degrees) (degrees)
(seconds)*** (seconds)***
150* +45 12 +45 13
n-Heptane 1 x 1 foot
(45.7) -45 14 -30 5
100 +45 6 +45 3
n-Heptane 1 x 1 foot
(30.5) -45 3 -30 2
80 +45 5 +45 4
n-Heptane 6 in. x 6 in.
(24.4) -45 6 -30 4
70 +45 5 +45 4
Isopropanol 6 in. x 6 in.
(21.3) -45 5 -30 6
100 +45 2 +45 4
Diesel** 1 x 1 foot
(30.5) -45 3 -30 3
150 +45 13 +45 10
Ethanol 1 x 1 foot
(45.7) -45 10 -30 8
40 +45 4 +45 3
Methanol 6 in. x 6 in.
(12.2) -45 6 -30 3
110 +45 9 +45 9
Methanol 1 x 1 foot
(33.5) -45 7 -30 3
30 inch 100 +45 7 +45 2
Methane
plume (30.5) -45 3 -30 2
100 +45 2 +45 3
JP-5** 1 x 1 foot
(30.5) -45 4 -30 2
180* +45 2 +45 3
JP-5** 2 x 2 feet
(54.9) -45 5 -30 2
90 +45 2 +45 1
JP-5** 2 x 2 feet
(27.4) -45 3 -30 2
80 +45 4 +45 2
Office Paper 0.5 lb. 19" x 19" x 8"
(24.4) -45 2 -30 1
80 +45 1 +45 3
Corrugated Panel 18" x 36"
(24.4) -45 1 -30 2
* Outdoor test condition.
** Pre-burn from ignition.
*** Add 2 seconds for EQP Model.
15.1 25 95-8527
FM Approval and Performance Report – Continued
Medium Sensitivity
Avg. Horiz. Avg. Vert.
Distance Horizontal Vertical
Fuel Size Response Time Response Time
feet (m) (degrees) (degrees)
(seconds)*** (seconds)***
75 +45 9 +45 10
n-Heptane 1 x 1 foot
(22.9) -45 6 -30 7
50 +45 4 +45 3
n-Heptane 1 x 1 foot
(15.2) -45 3 -30 3
60 +45 4 +45 4
Diesel** 1 x 1 foot
(18.3) -45 4 -30 2
60 +45 12 +45 12
Ethanol 1 x 1 foot
(18.2) -45 9 -30 9
50 +45 9 +45 9
Methanol 1 x 1 foot
(15.2) -45 3 -30 1
45 +45 3 +45 7
Methane 32 inch plume
(13.7) -45 3 -30 1
90 +45 4 +45 2
JP-5** 2 x 2 feet
(27.4) -45 2 -30 2
40 +45 2 +45 1
Office Paper 0.5 lb. 19" x 19" x 8"
(12.2) -45 1 -30 1
40 +45 2 +45 1
Corrugated Panel 18" x 36"
(12.2) -45 1 -30 1
** Pre-burn from ignition.
*** Add 2 seconds for EQP Model.
Low Sensitivity
Distance Horizontal Avg. Horiz. Response Vertical Avg. Vert. Response Time
Fuel Size
feet (m) (degrees) Time (seconds)*** (degrees) (seconds)***
35 +45 13 +45 9
n-Heptane 1 x 1 foot
(10.7) -45 13 -30 18
15 +45 14 +45 10
Methanol 1 x 1 foot
(4.6) -45 12 -30 8
15 +45 10 +45 8
Methane 32 inch plume
(4.6) -45 11 -30 10
*** Add 2 seconds for EQP Model.
15.1 26 95-8527
FM Approval and Performance Report – Continued
10 ft
30 ft
20 ft 30°
60 ft 30°
30 ft
90 ft
40 ft 15°
120 ft 15°
50 ft
150 ft 0°
0° 60 ft
180 ft 15° DETECTOR VERTICAL
DETECTOR VERTICAL FIELD OF VIEW
15° 70 ft
210 ft
FIELD OF VIEW 30° WITH DETECTOR AT
30° WITH DETECTOR AT 45° 45° FROM HORIZONTAL.
45° 45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet for
n-Heptane at Very High Sensitivity (1 x 1 foot) Field of View at Indicated Distance in Feet for
Isopropanol at Very High Sensitivity (6 in. x 6 in.)
0° 0°
15° 15° 15° 150 ft 15°
80 ft
30° 30° 30° 135 ft 30°
70 ft
120 ft
45° 60 ft 45° 45° 45°
105 ft
50 ft 90 ft
40 ft 75 ft
60 ft
30 ft
45 ft
20 ft 30 ft
10 ft 15 ft
15.1 27 95-8527
FM Approval and Performance Report – Continued
0° 0°
15° 210 ft 15° 15° 150 ft 15°
30° 30° 30° 135 ft 30°
180 ft
120 ft
45° 45°
45° 150 ft 45° 105 ft
120 ft 90 ft
75 ft
90 ft 60 ft
60 ft 45 ft
30 ft
15 ft
60 ft 30° 0°
15° 100 ft 15°
90 ft 30° 90 ft 30°
15° 80 ft
120 ft 45° 45°
70 ft
150 ft 60 ft
0° 50 ft
180 ft
DETECTOR VERTICAL 40 ft
15° FIELD OF VIEW
210 ft 30 ft
30° WITH DETECTOR AT
45° 45° FROM HORIZONTAL. 20 ft
10 ft
Field of View at Indicated Distance in Feet for
Ethanol at Very High Sensitivity (1 x 1 foot)
10 ft
0° 20 ft
15° 30°
40 ft 15° 30 ft
30° 30° 40 ft
35 ft
50 ft 15°
45° 30 ft 45°
60 ft
25 ft 70 ft
20 ft 0°
80 ft
15 ft 90 ft 15°
DETECTOR VERTICAL
FIELD OF VIEW
100 ft WITH DETECTOR AT
10 ft 30°
45° 45° FROM HORIZONTAL.
5 ft
Field of View at Indicated Distance in Feet for
Methane at Very High Sensitivity (30 inch plume)
0°
5 ft 15° 210 ft 15°
30° 30°
10 ft 30° 180 ft
15 ft 45° 150 ft 45°
20 ft 15° 120 ft
25 ft
90 ft
30 ft 0°
60 ft
35 ft DETECTOR VERTICAL
15° FIELD OF VIEW 30 ft
40 ft 30° WITH DETECTOR AT
45° 45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
Methanol at Very High Sensitivity (6 in. x 6 in.) JP-5 at Very High Sensitivity (2 x 2 feet)
15.1 28 95-8527
FM Approval and Performance Report – Continued
0° 0°
15° 100 ft 15° 15° 70 ft 15°
30° 90 ft 30° 30° 30°
60 ft
80 ft
45° 45°
70 ft 45° 50 ft 45°
60 ft
40 ft
50 ft
40 ft 30 ft
30 ft 20 ft
20 ft
10 ft 10 ft
Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
n-Heptane at Medium Sensitivity (1 x 1 foot) Methanol at Medium Sensitivity (1 x 1 foot)
0° 0°
15° 70 ft 15° 15° 65 ft 15°
30° 30° 60 ft 30°
60 ft 30°
30 ft 30 ft
20 ft 20 ft
10 ft 10 ft
Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
Diesel at Medium Sensitivity (1 x 1 foot) Methane at Medium Sensitivity (30 inch plume)
0° 0°
15° 85 ft 15° 15° 100 ft 15°
30° 80 ft 30° 30° 90 ft 30°
75 ft 80 ft
45° 45° 45° 45°
65 ft 70 ft
55 ft 60 ft
45 ft 50 ft
35 ft 40 ft
25 ft 30 ft
15 ft 20 ft
5 ft 10 ft
Field of View at Indicated Distance in Feet for Field of View at Indicated Distance in Feet for
Ethanol at Medium Sensitivity (1 x 1 foot) JP-5 at Medium Sensitivity (2 x 2 foot)
NOTE
FM Approvals minimum requirements are
response distance measurements at 0° (on
axis) and the limits of the field of view. These
high resolution field of view diagrams show the
measured response distances at all the indicated
angles in the horizontal plane.
15.1 29 95-8527
APPENDIX B
CSA Approval
PRODUCTS
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A);
Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C);
Class III; Enclosure Type 4X;
Multispectrum IR Flame Detector/Controller X3301 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts.
Relay contacts rated 30 Vdc, 5 Amps.
Note
Hazardous location testing has been successfully completed on the Model X3301 series from an ambient
temperature range of –55°C to +125°C; however, the detector label marking indicates –40°C to +75°C.
APPLICABLE REQUIREMENTS
CSA Std C22.2 No. 25-1966 – Enclosures for use in Class II Groups E, F & G Hazardous Locations.
CSA Std C22.2 No. 30-M1986 – Explosion-Proof Enclosures for use in Class I Hazardous Locations.
CAN/CSA C22.2 No. 94-M91 – Special Purpose Enclosures.
CSA Std C22.2 No. 142-M1987 – Process Control Equipment.
CSA Std C22.2 No. 213-M1987 – Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations.
15.1 30 95-8527
APPENDIX C
ATEX / CE Approval
Compliance with:
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-31: 2009
EN / IEC 60529: 2001.
Installation instructions
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring diameter from 14 AWG
(2.08 mm2) to 22 AWG (0.33 mm2).
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given by the
manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
15.1 31 95-8527
NOTE
Operational performance verified from –40°C to +75°C.
Note
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be
certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof
enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66 for the apparatus. Unused apertures shall be closed with suitable blanking
elements.
Note
For ATEX installations, the X3301 detector housing must be electrically connected to earth ground.
15.1 32 95-8527
APPENDIX D
IECEx Approval
Installation instructions
The field wiring connections in the terminal compartment are suitably certified and accepts wiring diameter from 14 AWG
(2.08 mm2) to 22 AWG (0.33 mm2).
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given by the
manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d" or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e".
They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected to
earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts.
The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk of
mechanical damage.
15.1 33 95-8527
APPENDIX E
VdS Schadenverhütung GmbH Approval
VdS
0786
EC-Certificate of Conformity
08 0786 – CPD – 20453
EN54-10 Flame detectors - Point detectors.
BASIS OF APPROVAL
DIN EN 54, Part 10 (05/02) - Flame Detectors.
15.1 34 95-8527
APPENDIX F
Offshore ApprovalS
DNV
Type Approval Certificate No. A-11022.
MED
Certificate No. MED-B-5872.
Is found to comply with the requirements in the following Regulations / Standards:
Annex A.1, item No. A.1/3.51 and Annex B, Module B in the Directive. SOLAS 74 as amended, Regulation II-2/7 & X/3, 2000 HSC
Code 7, FSS Code 9 and IMO MSC.1/Circ. 1242.
The equipment are found to comply with following location / application dependent requirements (for definition of each of the
location classes, see below the table):
Lloyd's Register
Type Approval Certificate No. 09/00027.
Models Available: Relay output, relay 0-20 mA output, and EQP LON output versions.
15.1 35 95-8527
APPENDIX G
Additional Approvals
SIL 2
IEC 61508
Certified SIL 2 Capable. Certificate DET070417 COO1
Applies to specific models – refer to the SIL 2 Certified X3301 Safety Manual (95-8582) for details.
FRENCH
I C AT I O N
RTIF
CE
R
O
FN
A
R
PA
NF-SSI
AFNOR Identification No: LIR 007 A0.
www.marque-nf.com
15.1 36 95-8527
APPENDIX H
Approved ACCESSORIES
15.1 37 95-8527
95-8527
T: 952.941.5665 or 800.765.3473
F: 952.829.8750
W: http://www.det-tronics.com
X3301 Multispectrum PointWatch Eclipse® FlexVu® Universal Display Eagle Quantum Premier®
IR Flame Detector IR Combustible Gas Detector w/ GT3000 Toxic Gas Detector Safety System E: det-tronics@det-tronics.com
Det-Tronics, the DET-TRONICS logo, Protect•IR, and Automatic Optical Integrity (oi) are registered trademarks or trademarks of Detector Electronics
Corporation in the United States, other countries, or both. Other company, product, or service names may be trademarks or service marks of others.